6. Refrigerant Pipe Installation
6. Refrigerant Pipe Installation
6.1
Maximum length and drop height
Ensure that the length of the refrigerant pipe, the number
of bends, and the drop height between the indoor and
outdoor units meets the requirements shown in the
following table.
For North America, Australia and Europe 3D Inverter
models:
Capacity(k
Btu/h
)
Max. Length
(m/ft)
Max. Elevation
(m/ft)
<15
25/82
10/32.8
15-23
30/98.4
20/65.6
24~35
50/164
25/82
36~60
65/213.3
30/98.4
For other models:
Capacity(k
Btu/h
)
Max. Length
(m/ft)
Max. Elevation
(m/ft)
12
15/49
8/26
18-24
25/82
15/49
30-36
30/98.4
20/65.6
42~60
50/164
30/98.4
Caution:
1. The capacity test is based on the standard length and
the maximum permissive length is based on the system
reliability.
2. Oil traps
If the indoor unit is installed higher than the outdoor unit:
-If oil flows back into the outdoor unit’s compressor, this
might cause liquid compression or deterioration of oil
return. Oil traps in the rising gas piping can prevent this.
An oil trap should be installed every 10m(32.8ft) of vertical
suction line riser.
The indoor unit is installed higher than the outdoor unit
If the outdoor unit is installed higher than the indoor unit:
-It is recommended that vertical suction risers not be
upsized. Proper oil return to the compressor should be
maintained with suction gas velocity. If velocities drop
below 7.62m/s(1500fpm (feet per minute)), oil return
will be decreased. An oil trap should be installed every
6m(20ft) of vertical suction line riser.
The outdoor unit is installed higher than the indoor unit
Содержание MUEU-18HRFNX-QRD0W
Страница 1: ...LIGHT COMMERCIAL INVERTER SERIES SM_LC GA _R410A_R32_3D INV_EU_NA_1811 SERVICE MANUAL...
Страница 2: ......
Страница 5: ......
Страница 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Страница 12: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Страница 14: ...Model Reference 3 2 External Appearance 2 1 Indoor Unit Compact Four way Cassette A6 Duct Floor Ceiling...
Страница 15: ...Model Reference 4 2 2 Outdoor Unit Outdoor Unit...
Страница 19: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Страница 21: ...IDU Compact Cassette 6 4 Service Place...
Страница 24: ...IDU Compact Cassette 9 Heating airflow velocity distributions Heating temperature distributions...
Страница 26: ...IDU Compact Cassette 11 Heating airflow velocity distributions Heating temperature distributions...
Страница 44: ...Outdoor Unit 3 Panel Plate B30...
Страница 45: ...Outdoor Unit 4 Panel Plate BA30...
Страница 46: ...Outdoor Unit 5 Panel Plate CA30...
Страница 47: ...Outdoor Unit 6 Panel Plate D30...
Страница 48: ...Outdoor Unit 7 Panel Plate E30...
Страница 49: ...Outdoor Unit 8 Panel Plate 590...
Страница 50: ...Outdoor Unit 9 2 Service Place...
Страница 62: ...Outdoor unit printed circuit board diagram 17122000002718...