Service manual
27
8.8
Evacuation
Procedure:
1. Connect the vacuum pump to the charge set’s centre hose.
2. Evacuation for approximately one hour.
§
Confirm that the gauge needle has moved toward -0.1 Mpa (-76 cmHg) [vacuum of 4 mmHg or less].
3. Close the valve (Low side) on the charge set, turn off the vacuum pump, and confirm that the
gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
4. Disconnect the charge hose from the vacuum pump.
§
Vacuum pump oil, if the vacuum pump oil becomes dirty or depleted, replenish as needle.
Содержание MSH-07CR
Страница 1: ...Cover MSH 07CR MSH 07HR MSH 09CR MSH 09HR MSH 12CR MSH 12HR MSH 16CR MSH 16HR MSH 18CR ...
Страница 10: ...Service manual 9 5 Refrigerant cycle diagram Ø Cooling only Ø Heat pump mode ...
Страница 12: ...Service manual 12 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram ...
Страница 13: ...Service manual 13 7 2 Wiring diagram 7 2 1 MSH 07CR MSH 09CR ...
Страница 14: ...Service manual 14 ...
Страница 15: ...Service manual 15 7 2 2 MSH 12CR ...
Страница 16: ...Service manual 16 7 2 3 MSH 16CR ...
Страница 17: ...Service manual 17 7 2 4 MSH 18CR ...
Страница 18: ...Service manual 18 7 2 4 MSH 07HR MSH 09HR ...
Страница 19: ...Service manual 19 7 2 5 MSH12HR ...
Страница 20: ...Service manual 20 7 2 6 MSH 16HR ...