MLCAC-UTSM-2010-10
Point Check Function
Outdoor Units 87
8.
Point Check Function
There is a check switch in outdoor PCB.
Push the switch SW1 to check the states of unit when the unit is running. The digital display tube will display
the follow procedure when push SW1 each time.
For units except model MOU-12HDN1:
Display Remark
00
Normal display
Display running frequency, running state or malfunction code
01
Indoor unit capacity demand code
Actual data*HP*10
If capacity demand code is higher than 99, the digital display
tube will show single digit and tens digit. (For example, the
digital display tube show “5.0”,it means the capacity demand
is 15. the digital display tube show “60”,it means the capacity
demand is 6.0)
02
Amendatory capacity demand code
03
The frequency after the capacity requirement
transfer
04
The frequency after the frequency limit
05
The frequency of sending to 341
06
Indoor unit evaporator outlet temp.(T2)
If the temp. is lower than 0 degree, the digital display tube will
show “0”.If the temp. is higher than 70 degree, the digital
display tube will show “70”.
07
Condenser pipe temp.(T3)
If the temp. is lower than -9 degree, the digital display tube will
show “-9”.If the temp. is higher than 70 degree, the digital
display tube will show “70”. If the indoor unit is not connected,
the digital display tube will show:
“――”
08
Outdoor ambient temp.(T4)
09
Compressor discharge temp.(Tp)
The display value is between 30~120 degree. If the temp. is
lower than 30 degree, the digital display tube will show “30”.If
the temp. is higher than 99 degree, the digital display tube will
show single digit and tens digit. (For example, the digital
display tube show “0.5”,it means the compressor discharge
temp. is 105 degree. the digital display tube show “1.6”,it
means the compressor discharge temp. is 116 degree)
10
AD value of current
The display value is hex number.
11
AD value of voltage
12
Indoor unit running mode code
Off:0, Fan only 1,Cooling:2, Heating:3, Forced cooling:4
13
Outdoor unit running mode code
14
EXV open angle
Actual data/4.
If the value is higher than 99, the digital display tube will show
single digit and tens digit.
For example ,the digital display tube show “2.0”,it means the
EXV open angle is 120
×
4=480p.)
15
Frequency limit symbol
Bit7
0
The display value is hex
number. For example,
the digital display tube
show 2A,then Bit5=1,
Bit3=1, Bit1=1.
It means frequency limit
caused by T4,T3 and
current.
Bit6
0
Bit5
Frequency limit
caused by T4.
Bit4
Frequency limit
caused by T2.
Bit3
Frequency limit
caused by T3.
Bit2
Frequency limit
caused by Tp.
Bit1
Frequency limit
caused by current
Bit0
Frequency limit
caused by voltage
Содержание MOU-12HDN1
Страница 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2012...
Страница 2: ......
Страница 4: ......
Страница 14: ...Dimensions MLCAC UTSM 2010 10 10 New Four way Cassette Compact 2 Dimensions 3 Service Space...
Страница 19: ...MLCAC UTSM 2010 10 Field Wiring New Four way Cassette Compact 15 10 Field Wiring MCA2 12HRDN1 Q MCA2 18HRDN1 Q...
Страница 20: ...Field Wiring MLCAC UTSM 2010 10 16 New Four way Cassette Compact MCA2 12HRDN1 Q MCA2 18HRDN1 Q...
Страница 26: ...Service Space MLCAC UTSM 2010 10 22 Four way Cassette Type 3 Service Space For 18 48k For 60k...
Страница 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Four way Cassette Type 9 The Specification of Power...
Страница 33: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 29 10 Field Wiring Wiring chart...
Страница 34: ...Field Wiring MLCAC UTSM 2010 10 30 Four way Cassette Type...
Страница 45: ...MLCAC UTSM 2010 10 The Specification of Power Duct Type 41 9 The Specification of Power...
Страница 46: ...Field Wiring MLCAC UTSM 2010 10 42 Duct Type 10 Field Wiring...
Страница 47: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 43 Air conditioner link circuit...
Страница 48: ...Field Wiring MLCAC UTSM 2010 10 44 Duct Type...
Страница 53: ...MLCAC UTSM 2010 10 Service Space Ceiling Floor Type 49 3 Service Space...
Страница 54: ...Wiring Diagrams MLCAC UTSM 2010 10 50 Ceiling Floor Type 4 Wiring Diagrams MUB 12HRDN1...
Страница 62: ...Field Wiring MLCAC UTSM 2010 10 58 Ceiling Floor Type 10 Field Wiring...
Страница 63: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 59 For model 12...
Страница 64: ...Field Wiring MLCAC UTSM 2010 10 60 Ceiling Floor Type For model 18 60...
Страница 66: ......
Страница 68: ...Dimensions MLCAC UTSM 2010 10 64 Console Type 2 Dimensions MFA 12HRDN1 MFA 18HRDN1...
Страница 69: ...MLCAC UTSM 2010 10 Service Space Console Type 65 3 Service Space...
Страница 75: ...MLCAC UTSM 2010 10 The Specification of Power Console Type 71 9 The Specification of Power...
Страница 76: ...Field Wiring MLCAC UTSM 2010 10 72 Console Type 10 Field Wiring...
Страница 77: ...MLCAC UTSM 2010 10 Field Wiring Console Type 73...
Страница 81: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 77 2 Service Space...
Страница 83: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams MOU 12HDN1...
Страница 84: ...Wiring Diagrams MLCAC UTSM 2010 10 80 Outdoor Units MOUA 18HDN1 C0 MOUB 24HDN1...
Страница 85: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 81 MOU 30HDN1 MOUB 36HDN1 Q MOU 48HDN1...
Страница 86: ...Wiring Diagrams MLCAC UTSM 2010 10 82 Outdoor Units MOUB 36HDN1 R MOUB 48HDN1 R MOUD 60HDN1 R...
Страница 87: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 83 MOUA 60HRDN1...
Страница 108: ...Troubleshooting MLCAC UTSM 2010 10 104 Outdoor Units 10 3 2 10 P0 malfunction...
Страница 109: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 105 10 3 2 11 P1 malfunction Only for 30K 60K...
Страница 110: ...Troubleshooting MLCAC UTSM 2010 10 106 Outdoor Units 10 3 2 12 P2 malfunction Only for 30K 60K...
Страница 111: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 107 10 3 2 13 P3 malfunction...
Страница 130: ...Control MLCAC UTSM 2010 06 126 Control Part 5 Control 1 Wireless Remote Controller 127...