Precaution on Installation
MLCAC-UTSM-2010-10
116
Installation
1. Precaution on Installation
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity.
Maximum pipe length
Model
Max. Length
Max. Elevation
12,000Btu/h 15m
8m
18,000Btu/h ~24,000Btu/h
25m
12m
30,000Btu/h 25m
15m
36,000Btu/h 30m
20m
48,000Btu/h~60,000Btu/h 50m
25m
Piping sizes
Model Liquid(mm)
Gas(mm)
12,000Btu/h~18,000Btu/h 6.35
12.7
24,000Btu/h~60,000Btu/h
9.52 15.9
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ
6.35
14.2
~
17.2N.m
(144
~
176 kgf.cm)
8.3 8.7
Φ
9.52
32.7
~
39.9N.m
(333
~
407kgf.cm)
12.0 12.4
Φ
12.7
49.5
~
60.3N.m
(504
~
616kgf.cm)
15.4 15.8
Φ
15.9
61.8
~
75.4N.m
(630
~
770 kgf.cm)
18.6 19.1
Φ
19
97.2
~
118.6N.m
(990
~
1210kgf.cm)
22.9 23.3
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part
of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other
impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
2) Locate
The
Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by
condensation.
c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in
fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
Содержание MOU-12HDN1
Страница 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2012...
Страница 2: ......
Страница 4: ......
Страница 14: ...Dimensions MLCAC UTSM 2010 10 10 New Four way Cassette Compact 2 Dimensions 3 Service Space...
Страница 19: ...MLCAC UTSM 2010 10 Field Wiring New Four way Cassette Compact 15 10 Field Wiring MCA2 12HRDN1 Q MCA2 18HRDN1 Q...
Страница 20: ...Field Wiring MLCAC UTSM 2010 10 16 New Four way Cassette Compact MCA2 12HRDN1 Q MCA2 18HRDN1 Q...
Страница 26: ...Service Space MLCAC UTSM 2010 10 22 Four way Cassette Type 3 Service Space For 18 48k For 60k...
Страница 32: ...The Specification of Power MLCAC UTSM 2010 10 28 Four way Cassette Type 9 The Specification of Power...
Страница 33: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 29 10 Field Wiring Wiring chart...
Страница 34: ...Field Wiring MLCAC UTSM 2010 10 30 Four way Cassette Type...
Страница 45: ...MLCAC UTSM 2010 10 The Specification of Power Duct Type 41 9 The Specification of Power...
Страница 46: ...Field Wiring MLCAC UTSM 2010 10 42 Duct Type 10 Field Wiring...
Страница 47: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 43 Air conditioner link circuit...
Страница 48: ...Field Wiring MLCAC UTSM 2010 10 44 Duct Type...
Страница 53: ...MLCAC UTSM 2010 10 Service Space Ceiling Floor Type 49 3 Service Space...
Страница 54: ...Wiring Diagrams MLCAC UTSM 2010 10 50 Ceiling Floor Type 4 Wiring Diagrams MUB 12HRDN1...
Страница 62: ...Field Wiring MLCAC UTSM 2010 10 58 Ceiling Floor Type 10 Field Wiring...
Страница 63: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 59 For model 12...
Страница 64: ...Field Wiring MLCAC UTSM 2010 10 60 Ceiling Floor Type For model 18 60...
Страница 66: ......
Страница 68: ...Dimensions MLCAC UTSM 2010 10 64 Console Type 2 Dimensions MFA 12HRDN1 MFA 18HRDN1...
Страница 69: ...MLCAC UTSM 2010 10 Service Space Console Type 65 3 Service Space...
Страница 75: ...MLCAC UTSM 2010 10 The Specification of Power Console Type 71 9 The Specification of Power...
Страница 76: ...Field Wiring MLCAC UTSM 2010 10 72 Console Type 10 Field Wiring...
Страница 77: ...MLCAC UTSM 2010 10 Field Wiring Console Type 73...
Страница 81: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 77 2 Service Space...
Страница 83: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams MOU 12HDN1...
Страница 84: ...Wiring Diagrams MLCAC UTSM 2010 10 80 Outdoor Units MOUA 18HDN1 C0 MOUB 24HDN1...
Страница 85: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 81 MOU 30HDN1 MOUB 36HDN1 Q MOU 48HDN1...
Страница 86: ...Wiring Diagrams MLCAC UTSM 2010 10 82 Outdoor Units MOUB 36HDN1 R MOUB 48HDN1 R MOUD 60HDN1 R...
Страница 87: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 83 MOUA 60HRDN1...
Страница 108: ...Troubleshooting MLCAC UTSM 2010 10 104 Outdoor Units 10 3 2 10 P0 malfunction...
Страница 109: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 105 10 3 2 11 P1 malfunction Only for 30K 60K...
Страница 110: ...Troubleshooting MLCAC UTSM 2010 10 106 Outdoor Units 10 3 2 12 P2 malfunction Only for 30K 60K...
Страница 111: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 107 10 3 2 13 P3 malfunction...
Страница 130: ...Control MLCAC UTSM 2010 06 126 Control Part 5 Control 1 Wireless Remote Controller 127...