31
5). Disconnect the charge hose from the vacuum pump.
2. Refrigerant charging
Procedure:
1). Connect the charge hose to the charging cylinder, open the 2-way valve and the 3-way valve.
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of
the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the
air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
If the system cannot be charge with the specified amount of refrigerant, or can be charged with a little at
a time (approximately 150g each time) , operating the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5).When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way
valve’s service port immediately.
If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air
conditioner before disconnecting the hose.
Electronic scale
Содержание MOA-11HN1-QB8
Страница 1: ...LUNA ON OFF SERIES Service Manual 2014 9ASEU B1 1401...
Страница 16: ...14 MS9A 12HRN1 QC7G...
Страница 17: ...15 MS9A 18HRN1 QC5...
Страница 18: ...16 MS9A 24HRN1 QB8W...
Страница 20: ...18 MOC 17HN1 QC0...
Страница 21: ...19 MOC 18HN1 QC0 MOF3 18HN1 QC5...
Страница 22: ...20 MOP 24HN1 QB8W...
Страница 23: ...21 MOF1 24HN1 QB8W...