Insulation Work
Installation
99
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
6.3.2 Water discharge test
1. Natural drainage mode(the indoor unit with outdoor drainage pump)
Infuse above 600ml water through water test hole slowly into the water collector, observe whether the
water can discharge through the transparent hard pipe at drainage outlet.
2. Pump drainage mode
2.1 Disconnect the plug of water level switch, remove the cover of water test hole and slowly infuse about
2000ml water through the water test hole, be sure that the water will not touch the motor of drainage
pump.
2.2 Power on and let the air conditioner operate for cooling. Check operation status of drainage pump, and
then connect the plug of water level switch, check the operation sound of water pump and observe
whether the water can discharge through the transparent hard pipe at drainage outlet.
(In light of the
length of drainage pipe, water shall be discharged about 1 minute delayed)
2.3 Stop the operation of air conditioner, power off the power supply and put the cover of water test hole
back to the original place.
a. After stopped the air conditioner 3 minutes, check whether there is anything abnormal. If drainage pipes
have not been distributed properly, over back-flow water shall cause the flashing of alarm indicator at
remote-controlled receiving board and even water shall run over the water collector.
b. Continuously infusing water until water level alarmed, check whether the drainage pump could
discharge water at once. If water level does not decline under warning water level 3 minutes later, it
Содержание MHF-18HWN1-Q
Страница 1: ...Contents i R410A ON OFF SERIES Service Manual 2013 LEUS B 1306...
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Duct Type 3 Service Space Ensure enough space required for installation and maintenance...
Страница 17: ...Wiring Diagrams Duct Type 13 4 Wiring Diagrams MHF 18HWN1 Q...
Страница 18: ...Wiring Diagrams 14 Duct Type MHF 24HWN1 Q...
Страница 19: ...Wiring Diagrams Duct Type 15 MHF 30HWN1 Q MHF 36HWN1 Q...
Страница 20: ...Wiring Diagrams 16 Duct Type MHF 30HWN1 R MHF 36HWN1 R MHF 48HWN1 R MHF 60HWN1 R...
Страница 21: ...Wiring Diagrams Duct Type 17...
Страница 27: ...Field Wiring Duct Type 23 10 Field Wiring MHF 18HWN1 Q...
Страница 32: ...Service Space 28 Ceiling Floor Type 3 Service Space...
Страница 33: ...Wiring Diagrams Ceiling Floor Type 29 4 Wiring Diagrams MUE 36HRN1 Q...
Страница 34: ...Wiring Diagrams 30 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Страница 37: ...Field Wiring Ceiling Floor Type 33 9 Field Wiring MUE 36HRN1 Q...
Страница 38: ...Field Wiring 34 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Страница 44: ...Dimensions 40 Super slim Cassette Type 2 Dimensions Model A H 18 30 205 235 36 48 245 275 60 287 317...
Страница 45: ...Service Space Super slim Cassette Type 41 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 46: ...Wiring Diagrams 42 Super slim Cassette Type 4 Wiring Diagrams MCD 18HRN1 Q...
Страница 47: ...Wiring Diagrams Super slim Cassette Type 43 MCD 24HDN1 Q...
Страница 48: ...Wiring Diagrams 44 Super slim Cassette Type MCD 36HDN1 R...
Страница 49: ...Wiring Diagrams Super slim Cassette Type 45 MCD 48HDN1 R MCD 60HDN1 R...
Страница 54: ...Field Wiring 50 Super slim Cassette Type 9 Field Wiring MCD 18HRN1 Q...
Страница 55: ...Field Wiring Super slim Cassette Type 51 MCD 24HRN1 Q MCD 36HRN1 R MCD 48HRN1 R MCD 60HRN1 R...
Страница 60: ...Wiring Diagrams 56 High Static Pressure Duct Type 4 Wiring Diagrams MHG 24HWN1 Q...
Страница 61: ...Static Pressure High Static Pressure Duct Type 57 5 Static Pressure 24 000Btu h...
Страница 66: ...Field Wiring 62 High Static Pressure Duct Type 10 Field Wiring MHG 24HWN1 Q...
Страница 73: ...Wiring Diagrams Outdoor Units 69 4 Wiring Diagrams MOU 18HN1 Q...
Страница 74: ...Wiring Diagrams 70 Outdoor Units MOU 24HN1 Q MOU 30HN1 Q...
Страница 75: ...Wiring Diagrams Outdoor Units 71 MOU 30HN1 R MOU 36HN1 Q...
Страница 76: ...Wiring Diagrams 72 Outdoor Units MOU 36HN1 R...
Страница 77: ...Wiring Diagrams Outdoor Units 73 MOU 48HN1 R...
Страница 78: ...Wiring Diagrams 74 Outdoor Units MOUA 60HN1 R...