Drainage pipe installation
98
Installation
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
6.2.8 Blowhole setting
For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
Содержание MHF-18HWN1-Q
Страница 1: ...Contents i R410A ON OFF SERIES Service Manual 2013 LEUS B 1306...
Страница 2: ......
Страница 4: ......
Страница 16: ...Service Space 12 Duct Type 3 Service Space Ensure enough space required for installation and maintenance...
Страница 17: ...Wiring Diagrams Duct Type 13 4 Wiring Diagrams MHF 18HWN1 Q...
Страница 18: ...Wiring Diagrams 14 Duct Type MHF 24HWN1 Q...
Страница 19: ...Wiring Diagrams Duct Type 15 MHF 30HWN1 Q MHF 36HWN1 Q...
Страница 20: ...Wiring Diagrams 16 Duct Type MHF 30HWN1 R MHF 36HWN1 R MHF 48HWN1 R MHF 60HWN1 R...
Страница 21: ...Wiring Diagrams Duct Type 17...
Страница 27: ...Field Wiring Duct Type 23 10 Field Wiring MHF 18HWN1 Q...
Страница 32: ...Service Space 28 Ceiling Floor Type 3 Service Space...
Страница 33: ...Wiring Diagrams Ceiling Floor Type 29 4 Wiring Diagrams MUE 36HRN1 Q...
Страница 34: ...Wiring Diagrams 30 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Страница 37: ...Field Wiring Ceiling Floor Type 33 9 Field Wiring MUE 36HRN1 Q...
Страница 38: ...Field Wiring 34 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Страница 44: ...Dimensions 40 Super slim Cassette Type 2 Dimensions Model A H 18 30 205 235 36 48 245 275 60 287 317...
Страница 45: ...Service Space Super slim Cassette Type 41 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Страница 46: ...Wiring Diagrams 42 Super slim Cassette Type 4 Wiring Diagrams MCD 18HRN1 Q...
Страница 47: ...Wiring Diagrams Super slim Cassette Type 43 MCD 24HDN1 Q...
Страница 48: ...Wiring Diagrams 44 Super slim Cassette Type MCD 36HDN1 R...
Страница 49: ...Wiring Diagrams Super slim Cassette Type 45 MCD 48HDN1 R MCD 60HDN1 R...
Страница 54: ...Field Wiring 50 Super slim Cassette Type 9 Field Wiring MCD 18HRN1 Q...
Страница 55: ...Field Wiring Super slim Cassette Type 51 MCD 24HRN1 Q MCD 36HRN1 R MCD 48HRN1 R MCD 60HRN1 R...
Страница 60: ...Wiring Diagrams 56 High Static Pressure Duct Type 4 Wiring Diagrams MHG 24HWN1 Q...
Страница 61: ...Static Pressure High Static Pressure Duct Type 57 5 Static Pressure 24 000Btu h...
Страница 66: ...Field Wiring 62 High Static Pressure Duct Type 10 Field Wiring MHG 24HWN1 Q...
Страница 73: ...Wiring Diagrams Outdoor Units 69 4 Wiring Diagrams MOU 18HN1 Q...
Страница 74: ...Wiring Diagrams 70 Outdoor Units MOU 24HN1 Q MOU 30HN1 Q...
Страница 75: ...Wiring Diagrams Outdoor Units 71 MOU 30HN1 R MOU 36HN1 Q...
Страница 76: ...Wiring Diagrams 72 Outdoor Units MOU 36HN1 R...
Страница 77: ...Wiring Diagrams Outdoor Units 73 MOU 48HN1 R...
Страница 78: ...Wiring Diagrams 74 Outdoor Units MOUA 60HN1 R...