![Midea MGRH10A-PA1Z Скачать руководство пользователя страница 88](http://html1.mh-extra.com/html/midea/mgrh10a-pa1z/mgrh10a-pa1z_manual_1790912088.webp)
Aqua Mini Full DC Inverter Unitary Chiller 50Hz
88
P4:
Compressor
discharged
temperature
protection
When the discharged temperature of the compressor is higher than 115°C, the unit will stop running. When the
discharged temperature of the compressor is lower than 83°C , the unit resumes normal operation automatically.
LED displays P4
Discharged temperature protection of the compressor
Check whether the discharged temperature of the compressor is higher than 115°C.
NO
Check whether the compressor discharged
temperature sensor connects with PCB correctly
according to the wiring diagram.
YES
Check whether resistance of compressor discharged
temperature sensor is correct or not .
NO
Connect correctly again.
YES
Replace outdoor main PCB
Whether the discharged temperature sensor is damaged or not.
NO
Replace compressor discharged
temperature sensor.
Check refrigerant leaks or not.
Stop leaking and then add the refrigerant again.
YES
YES
Содержание MGRH10A-PA1Z
Страница 16: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 16 7 Wiring Diagram MGRH5A PA1Z MGRH7A PA1Z...
Страница 17: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 17 MGRH10A PA1Z...
Страница 18: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 18 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...
Страница 29: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 29 MGRH12A PA3Z MGRH14A PA3Z...
Страница 30: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 30 MGRH16A PA3Z...
Страница 32: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 32 13 Exploded View MGRH5A PA1Z MGRH7A PA1Z...
Страница 34: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 34 MGRH10A PA1Z...
Страница 36: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 36 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...