Aqua Mini Full DC Inverter Unitary Chiller 50Hz
43
Evaporator
Recirculation
For minimum chilled water flow rate
For maximum chilled water flow rate
Evaporator
Recirculation
Maximum chilled water flow
The maximum chilled water flow is limited by the permitted pressure drop in the evaporator. It is provided in
the below table.
If the system flow is more than the maximum unit flow rate, bypass the evaporator as shown in the diagram
to obtain a lower evaporator flow rate.
Minimum and maximum water flow rates
Item
Water flow rate(m
3
/h)
Model
Minimum
Maximum
MGRH5A-PA1Z
0.77
0.95
MGRH7A-PA1Z
1.08
1.32
MGRH10A-PA1Z
1.54
1.89
MGRH12A-PA3Z
1.72
2.11
MGRH14A-PA3Z
1.93
2.36
MGRH16A-PA3Z
2.24
2.73
g). Design of expansion tank
If a closed expansion tank with its filled volume of air is too small, the system pressure will easily exceed the
maximum allowable pressure and cause water to discharge from the pressure relief valve, thus wasting
water. If the closed tank is too large, when the water temperature drops, the system pressure may decrease
to a level below the minimum allowable value and cause trouble in the air vent. Therefore, accurate sizing of
a closed expansion tank is essential.
For diaphragm expansion tanks, the minimum volume of the water tank, Vt, gal(m3),can be calculated by the
following formula, recommended by ASHRAE Handbook 1996, HVAC Systems and Equipment:
V
t
=V
s
v
2
/v
1
-1-3
α
(T
2
-T
1
)
1-p
1
/p
2
T
1
=lower temperature,
o
F (
℃
)
T
2
=higher temperature,
o
F (
℃
)
V
s
=volume of water in system, gal(m
3
)
p
1
=absolute pressure at lower temperature,psia(kPa abs.)
p
2
=absolute pressure at higher temperature,paia(kPa abs.)
v
1
,v
2
=specific volume of water at lower and higher temperature, respectively, ft
3
/lb(m
3
/kg)
α
=linear coefficient of thermal expansion; for steel,
α
=6.5x10
-6
in./in
·
o
F(1.2x10
-5
per
℃
); for copper,
α
=9.5x10
-6
in./in
·
o
F(1.7x10
-5
per
℃
)
In a chilled water system, the higher temperature T2 is the highest anticipated ambient temperature when
Содержание MGRH10A-PA1Z
Страница 16: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 16 7 Wiring Diagram MGRH5A PA1Z MGRH7A PA1Z...
Страница 17: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 17 MGRH10A PA1Z...
Страница 18: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 18 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...
Страница 29: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 29 MGRH12A PA3Z MGRH14A PA3Z...
Страница 30: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 30 MGRH16A PA3Z...
Страница 32: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 32 13 Exploded View MGRH5A PA1Z MGRH7A PA1Z...
Страница 34: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 34 MGRH10A PA1Z...
Страница 36: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 36 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...