E6 malfunction: DC fan motor malfunction
LED displays E6
Outdoor unit DC fan cannot work.
Refers to the wiring diagram to check whether
the unit wiring is correct or not.
NO
Connect again.
YES
Check whether the power and voltage of the DC
fan motor is normal or not and whether the
voltage between red and black terminal of DC
motor is from 277V to 354V in waiting state.
是
YES
Check whether the power and voltage of the DC fan
motor is normal or not and whether the voltage between
white and black terminal of DC motor is from 15V in
waiting state.
NO
Replace IPM module.
Replace the main PCB.
YES
Whether the outdoor fan will work after the indoor fan
operates for 3 minutes.
NO
Check the voltage
between “+”,”-” port
of PFC module is within
277-354V.
Replace PFC
module board..
NO
NO
Check voltage
between yellow
and black
terminal of the
fan is over 2.4V
Replace fan.
YES
NO
YES
YES
Содержание MGRH10A-PA1Z
Страница 16: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 16 7 Wiring Diagram MGRH5A PA1Z MGRH7A PA1Z...
Страница 17: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 17 MGRH10A PA1Z...
Страница 18: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 18 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...
Страница 29: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 29 MGRH12A PA3Z MGRH14A PA3Z...
Страница 30: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 30 MGRH16A PA3Z...
Страница 32: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 32 13 Exploded View MGRH5A PA1Z MGRH7A PA1Z...
Страница 34: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 34 MGRH10A PA1Z...
Страница 36: ...Aqua Mini Full DC Inverter Unitary Chiller 50Hz 36 MGRH12A PA3Z MGRH14A PA3Z MGRH16A PA3Z...