5
Table 5-2 (10/12KW)
No.
Fault or protection type
Recovery mode
Error code
1
Communication fault between main control board and communication
terminals block
Recoverable
C0
2
IDU communication error
Recoverable
E2
3
T3 or T4 temperature sensor error
Recoverable
E4
4
Input voltage protection
Recoverable
E5
5
DC fan protection
Recoverable
E6
6
EEPROM error
Unrecoverable
E9
7
Wrong compressor parameters
Unrecoverable
E.9.
8
E6 fault occurs more than six times in an hour.
Unrecoverable
Eb
9
PFC fault
Unrecoverable
EF
10
Refrigerant radiator temperature sensor error
Recoverable
EH
11
Cooling ambient temperature lower than -5°C
Recoverable
EP
12
DC bus voltage protection
Recoverable
F1
13
Communication between the main control board and the inverter fails.
Recoverable
H0
14
M-Home mismatch(reserved)
Recoverable
HF
15
L (L0/L1) fault occurs three times in one hour.
Unrecoverable
H4
16
The fault is increased or reduced on the IDU.
Recoverable
H7
17
IPM protection
Recoverable
L0
18
DC bus low voltage protection
Recoverable
L1
19
DC bus high voltage protection
Recoverable
L2
20
MCE error
Recoverable
L4
21
Zero speed protection
Recoverable
L5
22
Compressor phase sequence error
Recoverable
L7
23
Protection for compressor speed change > 15Hz
Recoverable
L8
24
Protection for the difference between the set speed and the running speed
of the compressor > 15Hz
Recoverable
L9
25
Radiator surface temperature protection
Recoverable
PL
26
System high pressure protection
Recoverable
P1
27
System low pressure protection
Recoverable
P2
28
Overcurrent protection
Recoverable
P3
29
Discharge temperature T5 protection
Recoverable
P4
30
Outdoor condenser temperature T3 protection
Recoverable
P5
31
Typhoon protection
Recoverable
P8
32
IDU evaporator temperature T2 protection
Recoverable
PE