Midea MDV-D Series Скачать руководство пользователя страница 9

16(29)

16

25 (46)
35 (78)

60

50

380V 3N~

50Hz

80

70

a

MDV-D252( 8)W/S-830,MDV-D280(10)W/S-830,

MDV-D335(12)W/S-830, MDV-D400(14)W/S-830,

MDV-D450(16)W/S-830

b

MDV-D252W/CS
MDV-D280W/CS
MDV-D335W/CS
MDV-D400W/CS

MDV-D450W/CS

b

a

OUTDOOR UNIT INSTALLATION

    In snowy areas, facilities should be installed to 
    prevent snow. (See the chart below)(defective 
    facilities may cause malfunction.) Please lift the
    bracket higher and install snow shed at the air
    inlet and air outlet.
    

Snow shed for air inlet

Snow shed for air outlet

Snow shed for air inlet

ELECTRIC WIRING

CAUTION

Please select power supply for indoor unit and 
outdoor unit separately.

The power supply should have  specified branch 
circuit with leakage protector and manual switch.

Please put the connective wiring system between
indoor unit and outdoor unit with refrigerant piping 
system together.

Please comply with relevant National Electric Standard.

Power wiring should be done by professional electrician.

The power supply, leakage protector and manual of all
the indoor units connecting to the same outdoor unit 
should be universal. (Please set all the indoor unit power
supply of one system into the same circuit.) 

It is suggested to use 2-core shielded wire as signal 
wire between indoor and outdoor units, multi-core wire 
is unavailable.

POWER WIRING

Separate Power Supply (without power facility)  
(See table below)

<Outdoor unit>

Model 

Item 

Power 
supply

Min. Power wire diameter 

                   mm 

Wiring of mental and synthetic resin

2

Manual switch 

                (A)

Leakage 
protector

Grounding 
    wire

Capacity  Fuse 

100mA
0.1sec or 
less

Size Size

380V 3N~

50Hz

16(29)

25 (46)
35 (78)

16

Note: Select power cord these five models separately
          according to relevant standard.

Note: The  wiring diameter and the length in the table indicate 
          the condition that the voltage dropping range is within 
          2%. If the length exceeds the above figure, please select
          the wire diameter according to relevant standard.

380V  3N~

50Hz

Outdoor unit 
power supply

Leakage 
protector

Manual 
 switch 

Leakage 
protector

Manual 
 switch 

Outdoor unit 

Outdoor unit 

Outdoor unit 

Outdoor unit 

Outdoor unit 

Outdoor unit 

GND

GND

GND

GND

GND

GND

Branch box

GND

GND

GND

GND

GND

GND

With power facilities

     Power facilities
(with leakage protector)

Branch box

Leakage 
protector

Manual 
 switch 

Outdoor unit 

Outdoor unit 

Select the wire diameter

Power wiring refer to the main wire (a) connecting to 
branch box and the wiring (b) between branch  box and 
power facilities. Please select the wire diameter according
to the following requirement. 

(1) Diameter of main wire (a)
Depends on the total horsepower of outdoor unit and
following table.
E.g In system:(5Hp

1unit+8Hp

1unit+10Hp

1unit)

Total Hp=23Hp      (Table )      size of wire=70mm  (within 
50m)

(2) Wiring(b)  between branch box and power equipment
Depends on the number of combined outdoor unit. If fewer 
than 5, the diameter is the same as that of main wire (a); 
if more than6, there will be 2 electric control boxes, and the
diameter of wiring depends on the total horsepower of  
outdoor connecting 

to 

and 

following table.  
     

units 

each electric control box 

2

Select wire diameter (

) (table)       (unit :mm)

2

Содержание MDV-D Series

Страница 1: ...MDV D Series Model MDV D252W CS MDV D280W CS MDV D335W CS MDV D400W CS MDV D450W CS Digital Scroll Central Air Conditioner Outdoor Unit INSTALLATION MANUAL...

Страница 2: ...ower cord of ordinary motor Connect the indoor unit to the power after airtight test and vacuuming Do not twist or cross the power cord with wiring low voltage between indoor and outdoor unit or misha...

Страница 3: ...the panel then connect branch pipes towards left or right 4 When through the soleplate gap install the branch pipe towards left right or back To liquid side pipe 5 If through the front please remove...

Страница 4: ...s should be sealed by welding for single module Two modules See following chart for size of Y shaped pipe B on gas side See following chart for size of Y shaped pipe D on gas side NOTE See following c...

Страница 5: ...ipe size gas liquid Name Branch pipe Main pipe Pipe location Directly connect to indoor unit Not directly connect to indoor unit Number in chart Main pipe gas side liquid side Branch joint Note Select...

Страница 6: ...Query button Constraint cool button Outdoor unit address setting switch Outdoor unit capacity setting switch Mode setting switch Chart 2...

Страница 7: ...SW4 query instructions Display content Note Normal display Normal display ADDR of outdoor unit Cap of outdoor unit Qty of outdoor unit Total cap of outdoor units Cap REQT of indoor units Cap REQT of m...

Страница 8: ...in 4 way valve Relay Contactor Terminal Low pressure switch Hi pressue switch Electronic expansion valve Middle terminal Middle terminal Pipe temp sensor Outdoor temp sensor Current inductor Solenoid...

Страница 9: ...entalandsyntheticresin 2 Manual switch A Leakage protector Grounding wire Capacity Fuse 100mA 0 1sec or less Size Size 380V3N 50Hz 16 29 25 46 35 78 16 Note Select power cord these five models separat...

Страница 10: ...e dropping range is within 2 If the length exceeds the above figure please select the wire diameter according to relevant standard Single phase 220V 50Hz Indoor power supply Leakage protector Manual s...

Страница 11: ...l leakage detector alarming device related to mechanical ventilator if you can not regularly ventilate 1 Calculate the sum of the charge volume A kg 3 Calculate the refrigerant thickness A kg 3 B m 3...

Страница 12: ......

Отзывы: