-UTSM-12
86
Manifold valve
-76cmHg
Filler hose
Filler hose
V
a
c
u
u
m
p
u
m
p
Hi
-handle
Lo pressure valve
Multimeter
manometer
Lo-handle
Fig-32
Loosen and remove the maintenance orifice nut of valve A, and connect the filler hose of the manifold valve
to the maintenance orifice of valve A (tighten both valve A and valve B).
Connect the filler hose adapter to the vacuum pump.
Open the low pressure (Lo) handle of the manifold valve completely.
Start the vacuum pump to extract air. At the beginning of extracting air, slightly loosen the maintenance
orifice nut of valve
B, check whether any air enters it (the vacuum pump noise changes and the multi-meter indicate from
negative to 0). Then tighten this maintenance orifice nut.
Upon completion of vacuuming, tighten the low pressure (Lo) handle of the manifold valve completely and
stop the vacuum pump. Keep extracting air for over 15 minutes. Check whether the multi-meter points at
-1.0X10 Pa (-76cmHg).
Loosen and remove the square-head cover of valves A and B. After opening valves A and B completely,
tighten the square head cover of valves A and B.
Remove the filler hose off the maintenance orifice of valve A, and then tighten the nut.
5.3.1.5.
Procedure of using stop valve
Open the spool until it touches the stop block. Do not attempt to open further.
Use a spanner or a similar tool to tighten the bonnet. The bonnet tightening torque is shown in Table 3
“
Tightening torque
”
.
Upon completion of installation, open all valves before trial run. Each unit has two valves of different sizes
located at the outdoor unit side. Of the two valves, one is gas valve and the other is liquid valve. The
procedure of opening/closing the valve is shown in the right figure (Fig-33).
Procedure of opening the valve: Open the square-head cover, use a spanner to capture the square head
and open it thoroughly. Then tighten the square-head cover.
Procedure of closing the valve: Same as the procedure of opening the valve, but rotate the spanner
clockwise thoroughly.
Содержание MDFA-76CRN2
Страница 7: ...MCAC UTSM 12 8 3 Dimensions 3 1 MDTA 76C H RN2 MDTA 96C H RN2...
Страница 8: ...MCAC UTSM 12 9 3 2 MDTA 120C H RN2...
Страница 11: ...MCAC UTSM 12 12 6 Wiring Diagrams 6 1 MDTA 76CRN2 MDTA 96CRN2...
Страница 12: ...MCAC UTSM 12 13 6 2 MDTA 76HRN2 MDTA 96HN2 6 3 MDTA 120CRN2...
Страница 13: ...MCAC UTSM 12 14 6 4 MDTA 120HRN2...
Страница 34: ...MCAC UTSM 12 35 4 Service Space Front view 1 0 c m 1 0 cm Rear 30 cm No obstacle in front of it...
Страница 36: ...MCAC UTSM 12 37 6 Wiring Diagrams 6 1 MDFA 76CRN2 MDFA 96CRN2 CN20 CN20 CN20...
Страница 37: ...MCAC UTSM 12 38 6 2 MDFA 76HRN2 MDFA 96HRN2 CN20 CN20 CN20...
Страница 51: ...MCAC UTSM 12 53 2 Dimension 2 1 MDOV 76C H CN2 MDOV 96C H CN2...
Страница 52: ...MCAC UTSM 12 54 2 2 MDOV 120C H CN2...
Страница 54: ...MCAC UTSM 12 56 Foundation of the outdoor unit 762 676 500 mm 500 mm M12 foundation bolt 4 screws for 1 unit...
Страница 55: ...MCAC UTSM 12 57 4 Wiring Diagrams 4 1 MDOV 76C CN2 MDOV 96C CN2 MDOV 120C CN2...
Страница 56: ...MCAC UTSM 12 58 4 2 MDOV 76H CN2 MDOV 96H CN2 MDOV 120H CN2...
Страница 75: ...UTSM 12 78 76 96 120 kBtu h 150 kBtu h Fig 23 3 Connection between indoor unit and outdoor unit Fig 23...
Страница 87: ...UTSM 12 90 Floor standing type cooling and heating type 76 kBtu h 96 kBtu h...