MCAC-UTSM-12
85
5.3 Expelling Air
5.3.1. From the following table, select a method of expelling air.
Table 4:
Length of connective pipe
(single pass)
Procedure of expelling air
Less than 5m
Use refrigerant in the outdoor unit
5
~
15m
Use vacuum pump or refrigerant tank.
If the air conditioner is relocated, be sure to use a vacuum pump or refrigerant tank to expel air.
5.3.1.2.
Use the refrigerant in the outdoor unit to expel air (
see Fig-31
and
Fig-32
)
A
B
C
D
Outdoor unit
Intdoor unit
Stop valve
Air side
Liquid side
pipe adapter
Fig-31
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover of valves A and B, rotate the square-head spool of valve B
counterclockwise for 45 degrees and stay for about 10 seconds, and then close the spool of valve B tightly.
Detect leak for all adapters at A, B, C and D. After making sure that no leak exists, open the maintenance
orifice nut of valve A. After all air is expelled, tighten the maintenance orifice nut of valve A.
Open the spools of valves A and B completely.
Tighten the square-head cover of valves A and B completely.
5.3.1.3.
Use refrigerant tank to expel air (see Fig-31)
Screw up the pipe nuts at A, B, C and D completely.
Loosen and remove the square-head cover and the maintenance orifice nut of valves A and B.
Connect the filler hose of the refrigerant tank with the maintenance orifice of valve A.
Loosen the valve of the refrigerant tank, continue filling refrigerant for 6 seconds to expel the air, and tighten
the nut of valve B quickly.
Loosen the valve of the refrigerant tank again, and fill the refrigerant for 6 seconds. Detect leak for all
adapters at A, B, C and D. After making sure that no leak exists, screw off the filler hose. After all the filled
refrigerant is expelled, screw up the maintenance orifice nut of valve A quickly.
Open the square-head spools of valves A and B completely.
Tighten the square-head cover of valves A and B.
5.3.1.4.
Use a vacuum pump to expel the air (
Fig-32
) (For method of using the manifold valve, see the
operation manual of manifold valve):
Содержание MDFA-76CRN2
Страница 7: ...MCAC UTSM 12 8 3 Dimensions 3 1 MDTA 76C H RN2 MDTA 96C H RN2...
Страница 8: ...MCAC UTSM 12 9 3 2 MDTA 120C H RN2...
Страница 11: ...MCAC UTSM 12 12 6 Wiring Diagrams 6 1 MDTA 76CRN2 MDTA 96CRN2...
Страница 12: ...MCAC UTSM 12 13 6 2 MDTA 76HRN2 MDTA 96HN2 6 3 MDTA 120CRN2...
Страница 13: ...MCAC UTSM 12 14 6 4 MDTA 120HRN2...
Страница 34: ...MCAC UTSM 12 35 4 Service Space Front view 1 0 c m 1 0 cm Rear 30 cm No obstacle in front of it...
Страница 36: ...MCAC UTSM 12 37 6 Wiring Diagrams 6 1 MDFA 76CRN2 MDFA 96CRN2 CN20 CN20 CN20...
Страница 37: ...MCAC UTSM 12 38 6 2 MDFA 76HRN2 MDFA 96HRN2 CN20 CN20 CN20...
Страница 51: ...MCAC UTSM 12 53 2 Dimension 2 1 MDOV 76C H CN2 MDOV 96C H CN2...
Страница 52: ...MCAC UTSM 12 54 2 2 MDOV 120C H CN2...
Страница 54: ...MCAC UTSM 12 56 Foundation of the outdoor unit 762 676 500 mm 500 mm M12 foundation bolt 4 screws for 1 unit...
Страница 55: ...MCAC UTSM 12 57 4 Wiring Diagrams 4 1 MDOV 76C CN2 MDOV 96C CN2 MDOV 120C CN2...
Страница 56: ...MCAC UTSM 12 58 4 2 MDOV 76H CN2 MDOV 96H CN2 MDOV 120H CN2...
Страница 75: ...UTSM 12 78 76 96 120 kBtu h 150 kBtu h Fig 23 3 Connection between indoor unit and outdoor unit Fig 23...
Страница 87: ...UTSM 12 90 Floor standing type cooling and heating type 76 kBtu h 96 kBtu h...