8.4.3.5 Evaporator coil temperature
protection
Resume
Off
Decrease
Hold
When evaporator temperature temp. is more
than
the
setting
protection
value,
the
compressor will stop.
8.4.4 Auto-mode
This mode can be chosen with remote
controller and the setting temperature can be
changed between 17°C~30°C
In auto mode, the machine will choose cooling,
heating or fan-only mode according to ΔT (ΔT
=T1-Ts).
T1-Ts
Cooling
Heating*
Fan only
Heating*: For cooling only models, they will run
at fan speed
Indoor fan will run at auto fan of the relevant
mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for certain time and then choose mode
according to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
8.4.5 Drying mode
Indoor fan speed is fixed at breeze and can’t be
changed. The louver angle is the same as in
cooling mode.
All protections are active and the same as that
in cooling mode.
8.4.6 Forced operation function
Forced cooling mode:
The compressor and outdoor fan keep running
and the indoor fan runs at low speed. After
running for 30 minutes, AC will turn to auto
mode with 24
℃
setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal
auto
mode
with
24
℃
setting
temperature.
When AC receives signals, such as switch on,
switch off, timer on, timer off, mode setting, fan
speed setting, sleeping mode setting, follow me
setting, it will quit the forced operation.
8.4.7 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an
auto-restart module. In case of a sudden power
failure, the module memorizes the setting
conditions before the power failure. The unit will
resume the previous operation setting (not
including swing function) automatically after
certain time when power returns.
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for
certain time and turn to auto mode as 24
℃
setting temp.
If AC is off before power off and AC is required
to start up now, the compressor will have 1
minute delay when power on. Other conditions,
the compressor will have 3 minutes delay when
restarts.
Содержание MCHS-09PSH1
Страница 1: ...Mission 3D Inverter Series Service Manual 2016 MBSUL A 1604...
Страница 8: ...For 9k 12k For 18k 24k For 30k 36k...
Страница 11: ...5 Wiring Diagram 5 1 Indoor Unit MEHS 09PSH1 MEHS 12PSH1 MEHSU 09PHH2 MEHSU 12PHH2...
Страница 12: ...MEHSU 18PHH2 MEHSU 24PHH2 MEHS 30PSH2 MEHS 36PSH2...
Страница 13: ...5 2 Outdoor Unit MCHS 09PSH1 MCHS 12PSH1 MCHSU 09PHH2 MCHSU 12PHH2 MCHSU 18PHH2...
Страница 14: ...MCHSU 24PHH2 MCHS 30PSH2 MCHS 36PSH2...
Страница 45: ...P W N U...
Страница 46: ...N V N W...
Страница 78: ...compressor on bottom plate 4 Lift the compressor from the base pan assembly 3...