9.4.2.13 P5(High temperature protection of condenser) error diagnosis and solution.
Error Code
P5
Malfunction decision
conditions
When outdoor pipe temperature is more than 65°C, the unit will
stop, and unit runs again when outdoor pipe temperature is less
than 52°C
Supposed causes
●
The condenser temperature sensor faulty
●
Heat exchanger dirty
●
System block
Trouble shooting:
High temperature protection of
condenser
Check whether the
condenser temperature is
more than 65°C
Yes
Judge 1: Check whether the
outdoor ambient
temperature is higher than
50
℃
No
Judge 3: The refrigerant
pipe is blocked
Let the refrigerant out, then use the high
pressure nitrogen or refrigerant to blow pipe,
vacuumize and charge the refrigerant again
Yes
Judge 2: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Yes
Replace outdoor main board
Yes
Check whether the
resistance of condenser
temp. sensor is correct
refer to the
Appendix
1
Replace the temperature sensor
Stop the unit
Yes
No
No
Содержание M2OC-18HFN1-M
Страница 19: ...8 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor M2OC 18HFN1 M M2OD 18HFN1 M...
Страница 20: ...PCB board of M2OC 18HFN1 M M2OD 18HFN1 M...
Страница 21: ...IPM board of M2OC 18HFN1 M...
Страница 22: ...IPM board of M2OD 18HFN1 M...
Страница 23: ...8 2 Wiring diagram of 1 drive 3 outdoor M3OD 27HRDN1 M M3OC 30HRFN1 M...
Страница 24: ...PCB board of M3OC 30HRFN1 M...
Страница 25: ...IPM board of M3OC 30HRFN1 M...
Страница 26: ...PCB board of M3OD 27HRDN1 M...
Страница 27: ...IPM board of M3OD 27HRDN1 M...
Страница 28: ...8 3 Wiring diagram of 1 drive 4 outdoor M4OC 36HRFN1 M...
Страница 29: ...PCB board of M4OC 36HRFN1 M...
Страница 30: ...IPM board of M4OC 36HRFN1 M...
Страница 31: ...PFC board of M4OC 36HRFN1 M...
Страница 66: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone...
Страница 67: ...P N for qua zone...
Страница 68: ...bridge rectifier for dual tri zone bridge rectifier for qua zone...
Страница 69: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V...
Страница 71: ...Two ports of the inductance Inductance...
Страница 72: ......
Страница 77: ......
Страница 79: ......
Страница 81: ......
Страница 83: ......
Страница 96: ...6 EXV check Disconnect the connectors...
Страница 97: ...Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 98: ...Red Blue Red Yellow...
Страница 99: ...Brown Orange Brown White...
Страница 114: ...Screws of front panel Screws of right rear panel Screws of top cover...
Страница 122: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board...
Страница 128: ......