9.4.2.11 P3(Current protection of compressor) error diagnosis and solution.
Error Code
P3
Malfunction decision
conditions
If the compressor current exceeds the current limit value for
10 seconds, the LED will display the failure.
Supposed causes
●
Wiring mistake
●
Over load protector faulty
●
System block
●
Outdoor PCB faulty
Trouble shooting:
Current protection of compressor
Current protection of compressor
Judge 1: Check whether the input
current of the power supply wire
is more than 12.5A(18K) (For
27K, it is 17.For 30K, it is 18.5.For
36K, it is 23A)
Judge 1: Check whether the input
current of the power supply wire
is more than 12.5A(18K) (For
27K, it is 17.For 30K, it is 18.5.For
36K, it is 23A)
Yes
Replace the electric control box
Replace the electric control box
Check whether the
refrigerant system
is ok
Check whether the
refrigerant system
is ok
Judge 2: Check whether the
outdoor ambient temperature
is higher than 50
℃
Judge 2: Check whether the
outdoor ambient temperature
is higher than 50
℃
No
Stop the unit
Stop the unit
Yes
Judge 3: Check whether the
outdoor unit is bad ventilation
Judge 3: Check whether the
outdoor unit is bad ventilation
No
Make the outdoor unit ventilate well
Make the outdoor unit ventilate well
Yes
Judge 5: The refrigerant pipe is
blocked
Judge 5: The refrigerant pipe is
blocked
No
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize
and charge the refrigerant again
Let the refrigerant out, then use the high pressure
nitrogen or refrigerant to blow pipe, vacuumize
and charge the refrigerant again
Yes
Judge 4: Check whether the
heat exchanger is dirty
Judge 4: Check whether the
heat exchanger is dirty
No
Clean the heat exchanger
Clean the heat exchanger
Yes
Yes
Replace outdoor main
board,and check whether the
system can run normally
Replace outdoor main
board,and check whether the
system can run normally
No
Yes
Trouble is solved
Trouble is solved
Replace outdoor main board
Replace outdoor main board
No
Содержание M2OC-18HFN1-M
Страница 19: ...8 Wiring Diagrams 8 1 Wiring diagram of 1 drive 2 outdoor M2OC 18HFN1 M M2OD 18HFN1 M...
Страница 20: ...PCB board of M2OC 18HFN1 M M2OD 18HFN1 M...
Страница 21: ...IPM board of M2OC 18HFN1 M...
Страница 22: ...IPM board of M2OD 18HFN1 M...
Страница 23: ...8 2 Wiring diagram of 1 drive 3 outdoor M3OD 27HRDN1 M M3OC 30HRFN1 M...
Страница 24: ...PCB board of M3OC 30HRFN1 M...
Страница 25: ...IPM board of M3OC 30HRFN1 M...
Страница 26: ...PCB board of M3OD 27HRDN1 M...
Страница 27: ...IPM board of M3OD 27HRDN1 M...
Страница 28: ...8 3 Wiring diagram of 1 drive 4 outdoor M4OC 36HRFN1 M...
Страница 29: ...PCB board of M4OC 36HRFN1 M...
Страница 30: ...IPM board of M4OC 36HRFN1 M...
Страница 31: ...PFC board of M4OC 36HRFN1 M...
Страница 66: ...IPM for dual tri zone IPM for qua zone P N for dual tri zone...
Страница 67: ...P N for qua zone...
Страница 68: ...bridge rectifier for dual tri zone bridge rectifier for qua zone...
Страница 69: ...Remark Measure the DC voltage between and port The normal value should be 190V 250V...
Страница 71: ...Two ports of the inductance Inductance...
Страница 72: ......
Страница 77: ......
Страница 79: ......
Страница 81: ......
Страница 83: ......
Страница 96: ...6 EXV check Disconnect the connectors...
Страница 97: ...Resistance to EXV coil Color of lead wire Normal Value Red Blue About 50 Red Yellow Brown Orange Brown White...
Страница 98: ...Red Blue Red Yellow...
Страница 99: ...Brown Orange Brown White...
Страница 114: ...Screws of front panel Screws of right rear panel Screws of top cover...
Страница 122: ...Screws of big handle Screws of right rear panel Screws of water collector Screws of terminal board...
Страница 128: ......