MCAC-HTSM-201409                    Midea R410A Domestic Pools & Spas HPWH 50Hz Technical Manual 

26 
 

1. Safety information 

To prevent injury to the user or other people and property damage, the following instructions must be 

followed. Incorrect operation due to ignoring of instructions may cause harm or damage. 

  The unit must be earthed effectively. The earthing pole of socket must be grounded well, make 

sure that power supply socket and plug are dry enough and connected tightly. 

  If the power supply cord is damaged, it must be replaced by the qualified person. 

  Do not remove, cover or deface any permanent instructions, labels, or the data labels from either 

the outside of the unit or inside of unit panels. 

  Ask qualified person to perform the installation of this unit in accordance with local national 

regulations and this manual. Improper installation may result in water leakage, electric shock or 

fire. 

  Ask qualified person for relocating, repairing and maintaining the unit. Improper installation may 

result in water leakage, electric shock or fire. 

  Electric connection work should obey the instructions of local power company, local electric 

utility and this manual. 

  Never use the wire and fuse with wrong rated current, otherwise unit may break down and cause 

fire furthermore. 

  Do not insert fingers, rods or other objects into the air inlet or outlet. When the fan is rotating at 

high speed, it will cause injury. 

  In order to avoid injury, do not remove the fan guard of the units. 

  Never use a flammable spray such as hair spray, lacquer paint near the unit. It may cause a fire. 

  This appliance is not intended for use by person (including children) with reduced physical, 

sensory or mental capabilities, or lack of experience and knowledge, unless they have been 

given supervision or instruction concerning use of the appliance by a person responsible for their 

safety. Children should be supervised to ensure that they do not play with the appliance. 

  If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or 

similarly qualified person. 

Содержание LRSJ-120/NYN1-A1

Страница 1: ...Spas Heat Pump Water Heater 50Hz A1 Series Technical Manual Applicable Model New CE safety directive LRSJ 60 NYN1 A1 LRSJ 80 NYN1 A1 LRSJ 120 NYN1 A1 LRSJ 140 NYN1 A1 Midea reserves the right to disc...

Страница 2: ...MCAC HTSM 201409 Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual 2 Content Part 1 General information 3 Part 2 Performance 5 Part 3 Installation 25...

Страница 3: ...Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual MCAC HTSM 201409 3 Part 1 General information 1 Model Names of Units 4 2 External Appearance 4 3 Nomenclature 4...

Страница 4: ...NYN1 A1 220 240V 1Ph 50Hz LRSJ 120 NYN1 A1 220 240V 1Ph 50Hz LRSJ 140 NYN1 A1 220 240V 1Ph 50Hz 2 External Appearance LRSJ 60 NYN1 A1 LRSJ 80 NYN1 A1 LRSJ 120 NYN1 A1 LRSJ 140 NYN1 A1 3 Nomenclature L...

Страница 5: ...Technical Manual MCAC HTSM 201409 5 Part 2 Performance 1 Features 6 2 Specifications 7 3 Dimensions Unit mm 10 4 Service Space 11 5 Refrigerant circuit 12 6 Wiring Diagrams 13 7 Electric Characteristi...

Страница 6: ...ctly connected with poor Without secondary heat exchanger it is can improve the efficiency of whole system Easy operation and automatic control the system can be controlled simply through the wired co...

Страница 7: ...vel dB A 58 58 Refrigerant Type Discharged R410A 1 00kg R410A 1 25kg Refrigerant control Capillary Capillary Fan Type Axial fan Axial fan Motor model YDK85 6 YDK85 6 Motor brand Welling Welling Quanti...

Страница 8: ...erature 27 C Water flow volume has been defined Model LRSJ 120 NYN1 A1 LRSJ 140 NYN1 A1 Power supply 220 240V 1Ph 50Hz 220 240V 1Ph 50Hz Outlet water temperature Heating mode Default 28 C 20 C 35 C De...

Страница 9: ...V Rated current RLA A 11 40 13 10 Locked rotor Amp LRA A 61 63 Thermal protector Internal Internal Refrigerant oil ml 950 1 100 Water pipe Inlet pipe mm 50 50 Outlet pipe mm 50 50 Water circulation pi...

Страница 10: ...H 50Hz Technical Manual 10 3 Dimensions Unit mm Top view Unit mm Model A B C D E F LRSJ 60 NYN1 A1 610 390 170 1 015 385 705 LRSJ 80 NYN1 A1 610 390 170 1 015 385 705 LRSJ 120 NYN1 A1 590 333 165 1 05...

Страница 11: ...Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual MCAC HTSM 201409 11 4 Service Space...

Страница 12: ...MCAC HTSM 201409 Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual 12 5 Refrigerant circuit...

Страница 13: ...Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual MCAC HTSM 201409 13 6 Wiring Diagrams LRSJ 60 NYN1 A1 LRSJ 80 NYN1 A1...

Страница 14: ...MCAC HTSM 201409 Midea R410A Domestic Pools Spas HPWH 50Hz Technical Manual 14 LRSJ 120 NYN1 A1 LRSJ 140 NYN1 A1...

Страница 15: ...RSJ 140 NYN1 A1 Item Detail N C No need connect Tout Outlet water temperature sensor T3 Heat exchanger temperature sensor T4 Outdoor ambient temperature sensor T6 Inlet water temperature sensor Tp Tem...

Страница 16: ...A TOCA Total Over current Amps A MSC Max Starting Amps A RLA Rated Locked Amps A OFM Outdoor Fan Motor kW Fan Motor Rated Output kW FLA Full Load Amps A Model LRSJ 120 NYN1 A1 LRSJ 140 NYN1 A1 Outdoor...

Страница 17: ...201409 17 8 Capacity Curve LRSJ 60 NYN1 A1 Heating mode Test condition inlet water temperature of the units is 27 C outlet water temperature is 29 C Relation between heating capacity and outdoor ambi...

Страница 18: ...s HPWH 50Hz Technical Manual 18 Cooling mode Test condition inlet water temperature of the units is 27 C water volume is 2 6m3 h Relation between cooling capacity and outdoor ambient temperature Relat...

Страница 19: ...anual MCAC HTSM 201409 19 LRSJ 80 NYN1 A1 Test condition inlet water temperature of the units is 27 C outlet water temperature is 29 C Relation between heating capacity and outdoor ambient temperature...

Страница 20: ...s HPWH 50Hz Technical Manual 20 Cooling mode Test condition inlet water temperature of the units is 27 C water volume is 3 5m3 h Relation between cooling capacity and outdoor ambient temperature Relat...

Страница 21: ...nual MCAC HTSM 201409 21 LRSJ 120 NYN1 A1 Test condition inlet water temperature of the units is 27 C outlet water temperature is 29 C Relation between heating capacity and outdoor ambient temperature...

Страница 22: ...s HPWH 50Hz Technical Manual 22 Cooling mode Test condition inlet water temperature of the units is 27 C water volume is 5 0m3 h Relation between cooling capacity and outdoor ambient temperature Relat...

Страница 23: ...nual MCAC HTSM 201409 23 LRSJ 140 NYN1 A1 Test condition inlet water temperature of the units is 27 C outlet water temperature is 29 C Relation between heating capacity and outdoor ambient temperature...

Страница 24: ...ter temperature of the units is 27 C water volume is 5 8m3 h Relation between cooling capacity and outdoor ambient temperature Relation between EER and outdoor ambient temperature 9 Accessories Name Q...

Страница 25: ...l Manual MCAC HTSM 201409 25 Part 3 Installation 1 Safety information 26 2 Unit Installation 28 3 Functions maintenance 34 4 Controller operation 37 5 Trial run 40 6 Fault analysis and solutions 41 7...

Страница 26: ...epairing and maintaining the unit Improper installation may result in water leakage electric shock or fire Electric connection work should obey the instructions of local power company local electric u...

Страница 27: ...dual operating current not exceeding 30mA and disconnection must be incorporated in the fixed wiring in accordance with the wire rules Arrange the drain pipe to ensure smooth draining Improper drainag...

Страница 28: ...t affect neighbors Installing the unit in any of the following places may lead to faults of the unit If that is inevitable please consult the factory The site contains mineral oils such as cutting lub...

Страница 29: ...lling site please confirm the main unit is placed in horizontal Choose the appliance installation site according to the following criteria the clearance around the appliance must be respected to avoid...

Страница 30: ...mpliance with applicable standards Keep the unit out of reach of children 2 4 Distance of unit ground screws Unit mm Model A B C D E LRSJ 60 NYN1 A1 610 390 170 1 015 385 LRSJ 80 NYN1 A1 610 390 170 1...

Страница 31: ...insulation materials should be employed to seal up inlet and outlet water pipes Before operation please confirm that the specifications of connective pipes are correct and thermal insulation layer has...

Страница 32: ...e a specialized power supply which voltage must in compliance with the rated voltage Power supply circuit of the unit with earthing wires that must be reliably connected Wiring must be performed by pr...

Страница 33: ...an 2 If the continuous wire length valve larger than the one of the table please choose its size in compliance with the relevant rules Model Power supply Min wire size mm 2 Metal pipe synthetic resin...

Страница 34: ...ections of low voltage electric signal wire with heavy electric wire otherwise some of electric control elements will burned out The following diagram is electric wiring diagram for the units 3 Functi...

Страница 35: ...e When protection device does operate though the unit stops the operating indicator of wired controller still will be blinking When protection device operates nixie indicator will display malfunction...

Страница 36: ...has serviced for a period of time Generally once a month it is necessary to press the test button at close circuit to check whether the performance of RCCB is work normally Every time press this butt...

Страница 37: ...heating capacity The heating process is a heat pump mode that it absorbs heat from outdoor and release to water Once the outdoor temperature decreases the heating capacity will also decrease simultane...

Страница 38: ...n or protection time 6 ALARM indicator It will flash at the malfunction or protection time 4 2 Names of keys on the controller 7 MODE key Used to set different modes 8 UP key Used to add time or tempe...

Страница 39: ...hen the swimming temperature is high in summer Heat mode The unit heats swimming pool water by compressor driving according to heat pump principle Used when the ambient temperature is low Pump mode Th...

Страница 40: ...compulsory operation It is very dangerous if the protection device is not active Trial run is stop performed only after all installation is finished Confirm the following insure before operation The w...

Страница 41: ...f hiss every now and then At the beginning and the end of the defrost process sound is given out in motor valve During the process or just after having stopped sound like water flow occur which will b...

Страница 42: ...Remarks 1st Normal display Inlet water temperature Value of T6 2nd Mode code 0 6KW 1 8KW 2 11 7KW 3 13 6KW 3rd Operate mode 1 Water cooling 16 Water heating 4 Pump 8 standby 4th Fan speed 0 Off 1 Low...

Страница 43: ...ged Check whether the T6 temperature sensor is correctly connected to the motherboard Check whether the signal of T6 sensor is in strong electromagnetic interference E5 Evaporator pipe temperature sen...

Страница 44: ...load protection Check whether the dial code S2 is correct Check whether the voltage supplied is in the accepted voltage range Check whether compressor is damaged Check whether the refrigerant pipes i...

Страница 45: ...34 6 68355 74 1 43498 114 0 42304 5 46 5725 35 6 40021 75 1 38703 115 0 41164 4 44 36 6 13059 76 1 34105 116 0 4006 3 41 5878 37 5 87359 77 1 29078 117 0 38991 2 39 8239 38 5 62961 78 1 25423 118 0 3...

Страница 46: ...2 2 63 7 261 4 33 38 89 73 8 643 113 2 559 6 247 8 34 37 3 74 8 358 114 2 489 5 234 9 35 35 78 75 8 084 115 2 422 4 222 8 36 34 32 76 7 82 116 2 357 3 211 4 37 32 94 77 7 566 117 2 294 2 200 7 38 31 6...