3.13 Function

 

Auto Mode

 

Under auto mode, the air conditioner will compare the room temperature with the setting temperature, 

automatically select the suitable operation. If auto mode operation is not suitable for you, it can select 

other operation mode.

 

 

Cool / Heat Mode

 

In the cool / heat mode, the temperature can be set.

 

When  it  is  the  cool  operation,  the  free  cooling

 

function  is  default  operated.  When  the  room 

temperature is high than 16°C,

 

the outdoor temperature is lower than 20°C, the humidity

 

is higher 

than  80%,    the  air  conditioner  will  switch

 

to  free  cooling

 

mode.  When  the  outdoor  temperature  is 

higher than 21°C,

 

or the humidity keep higher than 85% in 5 minutes,

 

the air conditioner will exit free 

cooling

 

mode with cool operation.

 

When it is the heat operation, the electric heater will be switch on till the room temperature is higher 

than the setting temperature.

 

 

Dry mode

 

The  unit  operates  in  the  fixed  temperature  which  is  15°C.

 

At  the  same  time,  the  indoor  fan  speed 

cannot

 

be adjusted.

 

 

Compressor delay 3 min protection

 

To protect

 

the compressor,

 

after the compressor turn off, the compressor turn on

 

after 3 minutes.

 

 

Power-down memory function

 

When the air conditioner re-connect to the power after power down, the unit will operate as the state 

before power down.

 

 

Dual units switch function

This function only is effective when setting the unit for main unit.

After se the dual units switch function, when switch time is up, if the formal main unit is operated, then 

the main unit will be closed, and operate the slave unit. If the formal slave unit is operated, then close 

the slave unit, operate the main unit. 

If when the operating the main unit has error, then the slave unit will be operated automatically. If the 

slave unit has error, then the main unit will be operated automatically.

High/Low Temp Cascade function

This function only is effective when setting the unit for main unit. After set the high/low function, when 

the temperature of main unit is higher/lower the setting high/low temperature, it will force the main 

and slave unit operate the setting temperature to be cool/heat mode with locked temperature at the 

same  time.  When  the  temperature  which  checked by  the  main  unit  is  lower/higher  the  setting 

high/low temperature 2°C, the main unit will recover to the previous operating state, and the slave 

unit will automatically off.

Содержание KCD-120L/S-JZ

Страница 1: ...3 COMPACT TYPE BASE STATION AIR CONDITIONER 3 1 FEATURES 3 2 REFRIGERANT CIRCUIT 3 3 UNIT STRUCTURE 3 4 SPECIFICATIONS 3 5 DIMENSION 3 6 INDOOR UNIT CAPACITY CURVE 3 7 WIRING DIAGRAM 3 8 INSTALLATION...

Страница 2: ...gned for running 24 hours a day and 365 days a year There are two types of unit structures split type and compact type the cooling capacity range is from 5 5kW to 13kW 1 1 Model names of base station...

Страница 3: ...1 2 External appearance Compact type...

Страница 4: ...45 C outside temperature At low outside temperature cooling directly with outside air to save energy Fresh air inlet is equipped with dual filter to prevent equipment in station from dust damage Auto...

Страница 5: ...equipped with rotary compressor KCD 75L S JZ E2 KCD 120L S JZ are equipped with scroll compressor Condenser and Evaporator Copper tube and Aluminum fin type heat exchanger Capillary Capillary subassem...

Страница 6: ...3 3 Unit structure Air distribution Displayer Controller Return Air Intake Handler Supply Air Outlet Drain pipe Cooling mode Free cooling mode...

Страница 7: ...P 582 VR52KS TFP 542 Brand Hitachi Copeland Copeland Capacity Btu h 17265 25000 43700 Input W 1650 2230 3770 Rated current A 7 75 4 1 6 8 Locked rotor amp A 41 34 59 Up motor Model YDK120 8H YDK120 8G...

Страница 8: ...3 5 Dimension KCD 60L S JZ E1 KCD 75L S JZ E2 MRT 60HN2 MRT 75HN2 MRT 60HN2 MRT 75HN2 MRT 60HN2 MRT 75HN2 MRT 60HN2 MRT 75HN2...

Страница 9: ...KCD 120L S JZ MRT 60HN2 MRT 60HN2 MRT 60HN2...

Страница 10: ...3 6 Indoor unit capacity curve KCD 60L S JZ E1 KCD 75L S JZ E2 MRT 60HN2 MRT 60HN2 MRT 60HN2 MRT 75HN2 MRT 75HN2 MRT 75HN2 MRT 75HN2...

Страница 11: ...KCD 120L S JZ 3 7 Wiring diagram KCD 60L S JZ E1 MRT 120HN2 MRT 120HN2 MRT 120HN2 MRT 120HN2 MRT 60HN2 MRT 60HN2 MRT 60HN2 MRT 60HN2...

Страница 12: ...KCD 75L S JZ E2 KCD 120L S JZ MRT 75HN2 MRT 75HN2 MRT 75HN2 MRT 75HN2 MRT 120HN2 MRT 120HN2 MRT 120HN2 MRT 120HN2...

Страница 13: ...3 8 Installation Dorsal view KCD 60L S JZ E1 KCD 75L S JZ E2 MRT 75HN2 MRT 60HN2 MRT 75HN2 MRT 60HN2 MRT 75HN2 MRT 60HN2 MRT 75HN2 MRT 60HN2...

Страница 14: ...d away from the heat source and vapor source There is no any obstruction to block the air circulation The location should be able to support the unit weight and will not increase the running noise and...

Страница 15: ...t place the end of the drain pipe in the water 3 9 Field wiring The maximum allowed voltage fluctuation is 10 Be sure unit is correctly earthing Be sure equipped electric leakage switch main switch an...

Страница 16: ...ature difference Room temperature difference Whether the liquid in the evaporator flows and frosts After 30 minutes the unit will automatically stop the trial run In the trial run state press the Tria...

Страница 17: ...broken Change the fuse There has air come out but the cooling heating effect is not good The temperature setting is not suitable Properly set the temperature The air filter has been blocked by dust Cl...

Страница 18: ...E1 E2 E4 E6 E8...

Страница 19: ...P1 P2...

Страница 20: ...P3 P4...

Страница 21: ...turn off the compressor turn on after 3 minutes Power down memory function When the air conditioner re connect to the power after power down the unit will operate as the state before power down Dual...

Страница 22: ...etting temperature will automatically be adjusted to the temperature locking value of the current mode Notes 1 Temperature set through upper unit will not automatically be adjusted to the set temperat...

Страница 23: ...ton Press the MODE button select the Auto Press the Adjust button select the temperature then the air conditioner will operate under the auto mode meanwhile the fan speed will be auto controlled Press...

Страница 24: ...he fan speed will be auto controlled Press the ON OFF button again the unit will be stopped Dry operation Press the ON OFF button Press the MODE button and select the Dry mode The air conditioner will...

Страница 25: ...irmation Press the Adjust button to select the high low temp to be the one which you need every press the button will add 1 C Press the Auxiliary button again for confirmation To switch off the functi...

Страница 26: ...Press the Auxiliary button again for confirmation Press the Adjust button then will one by one display T1 T2 T3 T4 temperature humidity or protection code Without the protection no display Notes Humi...

Отзывы: