REFRIGERANT  PIPE  CONNECTION

Settlement of outdoor unit

Anchor the outdoor unit with a bolt and 
nut  

φ

10 or 

φ

8 tightly and horizontally 

on a concrete or rigid mount.

A

B

Air inlet 

Air outlet

Air inlet 

Fig.14

Refrigerant pipe connection

Oblique

90

Roughness

Burr

Main cause for refrigerant leakage
is due to defect in the flaring work. 
Carry out correct flaring work
using the following procedure:

A: Cut the pipes and the cable.

1. Use the piping kit accessory or pipes 
    purchased locally.
2. Measure the distance between the indoor 
    and the outdoor unit.
3. Cut the pipes a little longer than the 
    measured distance.
4. Cut the cable 1.5m longer than the pipe  
    length.

1. Flaring work

Fig.15

B: Burr removal

1. Completely remove all burrs from the cut 
     cross section of pipe/tube.
2. Put the end of the copper tube/pipe in a 
    downward direction as you remove burrs in 
    order to avoid dropping burrs into the tubing.

Pipe

Reamer

Point down

Fig.16

Fig.17

Outdoor unit dimension
          mm(WxHxD)

A(mm)

B(mm)

530

290

484

600

560

590

275

320

335

333

549

280

Mounting dimensions

780x540x250

760x590x275

670x540x250

775x545x310

840x700x320

895x860x330

Drain joint installation 

Seal

Drain joint

Base pan hole of
outdoor unit

Seal

Drain pipe

(A)

(B)

For the drain joint with the seal(Fig.15 (A)), first
fit  the seal onto the drain  joint, then insert  the  
drain  joint  into the base pan hole of outdoor unit,

 rotate  90

to securely  assemble them. To install 

drain joint as shown in Fig.15 (B), insert  the  drain  
joint into the base pan hole of outdoor unit until it 
remains fixed  with a clicking sound. Connecting 
the drain joint with an extension drain hose (Locally 
purchased), in case of the water draining off the 
outdoor unit during the heating mode.

NOTE: 

The drain joint is slightly different 

according to the different outdoor unit.

Содержание INVERTER SPLIT TYPE ROOM AIR CONDITIONER

Страница 1: ...ompletely before installing the product If the power cord is damaged replacement work shall be performed by authorised personnel only Installation work must be performed in accordance with the nationa...

Страница 2: ...use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the...

Страница 3: ...ring standard regulation and this installation instructions An independent circuit and single outlet must be used If electrical circuit capacity is not enough or defect found in electrical work it wil...

Страница 4: ...ated by arrows from wall or other obstacles Do not place animals and plants in the path of the air inlet or outlet Take the air conditioner weight into account and select a place where noise vibration...

Страница 5: ...e 60c m abo ve 30cm above Air Filter Air Outlet 30cm above Wrapping tape B 200cm above Additional drain pipe Accessories Parts you must purchase Consult the dealer about the pipe size 6 35 9 53 12 7 9...

Страница 6: ...mensions are in mm unless otherwise stated 1 Determine hole positions according to the diagramdetailed in Fig 5 Drill one 1 hole 65mm slanting slightly to outdoor side 2 Always use wall hole conduit w...

Страница 7: ...the indoor unit with a cushioning material between the indoor unit and the wall Get it out after finish piping 4 Push the lower part of the indoor unit up on the wall then move the indoor unit from s...

Страница 8: ...se sloped downward to drain out the condensed water smoothly CAUTION Install the outdoor unit on a rigid base to prevent increasing noise level and vibration Determine the air outlet direction where t...

Страница 9: ...r tube pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing Pipe Reamer Point down Fig 16 Fig 17 Outdoor unit dimension mm WxHxD A mm B mm 530 290 484 600...

Страница 10: ...air conditioner and explain to the client until the problem is solved 2 Power voltage should be in the range of 90 110 of rated voltage 3 The creepage protector and main power switch with a 1 5 times...

Страница 11: ...oosening the screw as shown in Fig 22 4 Ensure the colour of wires of outdoor unit and the terminal Nos are the same to the indoor s respectively 5 Wrap those cables not connected with terminals with...

Страница 12: ...connecting means must be provided and shall be located within sight from and readily accessible from the air conditioner Connecting cable with conduit shall go through the hole of the conduit panel No...

Страница 13: ...the fixed wiring and have an air gap contact separation of at least 3mm in each active phase conductors CAUTION CAUTION CAUTION CAUTION Air and moisture in the refrigerant system have undesirable eff...

Страница 14: ...ully open the handle Lo of the manifold valve 4 Operate the vacuum pump to evacuate After starting evacuation slightly loose theflare nut of the Lo valve on the gas pipe side and check that the air is...

Страница 15: ...If bubbles come out the pipes have leakage 2 Leak detector Use the leak detector to check for leakage Test running Safety and leakage check 14 TEST RUNNING Manual control button AUTO COOL Perform tes...

Страница 16: ...CS120I BP9A1 LH 202000192327 20110613 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Отзывы: