DIAGNOSIS AND SOLUTION (CONT)
Zero Speed Protection for Compressor/Outdoor Fan or Lack of Compressor Phase or Outdoor Fan/
Compressor Speed Malfunction
Description:
None
Recommended parts to prepare:
• Wiring mistake
• Faulty fan assembly faulty
• Faulty fan motor
• Faulty PCB
• Faulty compressor
Troubleshooting and Repair:
Check the wiring between the PCB
and compressor.
Is it improperly wired?
the wires and connectors.
YES
NO
Check the outdoor fan and the
properly?
Please refer to
Fan Speed
Out of Control
ƐŽůƵƟŽŶ
.
NO
Check the compressor
resistance values.
YES
Are they within
acceptable parameters?
Replace the compressor.
NO
Replace the outdoor PCB.
YES