background image

12

 32801000302

Specifications  subject to change without notice.

EXTERNAL STATIC PRESSURE

Using the KSACN0501AAA Wired Controller, the external static
pressure can:

S

Be manually changed to the fan curves SP2, SP3, SP4.

S

Choose the Automatic Airflow “AF” adjustment function which will

automatically identify the static pressure and regulate the amount of

airflow.

Follow instructions to configure:

1. Make sure the test run is done with a dry coil. If the coil is not

dry, run the unit for 2 hours in FAN ONLY mode to dry the coil.

2. Check that both the power supply wiring and the duct

installation have been completed. Check that any closing
dampers are open. Check that the air filter is properly attached to
the air return side passage of the unit.

3. If there is more than one air inlet and/or outlet, adjust the

dampers so that the airflow rate of each air inlet and outlet
conforms with the designed airflow rate. Ensure the unit is in
FAN ONLY mode. Press and set the airflow adjustment button
on the remote control to change the airflow rate from H or L.
Turn the indoor unit OFF.

4. Set the parameters for airflow adjustment. When the system is

OFF, perform the following steps.

a. Press and hold COPY for approximately 4 seconds.

b. Press “+” or “−” to scroll through the menu and make a

selection, either SP or AF.

NOTE:  T1, T2, T26, T3, T4 are sub−menus for thermistors.
Do not select for setting external static pressure.

Fig. 30

 - 

Wired Controller Menu Selection

(1.) If setting the external static pressure manually, select SP

and press CONFIRM. Select the SP number (SP1,
SP2, SP3, SP4 − see static pressure Table 6 and curves
(Figs. 32 through 38)). Power down the unit to lock in
the selection. 

(2.) If choosing the automatic airflow adjustment function,

select AF and press CONFIRM. The system will start
the fan for airflow automatic adjustment. ON will flash
when the fan is running during the Automatic Airflow
adjustment. After 3 to 6 minutes the system stops
operating once the automatic airflow adjustment has
finished.

Fig. 31

 - 

Automatic Airflow ON signal

CAUTION

!

DAMPERS

DO NOT adjust the dampers when the automatic airflow
adjustment is active.

CAUTION

AIRFLOW ADJUSTMENT

S

If there is no charge after the airflow adjustment in the
ventilation paths, be sure to reset the automatic airflow
adjustment.

S

If there is no charge to the ventilation paths after the airflow
adjustment, contact your dealer, especially if this occurs
after testing the outdoor unit or if the unit has been moved
to a different location.

S

Do not use the automatic airflow adjustment with the
remote control, if you are using booster fans, outdoor air
processing unit, or a HRV via duct.

S

If the ventilation paths have been changes, reset airflow
automatic adjustment as described from step 3 onwards.

!

CAUTION

Содержание DLFLDA

Страница 1: ...mages are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 INSTALLATION CLEARANC...

Страница 2: ...ill result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal i...

Страница 3: ...llustration purposes only Notes If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection...

Страница 4: ...EMF area and communication issues exist a 14 2 stranded shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only Sizes...

Страница 5: ...2 29 2 14 2 3 3 5 5 3 3 3 3 40 mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84 18 1 18 In 34 65 8 27 26 54 23 62 5 51 27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 54...

Страница 6: ...6 32801000302 Specifications subject to change without notice DIMENSIONS CONT Airflow Airflow Fig 5 Indoor Unit Sizes 58K...

Страница 7: ...ess Panel 17 7 in 45cm x 17 7 in 45cm 7 8 in 20cm 11 81 in 30cm 4 in 10cm Bottom Return Blower Motor Service Clearance Filter Service Clearance Blower Motor Service Clearance PCB Board Service Clearan...

Страница 8: ...ling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work CAUTION MOUNTING THE UNIT 1 INSTALLING HANGER BOL...

Страница 9: ...he condensate piping should be as close to the unit as possible see Fig 17 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 100 S When multipl...

Страница 10: ...with clamps on both ends c Connect the drainpipe to the connector D see Fig 20 d Plug the power cable of the external pump to CN13 PUMP pin and plug the water level sensor cable to the CN5 WATER to en...

Страница 11: ...T PUMP AND DRAINAGE TEST Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 27 2 Using a piece of tubing or pipe fill the condensate lift p...

Страница 12: ...lection either SP or AF NOTE T1 T2 T26 T3 T4 are sub menus for thermistors Do not select for setting external static pressure Fig 30 Wired Controller Menu Selection 1 If setting the external static pr...

Страница 13: ...40 Pa 24 42 72 98 0 100 24 In WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 1...

Страница 14: ...14 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 32 Fan Performance 40MBDQ09...

Страница 15: ...32801000302 15 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 33 Fan Performance 40MBDQ12...

Страница 16: ...16 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 34 Fan Performance 40MBDQ18...

Страница 17: ...32801000302 17 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 35 Fan Performance 40MBDQ24...

Страница 18: ...18 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 36 Fan Performance 40MBDQ36...

Страница 19: ...32801000302 19 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 37 Fan Performance 40MBDQ48...

Страница 20: ...20 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 38 Fan Performance 40MBDQ58...

Страница 21: ...5 0 56 420 48 3 2 0 75 560 58 3 65 0 952 1000 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS Fig 39 Connection Diagrams sizes 09 to 24 Fig 40 Connection Diagrams sizes 36 and 58 Fig 41 Control and Powe...

Страница 22: ...Table 9 for the flare nut spaces Table 9 Flare Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar C...

Страница 23: ...a wireless remote controller is used relocate the IR receiver within line of sight of remote location using the 6 ft cable included The factory location of the IR receiver is inside the control box s...

Страница 24: ...Open front panel of the indoor unit 4 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUTO Discharge air dir...

Страница 25: ...F6 Compressor low pressure protection H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator...

Страница 26: ...26 32801000302 Specifications subject to change without notice Copyright 2018 International Comfort Products CMNA 1025 Cobb Place Blvd NW Kennesaw GA 30152...

Отзывы: