background image

10

 32801000302

Specifications  subject to change without notice.

CONDENSATE DRAIN AND CONDENSATE LIFT
PUMP INSTALLATION (HORIZONTAL
INSTALLATION)

For sizes 9, 12 and 18, the condensate lift pump has been provided in a
separate box. Use the following steps to install the External Condensate
Lift pump for a Horizontal Installation of the indoor unit.

NOTE:  Drain connections A, B and C are covered with caps.

(1.) For sizes 09 and 12

a. Remove the cap on the drainage outlet.

b. Cut both ends of the rubber tubing provided into a straight one.

c. Connect the drainage outlet and condensate lift pump using the

rubber tubing and secure it with clamps on both ends, as shown
on Figure 19.

d. Plug the power cable of the external pump to CN13 / “PUMP”

pin and plug the water level sensor cable to the CN5 / ”WATER”
to enable the pump (see Fig. 23). 

(2.) For size 18

a. Remove the cap on drain connector B.

b. Connect the drain connector B and the condensate lift pump using

the L rubber hose and secure it with clamps on both ends.

c. Connect the drainpipe to the connector D (see Fig. 20). 

d. Plug the power cable of the external pump to CN13 / “PUMP”

pin and plug the water level sensor cable to the CN5 / “WATER”
to enable the pump (see Fig. 23).

Fig. 19

 - 

Condensate lift pump installation sizes 09−12

 

Connector A

 

Connector B 

Connector C 

Connector D 

Hose 

Fig. 20

 - 

Condensate lift pump installation size 18

(3.) Sizes 24, 36, 48 and 58 have a built−in condensate lift pump. The

drain connections (A, B and C) are covered with caps.

a. Connect the drainpipe to connector D (see Fig. 21).

 

Connector A 

Connector B 

Connector C 

Connector D 

Fig. 21

 - 

Connection of drain pipe to condensate lift pump sizes

24−58

VERTICAL INSTALLATION

Disable the Condensate Lift Pump

The pump must be disabled while the unit is installed vertically (up
flow) or the lift pump assembly is removed from its original position:

S

Open the cover of the E−Parts Box assembly, unplug the “PUMP” pin

to disable the pump function, and short connect the “CN5” plug to

disable the water level sensor (see Fig. 22 and Fig. 23).

 

Remove 

the cover 

 

Short connect the “CN5” 

Unplug the “PUMP” plug pin

Fig. 22

 - 

Unplug the PUMP Pin

Fig. 23

 - 

Condensate Lift Pump Connectors

Содержание DLFLDA

Страница 1: ...mages are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 INSTALLATION CLEARANC...

Страница 2: ...ill result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal i...

Страница 3: ...llustration purposes only Notes If the outdoor unit is higher than the indoor unit prevent rain from flowing into the indoor unit along the connection pipe by creating a downward arc in the connection...

Страница 4: ...EMF area and communication issues exist a 14 2 stranded shielded wire can be used to replace L2 and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only Sizes...

Страница 5: ...2 29 2 14 2 3 3 5 5 3 3 3 3 40 mm 700 200 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84 18 1 18 In 34 65 8 27 26 54 23 62 5 51 27 80 1 97 5 35 30 79 7 48 1 57 36 22 20 3 07 5 83 3 46 4 41 54...

Страница 6: ...6 32801000302 Specifications subject to change without notice DIMENSIONS CONT Airflow Airflow Fig 5 Indoor Unit Sizes 58K...

Страница 7: ...ess Panel 17 7 in 45cm x 17 7 in 45cm 7 8 in 20cm 11 81 in 30cm 4 in 10cm Bottom Return Blower Motor Service Clearance Filter Service Clearance Blower Motor Service Clearance PCB Board Service Clearan...

Страница 8: ...ling grid is supported separately from the unit The ceiling grid must not be supported by any part of the unit or any associated wiring or piping work CAUTION MOUNTING THE UNIT 1 INSTALLING HANGER BOL...

Страница 9: ...he condensate piping should be as close to the unit as possible see Fig 17 S Condensate piping should slope downward in the direction of condensate flow with a minimum gradient of 1 100 S When multipl...

Страница 10: ...with clamps on both ends c Connect the drainpipe to the connector D see Fig 20 d Plug the power cable of the external pump to CN13 PUMP pin and plug the water level sensor cable to the CN5 WATER to en...

Страница 11: ...T PUMP AND DRAINAGE TEST Follow these steps to perform the test 1 Remove the test cover by rotating it counter clockwise as shown in Fig 27 2 Using a piece of tubing or pipe fill the condensate lift p...

Страница 12: ...lection either SP or AF NOTE T1 T2 T26 T3 T4 are sub menus for thermistors Do not select for setting external static pressure Fig 30 Wired Controller Menu Selection 1 If setting the external static pr...

Страница 13: ...40 Pa 24 42 72 98 0 100 24 In WG 0 10 0 216 0 336 0 528 0 0 64 Pa 25 54 84 132 0 160 36 In WG 0 168 0 312 0 48 0 62 0 0 64 Pa 42 78 120 155 0 160 48 In WG 0 18 0 404 0 616 0 64 0 0 64 Pa 45 101 154 1...

Страница 14: ...14 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 32 Fan Performance 40MBDQ09...

Страница 15: ...32801000302 15 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 33 Fan Performance 40MBDQ12...

Страница 16: ...16 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 34 Fan Performance 40MBDQ18...

Страница 17: ...32801000302 17 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 35 Fan Performance 40MBDQ24...

Страница 18: ...18 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 36 Fan Performance 40MBDQ36...

Страница 19: ...32801000302 19 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 37 Fan Performance 40MBDQ48...

Страница 20: ...20 32801000302 Specifications subject to change without notice FAN PERFORMANCES AT VARYING STATIC PRESSURES CONT Fig 38 Fan Performance 40MBDQ58...

Страница 21: ...5 0 56 420 48 3 2 0 75 560 58 3 65 0 952 1000 LEGEND FLA Full Load Amps CONNECTION DIAGRAMS Fig 39 Connection Diagrams sizes 09 to 24 Fig 40 Connection Diagrams sizes 36 and 58 Fig 41 Control and Powe...

Страница 22: ...Table 9 for the flare nut spaces Table 9 Flare Nut Spacing OUTER DIAM mm A mm Max Min 1 4 6 35 0 05 1 3 0 03 0 7 3 8 9 52 0 06 1 6 0 04 1 0 1 2 12 7 0 07 1 8 0 04 1 0 5 8 15 88 0 09 2 2 0 08 2 0 Bar C...

Страница 23: ...a wireless remote controller is used relocate the IR receiver within line of sight of remote location using the 6 ft cable included The factory location of the IR receiver is inside the control box s...

Страница 24: ...Open front panel of the indoor unit 4 Push the manual switch once to energize the unit The set conditions of manual operation are as follows Preset set point 76_F 24_C Fan speed AUTO Discharge air dir...

Страница 25: ...F6 Compressor low pressure protection H 4 times X E3 Indoor fan speed has been out of control H 5 times X E4 Indoor room temperature sensor T1 open circuit or short circuit H 6 times X E5 Evaporator...

Страница 26: ...26 32801000302 Specifications subject to change without notice Copyright 2018 International Comfort Products CMNA 1025 Cobb Place Blvd NW Kennesaw GA 30152...

Отзывы: