background image

8

 32801000801

Specifications  subject to change without notice.

INSTALLATION TIPS

Ideal installation locations include:

Outdoor Unit

S

  A location which is convenient to installation and not exposed to

strong wind.

S

  A location which can bear the weight of outdoor unit and where  the

outdoor unit can be mounted in a level position.

S

  A location which provides appropriate clearances (see Fig. 3).

S

  Do not install the indoor or outdoor units in a location with special

environmental conditions. For those applications, contact your
Ductless Split representative.

OUTDOOR UNIT INSTALLATION

1. Use a rigid base to support unit in a level position.

2. Locate outdoor unit and connect piping and wiring.

CAUTION

!

EQUIPMENT DAMAGE HAZARD

Failure to follow  this caution may result in equipment damage
or improper operation.

In regions with snowfall and cold temperatures, avoid
installing the outdoor unit in areas where it can be covered by
snow. If the outdoor unit is installed in areas where heavy
snow is expected, a field supplied ice or snow stand and/or
field supplied−installed wind baffle should be installed to
protect the unit from snow accumulation and/or blocked air
intake. Blocking the air intake may result in reduced airflow,
significantly reduced performance and damage to the
equipment.

NOTE:   Install the outdoor unit on a rigid base to reduce noise
levels and vibration. Determine the optimal air outlet direction to
prevent discharged air from being blocked. If the installation site
is exposed to strong winds such as a coastal areas, ensure the fan’s
proper operation by installing the unit lengthwise along the wall
or use dust or shield plates. If the unit needs to be suspended, the
installation bracket should comply with the suspension
requirements in the installation bracket diagram. The installation
wall should be solid brick, concrete or the same intensity
construction, or take steps to reinforce and dampen the support.
The connection between the bracket and the wall as well as the
bracket and the air conditioner should be firm, stable and reliable.
Ensure there is no obstacle which may block the radiating air.

Strong

wind

A07350

Fig. 5

 - 

High Wind Installation

MAKE REFRIGERANT PIPING CONNECTIONS
(OUTDOOR UNIT)

IMPORTANT:

 

Use refrigeration grade tubing ONLY. No other type

of tubing may be used. Use of other types of tubing will void
manufacturer’s warranty.

Do not open service valves or remove protective caps from

 

tubing ends

until all the connections are made.

Bend tubing with bending tools to avoid kinks and flat spots.

Keep the tubing free of dirt, sand, moisture, and other contaminants

 

to

avoid damaging the refrigerant system.

Avoid sags in the suction line to prevent the formation of oil

 

traps.

 

Insulate

each tube with minimum 3/8−in. (10 mm) wall thermal pipe insulation.
Inserting the tubing into the insulation before making

 

the connections will

save time and improve installation quality.

1. Remove the service valve cover, if provided with the unit.
2. Cut the pipe, with a pipe cutter, at 90 degrees (see Fig. 6).
3. Remove the service connection, if provided with the unit.

Oblique

DŽ

90

Roughness

Burr

A150767

Fig. 6

 - 

Cut the Pipe

4. Remove all the burrs from the cut cross section of the pipe

avoiding any burrs inside the tubes.

5. Remove the flare nuts attached to the indoor and outdoor units.

6. Install the correct size flare nut onto the tubing and make a flare

connection. Refer to Table 6 for the flare nut spaces.

Table 6—Flare Nut Spacing

OUTER DIAM. (mm)

A (mm)

Max.

Min.

Ø1/4”(6.35)

0.05 (1.3)

0.03(0.7)

Ø3/8”(9.52)

0.06 (1.6)

0.04(1.0)

Ø1/2”(12.7)

0.07 (1.8)

0.04(1.0)

Ø5/8”(15.88)

0.09 (2.2)

0.08(2.0)

Bar

Copper pipe

Clamp handle

Red arrow mark

Cone

Yoke

Handle

Bar

"A"

A150768

Fig. 7

 - 

Flare Nut Spacing

7. Apply a small amount of refrigerant oil to the flare connection

on the tubing.

8. Align center of the pipes and/or service valve.

Indoor unit tubing

Flare nut

Piping

A150769

Fig. 8

 - 

Align Pipe Center

9. Connect both the liquid and gas piping to the indoor unit

10. Tighten the flare nut using a torque wrench as specified in the

Table 7.

11. Complete the installation.

Table 7—Tightening Torque

PIPE DIAMETER

INCH (mm)

TIGHTENING TORQUE

Ft-lb

N-m

Ø1/4” (6.35)

10 to 13

13.6 to 17.6

Ø3/8” (9.5

2

)

24 to 31

32.5 to 42.0

Ø1/

2

” (1

2

.7)

37 to 46

50.1 to 62.3

Ø5/8” (15.88)

50 to 60

67.7 to 81.3

Содержание DLCSRAH09AAJ

Страница 1: ...tarting the installation Images are for illustration purposes only Actual models may differ slightly TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 5 DIMENSIONS OUTDOOR 6 CLEARANCES OUTDOOR 7 INSTALLATION TIPS 8 OUTDOOR UNIT INSTALLATION 8 ELECTRICAL DATA 11 CONNECTION DIAGRAMS 11 SYSTEM VACUUM AND CHARGE 12 START UP 13 TROUBLESHOOTING 13 ...

Страница 2: ...entifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation WARNING ELECTRIC...

Страница 3: ...king a downward arc in the connection pipe before it enters the wall to the indoor unit This will ensure that rain will drip from the connection pipe before it enters the wall Piping and the interconnecting wiring are field supplied Figure 1 is only a sketch Different models may differ slightly Table 2 lists the units covered in this document Table 2 Unit Sizes SYSTEM TONS kBTUh VOLTAGE PHASE OUTD...

Страница 4: ... indoor height difference IU higher than OU ft m 33 10 33 10 33 10 33 10 66 20 66 20 82 25 98 30 Max Piping Length with no additional refrigerant charge per System Standard Piping length ft m 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 24 6 7 5 Total Max Piping Length per system ft m 82 25 82 25 82 25 82 25 98 30 98 30 164 50 213 65 Additional refrigerant charge between Standard...

Страница 5: ...talled in a high Electromagnetic field EMF area and communication issues exists a 14 2 stranded shielded wire can be used to replace L2 N and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation Wires should be sized based on NEC and local codes CAUT...

Страница 6: ... 81 554 27 64 702 31 89 810 31 89 810 31 89 810 Width W in mm 30 31 770 31 5 800 31 5 800 31 5 800 33 27 845 37 24 946 37 24 946 37 24 946 Depth D in mm 11 81 300 13 11 333 13 11 333 13 11 333 14 29 363 16 54 420 16 54 420 16 54 420 L1 in mm 19 2 487 20 24 514 20 24 514 20 24 514 21 26 540 26 5 673 26 5 673 26 5 673 L2 in mm 11 73 298 13 39 340 13 39 340 13 39 340 13 8 350 15 87 403 15 87 403 15 8...

Страница 7: ...ounted at least 2in 50mm above the maximum anticipated snow depth 118in 300cm ormore 19in 48cm ormore onamultipleparallel unitarrangement 4in 10cm ormoreon asingleparallelunit arrangement 24in 60cm ormore 59in 150cm ormoreona multipleparallel unitarrangement 24in 61cm ormore onasingleparallel unitarrangement 9 8in 25cm ormorefor properairflow 24in 61cm or moreis recommended forservice 9 8in 25cm o...

Страница 8: ...ld be firm stable and reliable Ensure there is no obstacle which may block the radiating air Strong wind A07350 Fig 5 High Wind Installation MAKE REFRIGERANT PIPING CONNECTIONS OUTDOOR UNIT IMPORTANT Use refrigeration grade tubing ONLY No other type of tubing may be used Use of other types of tubing will void manufacturer s warranty Do not open service valves or remove protective caps from tubing ...

Страница 9: ...nit capacity and voltage 7 Ground unit in accordance with NEC and local electrical codes 8 Use lock nuts to secure conduit 9 Reinstall field wiring cover CAUTION EQUIPMENT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation S Be sure to comply with local codes while running wire from indoor unit to outdoor unit S Every wire must be connected firmly Loo...

Страница 10: ...int Images are for illustration purposes only CAUTION In cold climates ensure the drain hose is as vertical as possible to ensure swift water drainage If water drains too slowly it can freeze in the hose and flood the unit NOTE Basepan built in with multiple holes for proper draining during defrost For applications where it is required to seal these holes and re direct the condensate drain rubber ...

Страница 11: ...ble limits of the voltage range at which the unit will operate satisfactorily LEGEND FLA Full Load Amps MCA Minimum Circuit Amps RLA Rated Load Amps CONNECTION DIAGRAMS S L N 115 1 60 Main Power Supply 115 1 60 L N S L N Power to Indoor Unit CONNECTING CABLE OUTDOOR TO INDOOR GND Ground Indoor Signal High Voltage 115 1 60 115 1 60 FIELD POWER SUPPLY GND Indoor Signal High Voltage Indoor Unit Power...

Страница 12: ...ow side valve A07361 Fig 14 Manifold Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth The deep vacuum method is the best way to assure a system is free of air and liquid water see Fig 15 500 MINUTES 0 1 2 3 4 5 6 7 1000 1500 LEAK IN SYSTEM VACUUM TIGHT TOO WET TIGHT DRY SY...

Страница 13: ...the systems are equipped with diagnostic code display LEDs on both the indoor and outdoor units The outdoor diagnostic display is two LEDs Red and Green on the outdoor unit board and is limited to very few errors The indoor diagnostic display is a combination of flashing LEDs on the display panel or the front of the unit There may be a few error codes displayed in the indoor unit that might relate...

Страница 14: ...14 32801000801 Specifications subject to change without notice Copyright 2018 International Comfort Products CMNA 1025 Cobb Place Blvd NW Kennesaw GA 30152 ...

Отзывы: