9.2.2
Indoor / outdoor unit’s communication diagnosis and solution(E1)
Error Code
E1
Malfunction decision
conditions
Indoor unit does not receive the feedback from outdoor unit during
110
seconds and this condition happens four times continuously.
Supposed causes
●
Wiring mistake
●
Indoor or outdoor PCB faulty
Trouble shooting:
Measure Vs, is it positive fluctuation?
(Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
Measure Vs, is it positive fluctuation?
(Vs is the voltage between S and N of
outdoor unit. Red pan-S, Black pan-N)
Yes
Power off, then restart the unit 2 minutes later
Power off, then restart the unit 2 minutes later
No
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Replace the outdoor main PCB.
Power on. Is the error
extinguished?
Check the outdoor wiring connection
Check the outdoor wiring connection
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Replace the indoor main PCB.
Power on. Is the error
extinguished?
Yes
Replace the outdoor main PCB.
Replace the outdoor main PCB.
No
Replace the indoor main PCB.
Replace the indoor main PCB.
No
Check the indoor wiring connection
Check the indoor wiring connection
Yes
Yes
Check whether reactor
is normal?
Check whether reactor
is normal?
Yes
Replace the reactor
Replace the reactor
No
Содержание Aurora MOF-24HFN1-QRD0GW
Страница 1: ...Aurora 3D Inverter Series Service Manual 2014 ABSEU A1 1410...
Страница 9: ......
Страница 12: ...5 Wiring Diagram 5 1 Indoor Unit MSABAU 09HRDN1 QRC8GW MSABBU 12HRDN1 QRC8GW MSABDU 18HRDN1 QRC8GW...
Страница 13: ...MSABEU 24HRDN1 QRC8GW...
Страница 14: ...5 2 Outdoor Unit MOZ 09HFN1 QRD0GW MOZ 12HFN1 QRD0GW...
Страница 15: ...MOZ1 18HFN1 QRDOGW...
Страница 16: ...MOF 22HFN1 QRD0GW...
Страница 23: ...Be sure to check for gas leakage...