6 Installation Details
6.1 Wrench torque sheet for installation
Outside diameter
Torque
Additional tightening torque
mm
inch
N.cm
N.cm
Ф6.35
1/4
1500(153kgf.cm)
1600(163kgf.cm)
Ф9.52
3/8
2500(255kgf.cm)
2600(265kgf.cm)
Ф12.7
1/2
3500(357kgf.cm)
3600(367kgf.cm)
Ф15.9
5/8
4500(459kgf.cm)
4700(479kgf.cm)
Ф19
3/4
6500(663kgf.cm)
6700(683kgf.cm)
6.2 Connecting the cables
The power cord of connect should be selected according to the following specifications sheet.
Rated current of appliance
Nominal cross-
sectional area (mm²)
>3 and ≤6
0.75
>6 and ≤10
1
>10 and ≤16
1.5
>16 and ≤25
2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated
on the nameplate which located on the side panel of the unit. Please refer to the nameplate before
selecting the cable, fuse and switch.
Содержание Aurora MOF-24HFN1-QRD0GW
Страница 1: ...Aurora 3D Inverter Series Service Manual 2014 ABSEU A1 1410...
Страница 9: ......
Страница 12: ...5 Wiring Diagram 5 1 Indoor Unit MSABAU 09HRDN1 QRC8GW MSABBU 12HRDN1 QRC8GW MSABDU 18HRDN1 QRC8GW...
Страница 13: ...MSABEU 24HRDN1 QRC8GW...
Страница 14: ...5 2 Outdoor Unit MOZ 09HFN1 QRD0GW MOZ 12HFN1 QRD0GW...
Страница 15: ...MOZ1 18HFN1 QRDOGW...
Страница 16: ...MOF 22HFN1 QRD0GW...
Страница 23: ...Be sure to check for gas leakage...