Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
89
25/35/65/80/130kW module
A
B
D
C
Input of airflow
Input of airflow
unit
E
Input of airflow
Input of airflow
unit
The recommend space parameter
Series
Module
Installation space (mm)
A
B
C
D
E
SS
MC-SS35/RN1L
≥1500
≥2000
≥2000
≥1500
≥8000
MC-SS65/RN1L
MC-SS80/RN1L
MC-SS130/RN1L
SP
MC-SP25-RN1L
MC-SP25M-RN1L
MC-SP35-RN1L
MC-SP35M-RN1L
MC-SP65-RN1
● Space requirements for parallel installation of multiple scroll units
To avoid back flow of the air in the condenser and operational faults of the unit, the parallel installation of
multiple scroll units can follow the direction A and D as shown in the figure above, the spaces between the
unit and the obstacle are given in the figure above, and the space between adjacent scroll units should not
be less than 300mm; the installation can also follow the direction B and C as shown in the figure above, the
spaces between the unit and the obstacle are given in the figure above, and the space between adjacent
scroll units should not be less than 600mm; the installation can also follow the direction combination of A
and D, and B and C, the spaces between the unit and the obstacle are given in the figure above, the space
between adjacent scroll units in the direction A and D should not be less than 300mm, and the space
between adjacent scroll units in the direction B and C should not be less than 600mm.
If the spaces mentioned above cannot be met, the air passing from the unit to the coils may be restricted, or
back flow of air discharge may occur, and the performance of the unit may be affected, or the unit may fail to
operate.
Series
Model
Max unit combined
quantity
L(mm)
M(mm)
N(mm)
SS
MC-SS35/RN1L
16
≥
600
≥
300
≥
300
MC-SS65/RN1L
16
≥
600
≥
300
≥
300
MC-SS80/RN1L
16
≥
600
≥
300
≥
300
MC-SS130/RN1L
16
≥
600
≥
300
≥
300
SP
MC-SP25-RN1L
16
≥
600
≥
300
≥
300
MC-SP25M-RN1L
16
≥
600
≥
300
≥
300
MC-SP35-RN1L
16
≥
600
≥
300
≥
300
MC-SP35M-RN1L
16
≥
600
≥
300
≥
300
MC-SP65-RN1
16
≥
600
≥
300
≥
300
13.1.3 Installation foundation
The unit should be located on the horizontal foundation, the ground floor or the roof which can bear
Содержание Aqua Tempo Super MC-SP25-RN1L
Страница 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Страница 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Страница 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Страница 30: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 28 SP series MC SP25 RN1L...
Страница 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Страница 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Страница 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Страница 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Страница 37: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 35 MC SP25M RN1L MC SP35M RN1L...
Страница 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Страница 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Страница 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Страница 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Страница 66: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 64 MC SS130 RN1L 32 35...
Страница 68: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 66 SP seris MC SP25 RN1L...
Страница 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...