MCAC-ATSM-201606 Aqua Tempo Super Series air cooled scroll chiller unit (50Hz)
78
Short circuit comes out from motor or connecting
interface.
Confirm resistors at motor are connected
corresponding to terminals.
Compressor stops
because of integrate
temperature sensor or
air discharge
temperature protection.
Over high or over low voltage.
Confirm voltage not higher or lower than the rated
v/-10%.
Over high air discharging pressure or excessive low
air suction pressure.
Adjust refrigerant charge volume.
Clean the heat exchanger.
Check the EXV, capillary, filter.
Component error.
Check the integrated temperature sensor after
motor is cool down.
Compressor stops
because of low pressure
protection.
Filter of electronic expanding valve is blocked.
Replace a new filter.
Low voltage switch error.
If the switch is defective, please replace a new
one.
Excessive low air suction pressure.
Add the refrigerant.
Clean the heat exchanger.
Check the EXV, capillary, filter.
Abnormal noise gives
out form compressor.
Liquid refrigerant flows into compressor from
evaporator result in liquid slugging.
Adjust refrigerant charge volume.
Aging of compressor.
Replace a new compressor.
Compressor can’t start.
Over current relay trip up, fuse burnt out.
Replace damaged assembly.
Control circuit without power though.
Check the wring of control system.
High voltage or low voltage protection.
Reference to mention in above the parts of air
suction and discharge pressure error.
Coils inside contactor are burnt out.
Replace damaged assembly.
Wrong connection of phase sequence.
Re-connect and adjust the any 2 wires among 3
phases.
Water system error and flow volume controller short
connection.
Check water system.
Error signal delivered from wired controller.
Find out the error type and carry out the
corresponding measure to settle.
Air side heat exchanger
excessive frost.
4-way valve or thermal resistor error.
Check the running state. Replace a new one if
necessary.
Air loop short circuit.
Settle the short circuit of air discharge.
With noise.
Fixing screws at panel are loosen.
Fix up all assemblies.
Содержание Aqua Tempo Super MC-SP25-RN1L
Страница 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Страница 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Страница 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Страница 30: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 28 SP series MC SP25 RN1L...
Страница 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Страница 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Страница 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Страница 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Страница 37: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 35 MC SP25M RN1L MC SP35M RN1L...
Страница 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Страница 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Страница 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Страница 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Страница 66: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 64 MC SS130 RN1L 32 35...
Страница 68: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 66 SP seris MC SP25 RN1L...
Страница 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...