Aqua Tempo Super Series air cooled scroll chiller unit (50Hz) MCAC-ATSM-201606
125
Yes
No
Yes
No
Main page
▼
Press “Setting” key twice to enter hour setting
interface of “Timer 1 On”
▼
▼
▼
Press “ ” key to enter minute setting interface of
“Timer 1 On”, adjust the minute number to be 10
Press “ ” key to enter hour setting interface of
“Timer 1 Off”, adjust the hour number of “Timer 1
Of
f” to be 12
Through the “▲” or “▼” key, set the hour
number of “Timing 1 On” to be 07
Press “ ” key to enter minute setting interface of
“Timer 1 Off”, adjust the minute number to be 30
The setting steps of
“Timer 2” and “Timer 3” are the same as “Timer 1”,
after setting all the settings then press
“OK” key, and the3 timing periods
will be effective, and then back to the main page.
“Timer 1” setting
failed, after 7
seconds, the
page shift to
Successfully set the On time of
“Timer 1” to be 07:10 and Off time
of “Timer 1 Off ” to be 12:30, then
back to the main page.
Finish setting the On time of
“Timer 1” to be 07:10 and Off
time to be 12:30, then enter the
setting of “Timer 2”.
Whether press “OK” key
Whether press “ ” key
During any period of timing setting to press “OK” key , then the timing period has been set will be effective
(only when the “On” and “Off” of one timing period have been set then this period setting can be finished).
Press “Cancel” then cancel the setting. Query timing information: if query the timing hour which has been set,
press “ ” or “
▲
” key under main page, the On and Off time of Timer1, Timer 2 and Timer3 will be displayed
in turns.
Cancel timing: long press “Cancel” key for 3 seconds, then all the effective timing periods will be cancelled.
Note:
5:00
8:00
10:00
12:00
18:00
22:00
5:00
8:00
7:00
12:00
To avoid the timing error, each period of timing should not be crossed. E.g.:
Correct:
Wrong:
TIMER 1
TIMER 2
TIMER 1
TIMER 2
TIMER 3
3) Set working mode (valid when wired controller set to 2,3,4)
Press
“
SET
”
key 3 times to enter the working mode setting when the main unit is off power. press the
“▲”
or
“▼”
key to adjust , press
“
OK
”
key or wait for 7 seconds to be effective, and back to the main page;
During setting process to press
“
Cancel
”
key then will exit without saving. The controller will show
different working mode when it is applied to different main unit and set to 2,3,4 respectively.
Содержание Aqua Tempo Super MC-SP25-RN1L
Страница 27: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 25 MC SS65 RN1L...
Страница 28: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 26 MC SS80 RN1L...
Страница 29: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 27 MC SS130 RN1L...
Страница 30: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 28 SP series MC SP25 RN1L...
Страница 31: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 29 MC SP25M RN1L...
Страница 32: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 30 MC SP35 RN1L...
Страница 33: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 31 MC SP35M RN1L...
Страница 34: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 32 MC SP65 RN1L...
Страница 37: ...Aqua Tempo Super Series air cooled scroll chiller unit 50Hz MCAC ATSM 201606 35 MC SP25M RN1L MC SP35M RN1L...
Страница 38: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 36 MC SP65 RN1L...
Страница 60: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 58 MC SS65 RN1L...
Страница 62: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 60 MC SS65 RN1L...
Страница 64: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 62 MC SS80 RN1L...
Страница 66: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 64 MC SS130 RN1L 32 35...
Страница 68: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 66 SP seris MC SP25 RN1L...
Страница 70: ...MCAC ATSM 201606 Aqua Tempo Super Series air cooled scroll chiller unit 50Hz 68 MC SP25M RN1L...