7.3 Main Protection
7.3.1 Time Delay at restart for compressor.
Less than 1 minute delay for the 1
st
time
start-up and 3 minutes delay for others.
7.3.2 Sensor protection at open circuit and
breaking disconnection.
7.3.3 Zero crossing detection error
protection
If AC can not detect zero crossing signal for 4
minutes or the zero crossing signal time interval
is not correct, the unit will stop and the LED will
display the failure. The correct zero crossing
signal time interval should be between 6-13ms.
7.3.4 Fan Speed is out of control
When Indoor Fan Speed is too low(lower than
300RPM) lasting 2 minutes, the unit stops and
LED displays failure information and can’t returns
to normal operation automatically.
7.3.5 Current protection
A
B
C
Resume
The current exceeds setting value for certain
time, the compressor and outdoor fan will shut
off.
7.3.6 Indoor fan delayed open function
When the unit starts up, the indoor fan will open
4s later.If the unit runs in heating mode, the
indoor fan will be also controlled by anti-cold
wind function.
7.3.7 Refrigerant leakage detection
This function is only active in cooling mode. It
can better prevent the compressor being
damaged by refrigerant leakage or compressor
overload.
Open condition:
When compressor is active, the value of the
Coil temperature of evaporator T2 has no
change or very little change.
Содержание ABSEU-A4-1511
Страница 1: ...Aurora ON OFF SERIES Service Manual 2015 ABSEU A4 1511...
Страница 8: ...For MSABA 07HRN1 QC2 MSABB 09ARN1 QB8 MSABA 09HRN1 QC2...
Страница 10: ...For MSABF 36HRN1 RC0W...
Страница 12: ...For MOAB30 07HN1 QC2 MOAB31 09HN1 QC2...
Страница 14: ...For MOCA30 24HN1 QB8W MOCA30 18HN1 QB8 MOCA30 24HN1 QB8W...
Страница 15: ...For MOD30 36HN1 RC0W 946 W 810 H 1030 W1 673 A 403B 455D3 410 D 810 H 455 D3 15 57 H1 117 H2 73 12 24...