Service manual
36
11.4.3 Auto fan at cooling mode:
Condition
T=Indoor Temp.-Setting Temp.
Indoor fan speed
T<1.5
℃
Low
1.5
℃
<T<4
℃
Mid.
Room temp. up
T>4
℃
High
T> 3
℃
High
1
℃
<T<3
℃
Mid.
Room temp. down
T<1
℃
Low
11.4.4 Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Evaporator
Temp.
Compressor
0
℃
<T< 4
℃
Decrease frequency of compressor
T< 0
℃
Off
11.4.5 Current protection
Model
Current
Compressor
I>18 A
Off
14.5A<I<18A
Decrease frequency of
compressor
Current up
MSH-18HRIN1
I< 12.0A
On
I>17.5 A
Off
14.0A<I<17.5A
Decrease frequency of
compressor
Current down
MSH-18HRIN1
I< 11.5A
On
11.4.6 Rated capacity test
Set mode to cooling mode
Set temp. to 17°C
Set fan speed to high speed
Push turbo button 5 times in 10 seconds.
Using special remoter controller
After 5 hours, cancel rated capacity test
Turbo function
Increasing frequency of compressor
After operating 30 minutes, return automatically to the mode and temp. previously selected.
11.5. Dehumidifying mode
11.5.1 The 4-way valve is off
11.5.2 the indoor fan is fixed in breeze speed
11.5.3 Compressor run in low frequency
11.5.4 Low room temperature protection:
11.5.5 When room temperature decreases to below 10
℃
, compressor and outdoor fan will stop
(indoor fan is Breeze). Dehumidifying operation will be resumed when room temperature restores to
over 12
℃
.
11.5.6 At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same as
that of cooling mode.
11.6. Heating mode
11.6.1. Generally, the 4-way valve is open at heating mode, but it is closed at defrosting. 4-way valve
must delay 2 minutes compared with compressor if the compressor changed into non-heating mode
or turned off. 4-way valve doesn't delay in dehumidifying mode.
11.6.2. Generally, the outdoor fan is turned off with the on-off action of compressor in heating mode,
except for the defrosting mode or the end of defrost.
11.6.3. Action of compressor and outdoor fan motor at heating mode: compressor must run for 7
minutes after starting and then judge temperature. Meanwhile other protections are still valid.
Содержание AAC-18ISCH
Страница 4: ......
Страница 16: ...Service manual 12 5 Refrigerant cycle diagram...
Страница 20: ...Service manual 16 7 1 5 Indoor main PCB Inverter Eco...
Страница 21: ...Service manual 17 7 1 6 Outdoor main PCB Inverter Eco...
Страница 22: ...Service manual 18 7 2 Wiring diagram 7 2 1 MSH 18HRDN1...
Страница 23: ...Service manual 19 7 2 2 MSC 18HRIN1...
Страница 24: ...Service manual 20 7 2 3 MSE 09HRIN2 MSE 12HRIN2...
Страница 25: ...Service manual 21 7 2 4 MSG 07HRIN2 MSG 09HRIN2 MSG 12HRIN2 1 Indoor unit 7 9K 2 Indoor unit 12K...
Страница 26: ...Service manual 22 3 Outdoor unit...