Service manual
35
11. Electronic function
11.1. Display board
1
22
3
4
5
6
11.1.1. AUTO indicator
This indicator illuminates when the air conditioner is in AUTO operation.
11.1.2. TIMER indicator
This indicator illuminates when TIMER is set ON/OFF.
11.1.3. PRE.-DEF. Indicator (For Cooling & Heating models only)
This indicator illuminates when the air conditioner starts defrosting automatically or when the warm
air control feature is activated in heating mode.
11.1.4. TEMPERATURE indicator
Usually it displays the temperature settings. When change the setting temperature, this indicator
begins to flash, and stops 20 seconds later.
It displays the room temperature when the air conditioner is in FAN only operation.
When the unit stops operation, it returns
to original factory settings.
Displays the malfunction code or protection code.
11.1.5. OPERATION indicator
This indicator flashes after power is on and illuminates when the unit is in operation.
11.1.6. FREQUENCY indicator
This indicator appears only when the compressor is in operation and indicates the current operating
frequency.
11.2. Protection
11.2.1. 3 minutes delay at restart for compressor.
11.2.2. Temperature protection of compressor top, compressor stops when the temp. of top of
compressor is more than 115
℃
, compressor runs when the temp. of top of compressor is less than
100
℃
.
11.2.3. Voltage protection, unit stop when the voltage is more than 260V and less than 175V.
11.2.4. Inverter module Protection, Inverter module Protection itself has a protection function against
current, voltage and temperature.
11.2.5. Sensor protection at open circuit and breaking disconnection
11.2.6. Fan Speed is out of control. When Indoor Fan Speed is too high(higher than 2100RPM)or too
low(lower than 300RPM), the unit stops and LED displays failure information and can’t return
to
normal operation automatically.
11.2.7. Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and can’t return to normal operation automatically.
11.3. Fan-only mode
Fan speed is high/mid/low/ Auto
11.4. Cooling mode
11.4.1. The 4-way valve is closed at cooling mode.
11.4.2. The action of the compressor and the outdoor fan:
Condition
T=Indoor Temp.
Compressor Outdoor
fan
T> Ts+1
On
On
Room temp. up
T<Ts+1 Off
Off
T> Ts
On
On
Room temp. down
T<Ts Off
Off
Содержание AAC-18ISCH
Страница 4: ......
Страница 16: ...Service manual 12 5 Refrigerant cycle diagram...
Страница 20: ...Service manual 16 7 1 5 Indoor main PCB Inverter Eco...
Страница 21: ...Service manual 17 7 1 6 Outdoor main PCB Inverter Eco...
Страница 22: ...Service manual 18 7 2 Wiring diagram 7 2 1 MSH 18HRDN1...
Страница 23: ...Service manual 19 7 2 2 MSC 18HRIN1...
Страница 24: ...Service manual 20 7 2 3 MSE 09HRIN2 MSE 12HRIN2...
Страница 25: ...Service manual 21 7 2 4 MSG 07HRIN2 MSG 09HRIN2 MSG 12HRIN2 1 Indoor unit 7 9K 2 Indoor unit 12K...
Страница 26: ...Service manual 22 3 Outdoor unit...