45
8.4.7.4 Timer on/off. The machine will turn on automatically when reaching the setting “on” time, and
then turn off automatically when reaching the setting “off” time.
8.4.7.5 Timer off/on. The machine will turn off automatically when reaching the setting “off” time, and
then turn on automatically when reaching the setting “on” time.
8.4.7.6 The timer function will not change the AC current operation mode. Suppose AC is off now, it will
not start up firstly after setting the “timer off” function. And when reaching the setting time, the timer
LED will be off and the AC running mode has not been changed.
8.4.7.7 The setting time is relative time.
8.4.8 Sleep function mode
8.4.8.1 Operation time in sleep mode is 7 hours. After 7 hours the AC quits this mode and turns off.
8.4.8.2. Operation process in sleep mode is as follow:
When cooling, the setting temperature rises 1
℃
(be lower than 30
℃
) every one hour, 2 hours later the
setting temperature stops rising and indoor fan is fixed as low speed.
When heating, the setting temperature decreases 1
℃
(be higher than 17
℃
) every one hour, 2 hours
later the setting temperature stops rising and indoor fan is fixed as low speed. (Anti-cold wind function
has the priority)
8.4.8.3 Timer setting is available
8.4.8.4 When user uses timer off function in sleep mode (or sleep function in timer off mode), if the
timing is less than 7 hours, sleep function will be cancelled when reaching the setting time. If the timing
is more than 7 hours, the machine will not stop until reaches the setting time in sleep mode.
8.4.9 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto-restart
module. In case of a sudden power failure, the module memorizes the setting conditions before the
power failure. The unit will resume the previous operation setting (not including swing function)
automatically after 3 minutes when power returns.
If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes
and turn to auto mode as 24
℃
setting temp.
If AC is off before power off and AC is required to start up now, the compressor will have 1 minute
delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
Содержание 9ASI-A-1209
Страница 1: ...LUNA INVERTER SERIES Service Manual 2012 9ASI A 1209...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MS9AU 09HRDN1 QRC4W MS9AU 12HRDN1 QRC4W MS9AU 18HRDN1 QRC4W...
Страница 13: ...13 MS9A 24HRDN1 QRC4W...
Страница 14: ...14 5 2 Outdoor Unit MOB 09HFN1 QRC4W MOB 12HFN1 QRC4W MOC 18HFN1 QRC4W...
Страница 15: ...15 MOF 24HFN1 QRC4W...
Страница 26: ...26 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 31: ...31 continuous 4 seconds and this situation happens 3 times the display area will show EC and AC will turn off...
Страница 48: ...48 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution E0...
Страница 49: ...49 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...
Страница 51: ...51 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 53: ...53 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...