38
Meanwhile, the maximum frequency is limited by the indoor fan speed.
Indoor fan speed
Maximum frequency
High speed/8 degree heating/ turbo function
No limit
Medium speed
FHeatMaxMidFan
Low speed/sleep mode
FHeatMaxLowFan
Silent mode
Fixed at F3
If users switch on AC by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, the frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
+5.0
+4.5
+3.5
+3.0
+2.5
+2.0
+1.5
T1-Ts+
¦ ¤
T
+1.0
I
G
F
E
D
C
B
A
+0.5
+4.0
H
J
While the zones of A,B,C... are corresponding to different compressor running frequency.
∆
T=0
℃
as default.
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A: Increase the frequency to 3 grade higher until to FREMAX.
B~E: Increase the frequency to 2 grade higher until to FREMAX.
F~G: Increase the frequency to 1 grade higher until to FREMAX.
H: Keep the current frequency.
I: Decrease the frequency to the 1 grade lower until to F1.
J: Run at F1 for 1h.(if T1-Ts-
∆
T >6
℃
, the compressor will stop)
Содержание 9ASI-A-1209
Страница 1: ...LUNA INVERTER SERIES Service Manual 2012 9ASI A 1209...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MS9AU 09HRDN1 QRC4W MS9AU 12HRDN1 QRC4W MS9AU 18HRDN1 QRC4W...
Страница 13: ...13 MS9A 24HRDN1 QRC4W...
Страница 14: ...14 5 2 Outdoor Unit MOB 09HFN1 QRC4W MOB 12HFN1 QRC4W MOC 18HFN1 QRC4W...
Страница 15: ...15 MOF 24HFN1 QRC4W...
Страница 26: ...26 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 31: ...31 continuous 4 seconds and this situation happens 3 times the display area will show EC and AC will turn off...
Страница 48: ...48 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution E0...
Страница 49: ...49 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...
Страница 51: ...51 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 53: ...53 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...