If T4
>
5
℃
or the compressor starts running, the preheating function will stop.
8.3.8 Zero crossing detection error protection(except MS9A-24HRDN1-QRC4W)
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display
the failure. The correct zero crossing signal time interval should be between 6-13ms.
8.3.9 Sensor protection at open circuit and breaking disconnection.
When there’s one temperature sensor in malfunction, the air conditioner will display error code and will
not stop immediately, to avoid the case that the air conditioner is in urgent need.
Fault temp.
sensor
Operation in cooling, drying and
fan only mode
Operation in heating mode
T1
Run supposed T1=26
℃
high fan
speed
Run supposed T1=26
℃
high fan
speed
T2
Refer to table 1
Refer to table 2
T3
Run with compressor frequency
not higher than F14
3 minutes’ defrosting every 40
minutes when T4<7
℃
; 2 minutes’
defrosting every 90 minutes when
T4
≥
7
℃
.
T4
Run supposed T4=50
℃
Run
supposed
T4=15
℃
TP
Run supposed T4=50
℃
Run
supposed
T4=15
℃
T1
25
23
F12
F4(30 minutes on+3
minutes off)
table 1
T1
20
18
F4
F12(Indoor fan 1 minute
off, 1 minute M- ane then
the setting fan speed.)
table 2
8.4.10 Refrigerant leakage detection
This function is only active in cooling mode. It can better prevent the compressor being damaged
by refrigerant leakage or compressor overload.
Open condition:
Define the evaporator coil temp.T2 of the compressor just starts running as Tcool.
In the beginning 5 minutes after the compressor starts up, if T2
<
Tcool
-
2
℃
does not keep
Содержание 9ASI-A-1209
Страница 1: ...LUNA INVERTER SERIES Service Manual 2012 9ASI A 1209...
Страница 12: ...12 5 Wiring Diagram 5 1 Indoor Unit MS9AU 09HRDN1 QRC4W MS9AU 12HRDN1 QRC4W MS9AU 18HRDN1 QRC4W...
Страница 13: ...13 MS9A 24HRDN1 QRC4W...
Страница 14: ...14 5 2 Outdoor Unit MOB 09HFN1 QRC4W MOB 12HFN1 QRC4W MOC 18HFN1 QRC4W...
Страница 15: ...15 MOF 24HFN1 QRC4W...
Страница 26: ...26 Use torque wrench to tighten the service port cap to a torque of 18N m Be sure to check for gas leakage...
Страница 31: ...31 continuous 4 seconds and this situation happens 3 times the display area will show EC and AC will turn off...
Страница 48: ...48 9 2 Diagnosis and Solution 9 2 1 EEPROM parameter error diagnosis and solution E0...
Страница 49: ...49 9 2 2 Indoor unit and outdoor unit communication protection error diagnosis and solution E1...
Страница 51: ...51 9 2 5 Open circuit or short circuit of temperature sensor diagnosis and solution E4 E5 F1 F2 F3...
Страница 53: ...53 9 2 7 Outdoor fan speed has been out of control diagnosis and solution F5...