background image

Part 3 Maintenance

CONSUMER INSTRUCTIONS

?

Keep the area around the burner clear and free of combustible material,  gasoline or other

flammable liquids or vapors. Do not obstruct burner air openings or ventilation grills for
combustion air.

?

The motor features permanently lubricated ball bearings and requires no maintenance.

WARNING: If any flame is observed when the burner is on standby, or if the

ignition spark or valve operator is heard to come on before the motor reaches
operating speed, immediately turn off the manual gas control and burner power. A
dangerous condition has developed and must be corrected. CONTACT A QUALIFIED
SERVICE TECHNICIAN FOR CLEANING, READJUSTMENT OR REPAIR.

?

Check that the pilot ignition spark does not come on before the motor reaches operating

speed. If it does, the air switch is defective and must be replaced. (See Section X, Motor /
Blower Interlock). 

LIGHTING INSTRUCTIONS

1.

SET OPERATING CONTROL TO 

OFF 

OR THERMOSTAT BELOW ROOM 

TEMPERATURE.

2.

TURN MANUAL GAS COCK 

ON.

3.

TURN BURNER POWER 

ON

.

4.

SET OPERATING CONTROL TO 

ON

OR THERMOSTAT TO CALL FOR 

HEAT.

5.

IF THE PILOT FLAME IS NOT PROVEN WITHIN 15 SECONDS, AFTER THE
PRE-PURGE, THE IGNITION CONTROL MODULE WILL SHUT OFF THE 
AUTOMATIC SAFETY SHUT-OFF VALVES AND LOCK OUT. IF THE PROOF
OF FLAME IS LOST DURING BURNER RUN AND THE PILOT IS NOT RE-
ESTABLISHED WITHIN15 SECONDS AFTER THE PRE-PURGE, THE 
PRIMARY  SAFETY CONTROL WILL SHUT OFF THE AUTOMATIC SAFETY
SHUT-OFF VALVES AND LOCKOUT. TO RESET FOR RESTART, DE-
ENERGIZE THE CONTROL BY SETTING THE OPERATING CONTROL TO 

OFF

OR THERMOSTAT BELOW ROOM TEMPERATURE FOR AT LEAST 60

SECONDS.

6.

REPEAT STEP 4 FOR RESTART.

TO SHUT OFF

1.

TURN MANUAL GAS COCK 

OFF.

2.

TURN BURNER POWER 

OFF.

SHOULD OVERHEATING OF THE APPLIANCE OCCUR

1.

Shut off the manual gas control to the appliance.

2.

Do not 

shut off the electrical supply power to the blower.

14

Part 3

Maintenance

Lighting Instructions

Содержание economite RE4400B

Страница 1: ...850BA RE4700BA RE4400B RE4400BA Gas Burners BURNER MODEL BILL OF MAT L NUMBER SERIAL CODE WIRING DIAGRAM FOR SERVICE CONTACT Name Address Phone Date of Installation Do not store or use gasoline or oth...

Страница 2: ...Listed 6 See Section XII of Operational Sequence CAUTION The ECONOMITE Models RE4850BA RE4700BA RE4400B and RE4400BA Burners are not intended for outdoor installation and must be protected from excess...

Страница 3: ...et at least 1 short of the inside surface because high combustion chamber temperatures will cause premature pilot electrode burner tube and sleeve deterioration WARNING BURNER MUST BE MOUNTED IN ORIEN...

Страница 4: ...between the hood or regulator and the combustion air supply see Figures 3 and 4 In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than th...

Страница 5: ...ir furnace fans or boiler pumps to a combination limit control and switch Set the thermostat heat anticipator for the total current draw handled by the thermostat The current draw of the ECONOMITE 24V...

Страница 6: ...in any position the main regulator if equipped should be mounted upright and in a horizontal run of pipe CAUTION Because it is difficult to accurately control pressure during supply pipe leak testing...

Страница 7: ...7 Part 1 Installation Continued Part 1 Installation RE4850BA UL Valve Train Assembly 24VAC Figure 5 Piping Diagram Continued...

Страница 8: ...low CAUTION Cover plates guards and enclosures must be maintained in place at all times except during maintenance and service 1 Check the burner piping and valves for gas leaks by applying a weak liqu...

Страница 9: ...TE AND BASED ON 0 OVERFIRE PRESSURE AT SEA LEVEL 2 4 2 5 2 7 2 8 2 4 3 9 3 3 2 7 2 2 3 3 0 15 0 688 0 563 0 500 0 422 0 422 0 358 0 358 0 358 0 358 0 290 0 688 3 5 3 1 2 7 2 8 2 4 2 8 3 15 2 4 2 6 4 3...

Страница 10: ...associated controls 11 Perform the following final adjustments for combustion and flue gas temperature Take the flue gas samples and temperature immediately ahead of the draft control A The flue gas t...

Страница 11: ...trols If trouble occurs contact the installing contractor service agency or fuel supplier See front cover DANGER Be sure that the main and pilot manual Shut Off Valves are closed and the burner power...

Страница 12: ...e will arc to the inside of the 3 8 Tee pilot See Figure 7A and 7B The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition Control Module will detect a proper flame...

Страница 13: ...er to the literature provided with the power burner For startup information see section VIII For operation characteristics maintenance and service procedures refer to manufacturer s literature provide...

Страница 14: ...ction X Motor Blower Interlock LIGHTING INSTRUCTIONS 1 SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM TEMPERATURE 2 TURN MANUAL GAS COCK ON 3 TURN BURNER POWER ON 4 SET OPERATING CONTROL TO ON...

Страница 15: ...nd the pilot is not re established after the pre purge the Ignition Control Module will lock out To reset the control for restart de energize the Ignition Control Module by setting the operating contr...

Страница 16: ...16 Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 1201 tel 773 604 8700 fax 773 604 4070 web www midco intl com email sales midco intl com 8471 24 Printed in USA...

Отзывы: