background image

Part 2 Service 

The pilot is of the premix, blast type. The full force of blower air is brought into the mixing tube
where the proper amount of gas is added through the pilot orifice. This mixture is discharged
through the pilot. The mixture provides the flame that contacts the flame sensing rod and also
ignites the main gas.

CAUTION: Do not indiscriminately increase pilot orifice size. Pilot troubles are rarely

cured in this manner and new troubles may be created.

?

Under normal conditions, with a slight negative pressure in the combustion chamber, pilot

operating pressures should be set as indicated in Table 4.

?

Some conditions which may require a change from the normal setting include: extremely long

tubing connections between the regulator and pilot solenoid, high negative or positive
combustion chamber pressure, actual air shutter setting and altitude extremes.

?

Do not subject the pilot to an inlet pressure over 14.0"W.C. See Section VI PIPING for high

pressure gas. 

?

To adjust outlet pressure, remove the seal cap for access to the adjusting screw. Turning the

screw clockwise will increase outlet pressure, counter clockwise will decrease outlet pressure.

?

The spark rod for a natural gas burner is welded to a round 1/2” perforated retention plate.

(The spark rod for a propane gas burner is welded to a round 1/2” 

solid

retention plate.)       

CAUTION: Make sure that the natural gas burner has the correct spark rod

retention plate before operating the burner. See “Replacement Parts Lists” if replacement
is needed. 

The 1/2” retention plate is centered in the 3/8” Tee pilot and is positioned so the high

tension voltage will arc to the inside of the 3/8” Tee pilot.(

See Figure 7A and 7B

).

?

The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition

Control Module will detect a proper flame.

?

Both the spark and flame rods are current carrying conductors and, along with their

connecting wires, must be kept free of contact with conductive metal parts of the burner. Rod
insulators and wire insulators should be clean, dry and free of cracks.

?

Both the spark and flame rods are made from heat resistant alloys and can be expected to

have a long service life. They should be routinely inspected, however, for corrosion or loss of
metal.

?

The pilot air tubing must be kept free of kinks or inside obstructions and must be positioned

per Figures 7A & 7B, otherwise air flow could be reduced and adversely affect the pilot flame.

CAUTION: BEFORE SERVICING, mark with a scribe line or measure opening of

air controlling shutter, so that it can be reset to its original position following servicing.

?

Cleaning of the blower wheel is usually the only service required. Need for cleaning is

indicated if the character of the flame indicates a deficiency of air. Motor cooling air vents (if
present) should also be cleaned at this time.

?

The  motor and wheel are removed as an assembly. Disconnect the motor wires from the

motor terminal strip. Disconnect the motor conduit from the motor and remove the mounting
bolts.

?

The burner is equipped with a diaphragm type air pressure switch so as to prevent the burner

from firing if the blower wheel is not running at its operating speed. When the motor is off there
is no air pressure present to activate the pressure switch and in turn there is no power flow to
the Ignition Control Module.

Figure 6: 

Motor / Blower Assembly

Part 2

Service Continued 

X

Motor Blower

Interlock

12 

IX

Pilot

Содержание economite RE4400B

Страница 1: ...850BA RE4700BA RE4400B RE4400BA Gas Burners BURNER MODEL BILL OF MAT L NUMBER SERIAL CODE WIRING DIAGRAM FOR SERVICE CONTACT Name Address Phone Date of Installation Do not store or use gasoline or oth...

Страница 2: ...Listed 6 See Section XII of Operational Sequence CAUTION The ECONOMITE Models RE4850BA RE4700BA RE4400B and RE4400BA Burners are not intended for outdoor installation and must be protected from excess...

Страница 3: ...et at least 1 short of the inside surface because high combustion chamber temperatures will cause premature pilot electrode burner tube and sleeve deterioration WARNING BURNER MUST BE MOUNTED IN ORIEN...

Страница 4: ...between the hood or regulator and the combustion air supply see Figures 3 and 4 In no case shall the relief opening of the draft hood or barometric draft regulator be located at a point lower than th...

Страница 5: ...ir furnace fans or boiler pumps to a combination limit control and switch Set the thermostat heat anticipator for the total current draw handled by the thermostat The current draw of the ECONOMITE 24V...

Страница 6: ...in any position the main regulator if equipped should be mounted upright and in a horizontal run of pipe CAUTION Because it is difficult to accurately control pressure during supply pipe leak testing...

Страница 7: ...7 Part 1 Installation Continued Part 1 Installation RE4850BA UL Valve Train Assembly 24VAC Figure 5 Piping Diagram Continued...

Страница 8: ...low CAUTION Cover plates guards and enclosures must be maintained in place at all times except during maintenance and service 1 Check the burner piping and valves for gas leaks by applying a weak liqu...

Страница 9: ...TE AND BASED ON 0 OVERFIRE PRESSURE AT SEA LEVEL 2 4 2 5 2 7 2 8 2 4 3 9 3 3 2 7 2 2 3 3 0 15 0 688 0 563 0 500 0 422 0 422 0 358 0 358 0 358 0 358 0 290 0 688 3 5 3 1 2 7 2 8 2 4 2 8 3 15 2 4 2 6 4 3...

Страница 10: ...associated controls 11 Perform the following final adjustments for combustion and flue gas temperature Take the flue gas samples and temperature immediately ahead of the draft control A The flue gas t...

Страница 11: ...trols If trouble occurs contact the installing contractor service agency or fuel supplier See front cover DANGER Be sure that the main and pilot manual Shut Off Valves are closed and the burner power...

Страница 12: ...e will arc to the inside of the 3 8 Tee pilot See Figure 7A and 7B The flame sensing rod must be positioned as shown in Figures 7A and 7B so that the Ignition Control Module will detect a proper flame...

Страница 13: ...er to the literature provided with the power burner For startup information see section VIII For operation characteristics maintenance and service procedures refer to manufacturer s literature provide...

Страница 14: ...ction X Motor Blower Interlock LIGHTING INSTRUCTIONS 1 SET OPERATING CONTROL TO OFF OR THERMOSTAT BELOW ROOM TEMPERATURE 2 TURN MANUAL GAS COCK ON 3 TURN BURNER POWER ON 4 SET OPERATING CONTROL TO ON...

Страница 15: ...nd the pilot is not re established after the pre purge the Ignition Control Module will lock out To reset the control for restart de energize the Ignition Control Module by setting the operating contr...

Страница 16: ...16 Midco International Inc 4140 West Victoria Street Chicago Illinois 60646 1201 tel 773 604 8700 fax 773 604 4070 web www midco intl com email sales midco intl com 8471 24 Printed in USA...

Отзывы: