background image

A.

Manual Gas Cock Knob on Combination Valve not in 

ON

position.

B.

Check for 24V* between blower interlock switch terminal 

NC

and 

GND

;

1. If no voltage, motor interlock switch or centrifugal actuator is defective. (See Section 

Blower Assembly

).

2. If voltage is present, valve operator is defective; entire valve must be replaced.

A.

Low manifold gas pressure.

B.

Main gas spud orifice too small.

C.

Primary air adjustment open too far.

A.

High manifold gas pressure.

B.

Main gas spud orifice too large.

C.

Primary air adjustment closed too far.

D.

Dirty Blower Wheel

A.

Electric Valve Operator(s) of Combination Valve is defective and entire valve must be

replaced.

* Normal low voltage:

Motor running-24V minimum
Combination Valve energized-21V minimum.

** 

IMPORTANT

: If changes are made in the main spud orifice size manifold gas pressure or pri-

mary air adjustment, change the installation data tag accordingly.

12

IV. Motor Runs

Continuously, Pilot is On,

But No Main Flame

V. Short Flame**

VI. Long, Hazy Flame**

VII. Gas Fails to Shut Off

Trouble Chart Contintued

Midco International Inc.

4140 West Victoria Street - Chicago, Illinois 60646  

tel  773.604.8700    fax  773.604.4070    web   www.midco-intl.com   email  [email protected]

201

8470 75

Printed in USA

Содержание Economite 400B-02 Series

Страница 1: ...tion equipment and remove such hazards Affix this manual adjacent to the conversion burner CODE COMPLIANCE IS THE SOLE RESPONSIBILITY OF THE INSTALLER WARNING If the information in these instructions...

Страница 2: ...g provision must be made for an outside air supply near the gas utilization equipment area Install permanently open grilles sized at not less than one square inch free area per 4 000 BTU of burner inp...

Страница 3: ...NG Burner cabinet must be mounted in orientation shown in figures 1 and 2 Any other mountings may cause a dangerous condition and will void burner warranty and agency approvals Non standard arrangemen...

Страница 4: ...rsely affect burner operation or if flue gas spillage might introduce a hazard If such a device is used it shall be of the listed type and installed and adjusted by a qual ified service technician in...

Страница 5: ...of 5 0 W C pressure 11 0 W C PROPANE to the inlet of the Combination Valve when the burner and all other gas utilization equipment are on Note If there is more than 1 0 W C differential in the inlet p...

Страница 6: ...and install the spud with the correct orifice size stamped with inch diameter from the SPUD KIT bag If the required firing rate is at the minimum of a capacity range select the next lower range spud...

Страница 7: ...ustment 8 Turn operating control to ON or set thermostat above room temperature Main flame should come on when the motor reaches operating speed If not refer to Trouble Chart To make a preliminary set...

Страница 8: ...C for NATUR AL gas 8 0 W C for PROPANE 1 Standby gas pressure inches W C 2 The efficiency of the thermocouple and the pilotstat safety control can be determined by timing the safety shut off With the...

Страница 9: ...te and electrical interlock switch so as to prevent the burner from firing if the Blower Wheel is not running at its operat ing speed When the motor is off the actuator spring forces the disk against...

Страница 10: ...u 5 for the method of isolating the problem If on a call for heat the main burner fails to operate even though the pilot is burning and the motor is running failure of the electric valve operator s ma...

Страница 11: ...t flame gas pressure See Section IX Venturi Casting and Pilot E Clogged pilot orifice s See Section IX Venturi Casting and Pilot F Defective ignitor ignitor wires spark rod or improper spark gap See F...

Страница 12: ...ent closed too far D Dirty Blower Wheel A Electric Valve Operator s of Combination Valve is defective and entire valve must be replaced Normal low voltage Motor running 24V minimum Combination Valve e...

Отзывы: