MICROWELL HP 1700 SPLIT Скачать руководство пользователя страница 4

I n s t a l l a t i o n   a n d   u s e r   m a n u a l  

H P 9 0 0 / 1 2 0 0   S P L I T     P R E M I U M  

V e r s i o n :   0 1 / 2 0 1 7  

P a g e  

4

/ 3 6

 

 

 

         

HEAT P

U

M

P

  

MI

C

R

O

W

E

L

HP

 

 

1.

 

INTRODUCTION  

In your hands you hold probably the most advanced and the most efficient heat pump currently 
available on the market. This heat pump provides warm water in your pool at lowest possible cost. 
The heat pump is manufactured in tightest accordance with related strict standards and norms, in 
order to provide high quality operation and long-term reliability.  
This Installation and user manual contains all the necessary information about the installation, 
operation and maintenance of the heat pump. Please read this Installation and user manual carefully 

before you start to use this product. The manufacturer is not responsible for any personal or property 
damage due to the improper installation, use or maintenance that is not in accordance with this User 

Manual.

 

This Installation and user manual is an inseparable part of this product; therefore it must be kept in 
good condition and must accompany the heat pump. 

1.1

 

Product description 

The heat pump is designed exclusively for swimming pool water heating or cooling and maintaining its 

temperature on the requested level. Other appropriate application is water temperature conditioning 
for fish tanks, wine ciders or horse cooling facilities. These applications should be discussed with local 

installer or distributor. Any other form of application is considered inappropriate. 

The heat pump achieves the highest efficiency at 15÷35°C air temperature. At ambient air 
temperatures lower than -5°C the efficiency of the device decreases and at the temperatures higher 

than +40°C the heat pump can get overheated which may result in its malfunction, damage or failure. 
Do not use the product out of the designated operational air temperature range which is stated in 

section 

3.1 Technical data.   

This heat pump is designed for swimming pools with up to 70 m

3

 - HP 1700 of pool water volume. For 

proper operations there must be water flow through the exchanger of the heat pump (within water 

filtration circuit) in the range of 686 m

3

/h.  

 

The heat pump enables heat gain from the external air surrounding the swimming pool through the 
compression – expansion cycles of the heat-carrying liquid. The air is driven by a fan through the 

evaporator where it will deliver its heat to the heat-carrying liquid (the air is being cooled at the same 
time). The heat-carrying liquid is then delivered to the spirals of the exchanger by the compressor 
which pressurises it and thus heats it up. In these spirals, the heat-carrying liquid delivers its heat to 

the swimming pool water.  From the exchanger there is a cooled liquid flowing to the expansion valve 
or capillary where its pressure decreases and it gets cooled down rapidly at the same time.  This 

cooled liquid flows to the evaporator again where it gets heated by the flowing air. The whole process 
runs fully automatically and is monitored by the pressure and temperature sensors. The same 
principle is applied when heat pump operates in cooling mode.  

Using simple language, a heat pump is able to extract the heat/cold that is present in ambient 
environment and leveraged pass it into the pool water. When heating, higher the ambient air 

temperature is, more free energy can the heat pump extract and thus reach higher efficiency. At 
favourable conditions you pay around 15% of heat, i.e. 85% of heat is free. Please review below 

drawing of different ambient air conditions with subsequent efficiencies.  

The heat pump efficiency grows by the increasing surrounding air temperature. 

It takes some days to achieve the requested swimming pool water temperature. This time period 

depends on heat loss and heat gain balance of your pool.  

Example factors of heat losses: poor pool construction, used materials, usage of cover, air – water 

temperature relationship, fresh water refilling, filtration, etc. 

Example factors of heat gains: intensity of sun, winds, orientation of pool, air – water temperature 
relationship, etc. 
In order to avoid heat loss when the swimming pool is not being used, it is highly advised to use 
pool’s cover. 

Содержание HP 1700 SPLIT

Страница 1: ...Version 01 2017 HEAT PUMP for swimming pool water heating cooling HP 1700 SPLIT Installation and user manual ...

Страница 2: ...on and usage of this heat pump which are valid in addition to this User manual Contents 1 INTRODUCTION 4 1 1 Product description 4 1 2 Package checking 5 1 3 Waste disposal information 5 2 SAFETY MEASURES 6 2 1 Electrical safety 6 2 2 Usage precautions 6 2 3 Handling precautions 7 3 TECHNICAL SPECIFICATION 8 3 1 Technical data 8 3 2 Swimming pool water parameters 9 3 3 Heat pump dimensions 9 3 4 D...

Страница 3: ...10 Circulation pump connection 24 5 REGULATION 25 6 ACCESSORIES 30 6 1 Winter module 30 6 2 Heat exchanger frost protection 30 6 3 Condensate tray defrost 30 6 4 Protection cover 30 7 HINTS AND TIPS 31 7 1 Water condensation 31 7 2 Winterizing 31 7 3 Heat pump season start 32 7 4 Failure reports 33 7 5 Troubleshooting save time and money 34 8 MAINTANANCE WARRANTY 35 8 1 Maintanance 35 8 2 Warranty...

Страница 4: ... m3 HP 1700 of pool water volume For proper operations there must be water flow through the exchanger of the heat pump within water filtration circuit in the range of 686 m3 h The heat pump enables heat gain from the external air surrounding the swimming pool through the compression expansion cycles of the heat carrying liquid The air is driven by a fan through the evaporator where it will deliver...

Страница 5: ...g 1 The heat pump condensing unit the heat exchanger indoor unit Please see section 3 4 Description of the basic parts to see how the heat pump looks like 2 This Installation and user manual 3 Four rubber silent blocks 1 3 Waste disposal information When using this heat pump in the European countries the following information must be followed DISPOSAL Do not dispose this product as unsorted munici...

Страница 6: ...y cause electrical or frequency disturbance such as welding machines motors or rotors WIFI WLAN routers or repeaters v It is forbidden to alter electrical installation of the device It is also forbidden to alter any other part or functionality of the device 2 2 Usage precautions Do not cover or block the intake or exhaust opening ventilator and evaporator covers It is forbidden to block or cover t...

Страница 7: ...hanger v Do not apply or use water of higher temperature than 40 C in water heat exchanger Water temperature above 45 C irreversibly damages the water heat exchanger v Manufacturer does not bear any responsibility concerning damages caused by inappropriate heat pump performance and or model selection installation or application Heat pump is considered undersized in the case it works usually and in...

Страница 8: ...m 20 Max length of refrigerant connection vertically m 15 Max recommended water pipe length m 30 Max operational water pressure 0 15MPa 1 5bar Net unit dimensions w h d condensing unit 1125 707 453 Gross unit dimensions w h d condensing unit 1150 843 480 Net Gross weight kg condensing unit 100 90 Net unit dimensions w h d water unit without box 650 370 400 Gross unit dimensions w h d water unit wi...

Страница 9: ...lowing pH value ranging from 6 8 to 7 9 total chlorine amount not exceeding 3 mg l salt content 6 wt wt Should you have different values of pH chlorine or salt please try to apply appropriate agents or contact your swimming pool builder to resolve the situation Above mentioned values are recommended for pools in general It is also advised to keep the water hardness on the lower limit of the optima...

Страница 10: ...igerant connection OUT condensing unit IN liquid heating mode 5 Refrigerant connection IN condensing unit OUT gas heating mode 6 Flow switch 7 Temperature sensor water in T2 8 Temperature sensor water out T5 9 Electro box 10 Heat exchanger box in cooling mode applies in reversed order Please note that above pictures may differ from your actual heat pump make 3 5 Security and control systems In ord...

Страница 11: ...tection will get activated so the unit cannot start the operation earlier than the pressures in the refrigerant circuit of the heat pump get balanced Interruption of the power supply during the pause time does not influence the time interval Antifreeze protection If an ambient air temperature is low e g below 7 C it is normal to have ice creations on the evaporator of your heat pump This is freezi...

Страница 12: ... 500W Sensors T4 Picture Power supply connection of the condensing unit auxliary circulation pump and 1 4 sensors of the water unit T3 T1 1 2 3 4 1 2 3 4 T2 T5 Picture Four pin terminal connection of water unit 1 4 sensor connection with condensing unit Legend FM Fan motor CM Compressor OUT 1 Compressor L OUT 2 Compressor N OUT 3 output of 4 way valve L OUT 4 output of 4 way valve OUT 5 fan L OUT ...

Страница 13: ...y circulation pump 1 4 sensors of the water unit and A B C connector of the control display T3 T1 1 2 3 4 1 2 3 4 T2 T5 Picture Four pin terminal connection of water unit 1 4 sensor connection with condensing unit and three pin terminal connection of the control display Legend FM Fan motor CM Compressor OUT 1 Compressor L OUT 2 Compressor N OUT 3 output of 4 way valve L OUT 4 output of 4 way valve...

Страница 14: ...tc Also do not place the air outlet against the dominant winds e The distance between the water unit and the condensing unit can be max 20m HP900 and max 30m HP1200 horizontally and max 15m vertically condensing unit above water unit Split heat pump was designed to provide with water temperature control of a pool and in the meantime provide no visual and or acoustic disturbance to a pool user It i...

Страница 15: ...s equipped with 2 threads enabling the connection of input and output fitting d50 For connection with the filtration circuit use the d50 PVC pipe or 50 38mm adapters 6 4 Please refer to section 3 4 Description of the basic parts in order to make sure which thread is water input and which water output It is advised to apply lubricating oil on threads before tightening the connection Please consider...

Страница 16: ...hese components are not part of heat pump package or delivery Important For proper operations there must be a water flow through the heat pump exchanger in range of 4 6 m3 hour In the case of water flow exceeding 10m3 h the heat pump will turn itself off and an error notice PL will pop up Repeated error notice or repeated exposure of the heat pump to the water flow higher than 8m3 h will cause irr...

Страница 17: ...rcuit of the swimming pool Note The manufacturer supplies the heat pump only The other parts and components shown in the picture are not included in heat pump package Swimming pool Skimmer Chlorine dozing machine Reversible nozzle Bottom outlet Filtration pump By pass valves Technical chamber min 3500mm Heat pump AIR unit min 500mm Wall Condensate outlet Heat pump WATER unit 4 way valve Filtration...

Страница 18: ...e in compliance with local valid electro technical requirements d The electro connection of the heat pump must be simple clear and comprehensible It is highly advised to have the connection performed in a way that would allow a third party electrician to understand the connection at no time Unnecessary cross connections are not appropriate e It is important to carefully check and measure the elect...

Страница 19: ... 40g of R410A per 1 meter for exceeding connecting distances between condensing and water unit Piping length and elevation Heat pump model Pipe size Factory pre charged connection distance Max vertical distance B Max distance A Additional refrigerant Gas diameter Liquid diameter inch mm inch mm HP1700 5 8 15 9 3 8 9 5 10m 15m 20m 40g m Refrigerant piping condensing unit 1 Align the center of the p...

Страница 20: ...cable from down upwards Fix the tapped piping with cable binder or equivalent onto the exterior wall It is important to make a trap to prevent water from entering into the electro installation of the condensing unit On refrigerant side it is important to form a syphon 4 6 Flaring work It is important to perform the flaring work correctly This will have positive effect towards long term reliability...

Страница 21: ...st can be performed with usual methods using manifold valve and or soap water Air purging can be performed by most commonly applied methods with vacuum pump This Installation and user manual elaborates vacuum pump method When the condensing unit is pre charged with refrigerant we do not recommend a pressure test using nitrogen Air purging with vacuum pump 1 Preparation a Check that each tube both ...

Страница 22: ... 2 Turn the valve stem of gas side valve counter clockwise to fully open the valve 3 Remove the charging hoses 4 Put service valve caps back at both gas and liquid side service valves and fasten them tight This completes air purging with a vacuum pump and refrigerant works Please note that above flaring and refrigerant work must be performed correctly with utmost care Any non compliance with above...

Страница 23: ...der achieve requested water temperature Such installation is particularly advised on public venues where continuity of operation service is paramount Installation of the multiple heat pumps follows the same procedure as single heat pump described above It is only necessary to install the heat pumps in parallel connection Serial connection would significantly decrease the heating cooling capacity a...

Страница 24: ... In order to save energy it is possible to install the heat pump on a separate water circuit with small circulation pump This is appropriate in the case the power consumption of circulation pump for filtration is considered high or simply if the whole filtration circuit running is not desired when heating cooling is required Normally swimming pool circulation pumps with water flow performance betw...

Страница 25: ...H P 9 0 0 1 2 0 0 S P L I T P R E M I U M I n s t a l l a t i o n a n d u s e r m a n u a l P a g e 2 5 3 6 V e r s i o n 0 1 2 0 1 7 H E A T P U M P M I C R O W E L L H P 5 REGULATION ...

Страница 26: ...I n s t a l l a t i o n a n d u s e r m a n u a l H P 9 0 0 1 2 0 0 S P L I T P R E M I U M V e r s i o n 0 1 2 0 1 7 P a g e 2 6 3 6 H E A T P U M P M I C R O W E L L H P ...

Страница 27: ...H P 9 0 0 1 2 0 0 S P L I T P R E M I U M I n s t a l l a t i o n a n d u s e r m a n u a l P a g e 2 7 3 6 V e r s i o n 0 1 2 0 1 7 H E A T P U M P M I C R O W E L L H P ...

Страница 28: ...I n s t a l l a t i o n a n d u s e r m a n u a l H P 9 0 0 1 2 0 0 S P L I T P R E M I U M V e r s i o n 0 1 2 0 1 7 P a g e 2 8 3 6 H E A T P U M P M I C R O W E L L H P ...

Страница 29: ... d u s e r m a n u a l P a g e 2 9 3 6 V e r s i o n 0 1 2 0 1 7 H E A T P U M P M I C R O W E L L H P Note The manufacturing settings may differ from the data in the chart Notice Manufacturer reserves the right to change parametres or controller functions without notice ...

Страница 30: ...matically regulated It turns itself on if the ambient air temperature decreases below 2 C Power consumption is 64W In the case the heat pump will not be used in winter time along with winterizing it is suggested to turn the heat pump s circuit breaker off in order to avoid unecessary energy consumption Heat exchanger frost protection is on demand and is not supplied with each heat pump by standard...

Страница 31: ... found in the outflowing water if chlorine or salt are used If there is no chlorine or salt then it is a condensate 7 2 Winterizing Split heat pump has been designed to have the water unit water heat exchanger installed in non freezing location Should your application have risk of freezing up please read through this section of this Installation and user manual carefully Your heat pump continuousl...

Страница 32: ...you need to prepare your heat pump for new season In general please refer to this Installation and user Manual Heat pump must be connected to the mains water circuit it must comply with positioning requirements During the initial start of the heat pump it is possible to have PL error This signals low high or none water flow and results in heat pump turning off If your water piping is intact circul...

Страница 33: ...P M I C R O W E L L H P 7 4 Failure reports Please find below table containing list of failure reports with their explanation and suggested solution In order to physically locate the sensor please refer to section 3 6 Block wiring diagram of the PCB board Display on condensing unit or 3 7 Block wiring diagram of the PCB board Display on water unit ...

Страница 34: ...e for figure 17 Section 5 6 Parameters check The figure must be sub zero If it s below zero your heat pump should initiate defrosting shortly If it s above zero then it is likely displaced Sensor must be placed correctly P1 failure report is signalled by digital control panel Your heat pump will automatically defreeze itself in 45min cycles You can force your heat pump to immediate defrosting Sect...

Страница 35: ...current and voltage DANGER Danger of electric shock WARNING The device is pressurized with refrigerant R410A The pressures can reach as high as 30bar a Clean the swimming pool and the filtration on regular basis to prevent the device from damage caused by dirty or clocked filter b Check the power supply on regular basis c Should the device appear to operate in unusual way turn it off immediately a...

Страница 36: ...in order to avoid its spread k Do not clean inner parts of water heat exchanger with hot water The heat exchanger will get damaged if water temperature inside it rises above 60 C l All the above measures must be performed by a trained technician m The maintenance of the refrigeration or electrical system must be performed by authorized technicians only 8 2 Warranty Your heat pump is covered by war...

Отзывы: