Press this button on the main interface to enter the clock setting. The four digital fields flash
at the same time. The clock indicator flashes. Press this button again to enter the hour
setting of current time. The digital tube flashes in minutes. Press the UP or DOWN button for
numerical adjustment. Press this button or the ON/OFF button to exit after completion.
When setting the timing time, press this button to cancel the timing and return to the main
interface. The corresponding timing indicator will be off.
4.3
System parameter
A: Check the current temperature
B: Check system parameters.
System parameter:
Code
Meaning
Range
Default
Remarks
0
Memory Function
0
(
N/A
)
/1
(
A
)
1
Adjustable
1
Daily Cycle Mark
0
(
N/A
)
/1
(
A
)
1
Adjustable
2
Return Difference X
2-10°C (35.6°F-50°F)
3
Adjustable
3
Return Difference Y
0-3°C (32°F -37.4°F)
0
Adjustable
4
Defrosting Cycle
30-90Min
40Min
Adjustable
5
Temp. to Enter Defrosting
-30°C-0°C (-22°F-32°F)
-1°C
(30.2°F)
Adjustable
6
Temp. to Exit Defrosting
2-30°C
(
35.6°F -86°F
)
15°C
(59°F)
Adjustable
7
Time to Exit Defrosting
1-12Min
8Min
Adjustable
8
Exhaust Protection
90-120°C (194°F -248°F)
110°C
(230°F)
Adjustable
9
Upper Setting Temp.
40-65°C (104°F -149°F)
40°C
(104°F)
Adjustable
10
Water Pump Mode
0
(
Special
)
/1
(
Common
)
1
Adjustable
11
Water Pump Stop Time
When Reaching the
Target Temp
3-20MIN
15
Adjustable