I n s t a l l a t i o n   a n d   u s e r   m a n u a l  

H P 1 0 0 0 / 1 4 0 0 / 1 7 0 0   G r e e n  

V e r s i o n :   0 1 / 2 0 2 1  

P a g e  

1 2

/ 4 0

 

 

 

    

   

  

H

E

AT

 PUM

P

 

 MIC

R

OWE

L

L HP 

 

3.5

 

Installation instructions

 

WARNING: Installation must be carried out by a qualified engineer.  

This section is provided for information purpose only and must be checked and adapted if 
necessary according to actual installation condition. 

a.

 

 

Pre‐Requirements 

Needed equipment for installation of heat pump: 

 

Suitable power supply cable for unit’s power. 

 

A by‐pass kit and an assembly of PVC tube, stripper, PVC adhesive and sandpaper. 

 

A set of wall plug and expansion screw. 

 

We recommend to use flexible PVC pipe in order to reduce transmission of vibration. 

 

Suitable fastening studs may be used to raise unit.  

 

b.

 

Location 

Please comply with the following rules about heat pump location choosing. 

1.

 

The unit’s location must be convenient for operation and maintenance in the future. 

2.

 

It must be installed and fixed on flat concrete floor. The floor is stable to support the 
weight of the unit. 

3.

 

A water drainage device must be provided close to the unit in order to protect the area 
where it is installed. 

4.

 

If necessary, mounting pads could be used to support the weight of unit. 

5.

 

Confirm the unit is under well‐ventilated condition; air outlet port is not facing to the 
windows of nearby buildings and the outlet air can not be returned. In addition, provide 
enough space around the unit for repair and maintenance. 

6.

 

The unit must not be installed in an area exposed to oil, flammable gases, corrosive 
products, sulphurous compounds or close to high frequency equipment. 

7.

 

To prevent mud splashes, do not install the unit near road or track. 

8.

 

To avoid noise to neighbours, please make sure the unit is installed in less noise 
sensitivity area or good sound isolation area. 

9.

 

Keep the unit as far as possible away from children. 

10.

 

Installation space 

 
Unit: mm 

 

Anything could not be placed within at least 1m in front of heat pump. 

Leave at least 500mm of empty space around the sides and rear of heat pump. 

Do not put any stuff on or in front of heat pump! 

Содержание HP 1000 GREEN

Страница 1: ...Version 01 2021 HEAT PUMP for swimming pool water heating cooling HP 1000 GREEN HP 1400 GREEN HP 1700 GREEN Installation and user manual ...

Страница 2: ... local regulations in your country regarding installation and usage of this heat pump which are valid in addition to this User manual Content 1 INTRODUCTION 3 1 1 Product description 3 1 2 Package checking 4 1 3 Waste disposal information 4 2 SAFETY MEASURES 5 2 1 Electrical safety 5 2 2 Usage precautions 5 2 3 Handling precautions 8 2 4 Transportation 8 3 TECHNICAL SPECIFICATION 9 3 1 Technical d...

Страница 3: ...re range which is stated in section 3 1 Technical data This heat pump is designed for swimming pools with up to 40 m3 HP 1000 and up to 60 m3 HP 1400 of pool water volume For proper operations there must be water flow through the exchanger of the heat pump within water filtration circuit in the range of 4 6 m3 h The heat pump enables heat gain from the external air surrounding the swimming pool th...

Страница 4: ...t accept the package if it shows signs of damage If the package appears intact please unpack the unit and check the content It should include the following 1 The heat pump condensing unit the heat exchanger indoor unit 2 This Installation and user manual 3 Four rubber silent blocks 1 3 Waste disposal information When using this heat pump in the European countries the following information must be ...

Страница 5: ...use electrical or frequency disturbance such as welding machines motors or rotors WIFI WLAN routers or repeaters It is forbidden to alter electrical installation of the device It is also forbidden to alter any other part or functionality of the device 2 2 Usage precautions Do not cover or block the intake or exhaust opening ventilator and evaporator covers It is forbidden to block or cover the int...

Страница 6: ...iency decreases Manufacturer does not bear any responsibility concenring damages caused by inappropriate heat pump selection installation or application Do not pressurize the water heat exchanger higher than 0 25MPa 2 5bar By pressure of 0 5MPa 5bar the water heat exchanger gets irreversibly damaged It is advised to install a security valve with pressure threshold at 0 25MPa 2 5Bar before the heat...

Страница 7: ...ir flow near inlet or outlet area otherwise the efficiency of the heater will be reduced or even stopped g Don t use or stock combustible gas or liquid such as thinners paint and fuel to avoid fire h In order to optimize the heating effect please install heat preservation insulation on pipes between swimming pool and the heater and please use a recommended cover on the swimming pool i Connecting p...

Страница 8: ...l freely onto the ground or any solid surface resulting in hard impact Please notify your reseller or distributor if you suspect that the unit was delivered damaged Unit may seem to work well at start but small damage can make the unit go out of order in short time In such case the unit must be inspected and approved for further use by your reseller Please notify your reseller or distributor if di...

Страница 9: ...Air side heat exchanger Hydrophilic fin exchanger Water side heat exchanger Titanium tube heat exchanger Water flow m h 4 5 3 7 1 Net dimension LxWxH mm 910x360x620 1000x385x665 Water pipe connection mm 50 Net weight kg 39 49 56 Noise level dB A 46 52 54 The manufacturer reserves the right to change the parameters without notice In the case Winter module condensate tray antifreeze or heat exchange...

Страница 10: ...value ranging from 6 8 to 7 9 total chlorine amount not exceeding 3 mg l salt content 6 wt wt Should you have different values of pH chlorine or salt please try to apply appropriate agents or contact your swimming pool builder to resolve the situation Above mentioned values are recommended for pools in general It is also advised to keep the water hardness on the lower limit of the optimal range i ...

Страница 11: ...2 19 Titanium heat exchanger 2 Electrical box cover 11 Front plate 20 Filter component 3 Electrical component 12 Fan motor cover 21 Four way valve 4 Left handle 13 Fixed plate 3 22 Water flow switch 5 Left plate 14 Compressor 23 High efficiency finned heat exchanger 6 Motor support 15 Right plate 24 Back net 7 Fan motor 16 Right handle 25 Ambient probe position 8 Fan 17 External WiFi 9 Fixed plate...

Страница 12: ...be installed and fixed on flat concrete floor The floor is stable to support the weight of the unit 3 A water drainage device must be provided close to the unit in order to protect the area where it is installed 4 If necessary mounting pads could be used to support the weight of unit 5 Confirm the unit is under well ventilated condition air outlet port is not facing to the windows of nearby buildi...

Страница 13: ... comply with the following instruction to connect heat pump Connect to appropriate power supply the voltage should comply with the rated voltage of the products Earth the machine well Wiring must be handled by a professional technician according to the circuit diagram Set leakage protector according to the local code for wiring leakage operating current 30mA The layout of power cable and signal ca...

Страница 14: ...and cable specification Model Power Supply Wires Electricity Supply Cable Diameter Specification HP1000 GREEN 220 240V 50Hz 3 2 5mm2 AWG 14 HP1400 GREEN 3 2 5mm2 AWG 14 HP1700 GREEN 3 4 0mm2 AWG 12 Above data is subject to modification without notice Note The above data is adapted to power cord 10m If power cord is 10m wire diameter must be increased The signal cable can be extended to 50m maximum...

Страница 15: ...is button briefly to switch modes heating mode refrigeration mode Long press this button 5S to enter the system parameter query The system parameter can be inquired by using the UP or DOWN button In the parameter query state press this button briefly to enter parameter settings The system parameter can be set by using the UP or DOWN button UP button When the unit is on press this button in the mai...

Страница 16: ...on indicator flashes Press this button again to enter the hour setting of Timer ON setting When the hour part of digital tube flashes press the UP or DOWN button for numerical adjustment Press this button again to enter the minute setting When the minute part of digital tube flashes press the UP or DOWN button for numerical adjustment Press this button or the ON OFF button to exit after completion...

Страница 17: ... corresponding timing indicator will be off 4 3 System parameter A Check the current temperature B Check system parameters System parameter Code Meaning Range Default Remarks 0 Memory Function 0 N A 1 A 1 Adjustable 1 Daily Cycle Mark 0 N A 1 A 1 Adjustable 2 Return Difference X 2 10 C 35 6 F 50 F 3 Adjustable 3 Return Difference Y 0 3 C 32 F 37 4 F 0 Adjustable 4 Defrosting Cycle 30 90Min 40Min A...

Страница 18: ...9 C 15 8 F 210 2 F Measured 16 Coil Temp 9 99 C 15 8 F 210 2 F Measured 17 Exhaust Temp 0 127 C C7 32 F 260 6 F Measured 18 Ambient Temp 9 99 C 15 8 F 210 2 F Measured 19 High Pressure Switch 0 Alarm when closing 1 Alarm when opening 2 Disable 1 Adjustable 20 Low Pressure Switch 0 Alarm when closing 1 Alarm when opening 2 Disable 2 Adjustable 21 Water Flow Switch 0 Close when water flow is abnorma...

Страница 19: ...urer s requirements when charging R32 gas and equipment maintenance This chapter focuses on special maintenance requirements for swimming pool heat pump with R32 gas Please refer to the technical service manual for detailed maintenance operation f Vacuumize completely before welding Welding can only be carried out by Professional personnel in service center 5 2 Failure solution and code Protection...

Страница 20: ...late E3 High Exhaust Temperature Protection 1 Check whether the refrigerant of the system is leaked If the refrigerant leaks repair the leak point and vacuum it again then charge the refrigerant according to the type and weight of the refrigerant on the nameplate 2 Replace exhaust temperature sensor 3 Replace PCB control board P8 Excessive Low Temp of Water Outlet When Cooling No need to deal with...

Страница 21: ...n 5 seconds to enter the compatible network mode power indication when power is on corresponds to the lower indicator light WIFI status After WIFI is connected corresponding to the lower indicator light is always on communication instructions when entering the default distribution network flashes quickly corresponding to the lower indicator When entering compatible distribution network flashes slo...

Страница 22: ... 2 1 P a g e 2 2 4 0 H E A T P U M P M I C R O W E L L H P 6 2 Wi Fi Function 6 2 1 Software Installation Method 1 Search Smart life in your APP store install Click GET to install Method 2 Scan the QR code below 6 2 2 Software Start up After installation click on your desktop to start up Smart Life Smart Life ...

Страница 23: ... I C R O W E L L H P 6 2 3 Software registration and configuration 6 2 3 1 Registration Users don t have account can click Register to create an account Register Enter your phone number Get Verification Code Enter Verification Code Set Code After registration you need to Create a Home Create a Home Set Home Name Set Home Location Add Rooms 1 2 3 4 ...

Страница 24: ... m a n u a l H P 1 0 0 0 1 4 0 0 1 7 0 0 G r e e n V e r s i o n 0 1 2 0 2 1 P a g e 2 4 4 0 H E A T P U M P M I C R O W E L L H P 6 2 3 2 Account ID Password Login Existing accounts can be logged in directly in the following order 1 2 3 4 ...

Страница 25: ... u s e r m a n u a l P a g e 2 5 4 0 V e r s i o n 0 1 2 0 2 1 H E A T P U M P M I C R O W E L L H P If you forget your password you can choose to login with your verification code and select Forget Password Enter your phone number Get verification code 1 2 3 4 1 2 3 4 ...

Страница 26: ...odule configuration steps Method 1 Intelligent distribution network mode Step 1 When power is on if there is no distribution network it will automatically connect through the default distribution network by default At this moment the indicator light under flashes rapidly 2 times per second mobile phone can connect it Manually enter the intelligent distribution network mode 10s after power on long ...

Страница 27: ...he phone s WIFI function and connect to the WIFI hotspot The WIFI hotspot must be able to connect to the Internet normally Step 3 Open the smart life APP log in into the main interface click on the top right corner or add equipment of the interface enter the equipment type selection the Large Home Appliances select Smart Heat Pump equipment and add equipment into the interface ...

Страница 28: ... the interface of Add Equipment and confirm that the line controller has selected the intelligent network distribution mode After the indicator light under flashes rapidly click Confirm indicator rapidly blink Enter the WIFI connection interface enter the WIFI password of the mobile phone it must be the same as the WIFI of the mobile phone click Next and then directly enter the connected state of ...

Страница 29: ... I n s t a l l a t i o n a n d u s e r m a n u a l P a g e 2 9 4 0 V e r s i o n 0 1 2 0 2 1 H E A T P U M P M I C R O W E L L H P Step 5 When Scan devices Register on Cloud Initialize the device are all completed connection succeed 1 2 3 ...

Страница 30: ...ly 1 time every 3s mobile phone can connect it Step 2 3 are the same with intelligent distribution network above Step 4 After entering the add device interface click AP Mode in the upper right corner Enter the AP mode to add the device interface confirm that the compatible network distribution mode has been selected icon flashes and click Confirm indicator rapidly blink The interface of WiFi conne...

Страница 31: ...U M P M I C R O W E L L H P click Go to Connect Enter the mobile phone WiFi connection interface find the SmartLife_XXXX connection and the APP will automatically enter the device connection state Step 5 is the same with intelligent distribution network above Note If the connection is failed please enter the compatible network mode 3 4 5 6 ...

Страница 32: ...t pump to enter the operation interface 1 Back 2 More You can change device name select device installation location check networking status add Shared users create device cluster view device information and more 3 Setting temperature adjustment The white circle slides counterclockwise to reduce the temperature but clockwise to increase the temperature 4 Target temperature 5 Current temperature 6 ...

Страница 33: ...U M P M I C R O W E L L H P rename the device Device sharing To share a bound device the user should do so in the following order After successful sharing the list will be added to show the person Shared If you want to delete the account you shared to cross the selected account to the left and delete it The user interface is as follows 1 2 ...

Страница 34: ...e n V e r s i o n 0 1 2 0 2 1 P a g e 3 4 4 0 H E A T P U M P M I C R O W E L L H P Enter the account of the Shared click Done and the share success list shows the newly added account of the Shared The interface of the person to be Shared is as follows The received shared device 1 2 3 ...

Страница 35: ...l a t i o n a n d u s e r m a n u a l P a g e 3 5 4 0 V e r s i o n 0 1 2 0 2 1 H E A T P U M P M I C R O W E L L H P is displayed Click it to operate and control the device Mode settings click on the main interface to switch modes select what you need ...

Страница 36: ...2 0 2 1 P a g e 3 6 4 0 H E A T P U M P M I C R O W E L L H P timer setting Click on the main interface to enter timer setting interface as shown below click to add timer After entering timer setting swipe up down to set timer set up repeat weeks and on off then click save to save your settings as follows 1 ...

Страница 37: ...ice and enter intelligent distribution mode again The indicator light under flashes rapidly for 3min The network can be rematched or quit it if no operation within 3 minutes By APP Click on the top right corner of the main interface to enter the device details interface and click device removal to enter intelligent distribution mode Indicator light under flashes rapidly for 3min The network can be...

Страница 38: ...I n s t a l l a t i o n a n d u s e r m a n u a l H P 1 0 0 0 1 4 0 0 1 7 0 0 G r e e n V e r s i o n 0 1 2 0 2 1 P a g e 3 8 4 0 H E A T P U M P M I C R O W E L L H P 2 1 ...

Страница 39: ...pment by yourself Improper operation may cause danger 6 In case of risking safety inspection must be carried before the maintenance or repairing for heat pumps with R32 gas 7 2 Warranty Your heat pump is covered by warranty For particular conditions of this warranty in terms of warranty period and subject please refer to your local regulations and or agreement with your distributor reseller or ins...

Страница 40: ... 0 0 G r e e n V e r s i o n 0 1 2 0 2 1 P a g e 4 0 4 0 H E A T P U M P M I C R O W E L L H P Distributed by Manufacturer MICROWELL spol s r o SNP 2018 42 927 01 Sala Slovakia tel 421 31 702 0540 fax 421 31 702 0542 e mail microwell microwell sk w w w m i c r o w e l l e u ...

Отзывы: