9  Modbus RTU communication 

Modbus RTU register address definition of electromagnetic flowmeter energy meter 

Protocol 
address 
Decimal 

Decimal

 

Protocol 

address 
Hexadecimal 

HEX

 

Data Format 

Register definition 

4112 

0x1010 

Float Inverse 

Instantaneous flow floating point representation 

4114 

0x1012 

Float Inverse 

Floating point representation of instantaneous flow rate

m/s

 

4116 

0x1014 

Float Inverse 

Reserve 

4118 

0x1016 

Float Inverse 

Floating point representation of fluid resistance 

4120 

0x1018 

Long Inverse 

Integer part of flow cumulative value 

4122 

0x101A 

Float Inverse 

Decimal part of flow cumulative value 

4124 

0x101C 

Unsigned short 

Instantaneous cooling capacity unit 
0

MJ/h;        1

GJ/h    2

KWh/h;      3:    MWh/h 

4125 

0x101D 

Unsigned short 

Total refrigeration unit 
0

MJ

    1

GJ      2

KWh

  3

MWh 

4126 

 

0x101E 

 

Unsigned short 

 

Instantaneous flow unit 
0: l/s

  1

l/m      2

l/h

3

m³/s    4: m³/m

5

m³/h 

4128 

0x1020 

Unsigned short 

Instantaneous heat unit 
0

MJ/h;    1

GJ/h    2

KWh/h;    3: MWh/h 

4129 

0x1021 

Unsigned short 

Flow cumulative total unit 
0: L

    1: m³

2: GAL

  3: GAL

4:kg

        5:T

 

4130 

0x1022 

Unsigned short 

Pressure range 
0

0.6MPa1

1.6MPa 

4131 

0x1023 

Unsigned short 

Total heat unit 
0

MJ

1

GJ      2

KWh;    3:MWh 

4132 

0x1024 

Unsigned short 

Empty Pipe alarm    0

Normal

1

Alarm 

4133 

0x1025 

Unsigned short 

System alarm      0

Normal

1

Alarm 

4134 

0x1026 

Float Inverse 

Instantaneous heat flow 

4136 

0x1028 

Long Inverse 

Total accumulated heat value 

4138 

0x102A 

Float Inverse 

Decimal value of total calorie accumulation 

4140 

0x102C 

Unsigned short 

Input temperature (

4141 

0x102D 

Unsigned short 

output temperature (

4142 

0x102E 

Long Inverse 

Total cumulative value of cooling capacity 

4144 

0x1030 

Float Inverse 

Total cumulative cooling capacity decimal value 

4146 

0x1032 

Float Inverse  Instantaneous cooling capacity 

 

Communication connection RS485 or RS232, Baud rate range 600-9600, communication parameter: 

Baud rate, N, 8, 1. 

Instrument terminal T+

A

, T-

B

and COM. 

Communication protocol conforms to MODBUS RTU protocol. In instruction table register number is 

register address. 

Composition of communication information: Address code - Function code - Data segment - CRC, A 

message is sent and received continuously, and the character interval cannot be greater than one 

character, otherwise it is regarded as the beginning of a new message or the end of the previous 

message. The message body consists of hexadecimal numbers. 

Содержание MFE600H Series

Страница 1: ...MFE600H Operation Manual V2 1...

Страница 2: ...f instrument energy meter 19 7 1 Flow parameter 19 7 2 Output parameters 20 7 3 Flow meter location 21 7 4 Temperature parameter 21 7 5 Total amount setting parameters 22 8 Installation requirements 2...

Страница 3: ...stitutions 2 Specifications Table 1 Diameter Flange type DN25 DN400 level of accuracy level 2 Electrode type Standard fixed electrode antifouling electrode Structure type Integrated type separated typ...

Страница 4: ...ect 220V AC or 24V DC wiring to avoid power wiring faults When wiring select the corresponding power terminal to connect to the power line according to the product specifications and then connect to t...

Страница 5: ...according to the required output form See Table 3 for the specific meaning of the integrated electromagnetic flowmeter wiring terminals Table 3 Terminal definition of separated type Terminal Symbol F...

Страница 6: ...and a converter and is ready for immediate use when it is supplied All operating data is factory set according to your order please refer to the provided inspection report for details After turning on...

Страница 7: ...limit The real time flow value is higher than the set upper limit of alarm value 5 Lower flow limit The real time flow value is lower than the set lower limit of alarm value 5 Operation 5 1 Key instru...

Страница 8: ...e done in the secondary menu password modification item Note If you modify level 1 or level 2 password please remember the modified password 6 Parameter setting and method 6 1 Report query In the main...

Страница 9: ...tructions Parameter Range 1 Language English 2 Communication address Range 0 255 3 Communication rate Rate 1200 2400 4800 9600 14400 Check no check odd parity Check even parity check 4 Pipe Diameter 3...

Страница 10: ...nt Yes No 12 Flow integration unit 1m 0 1m 0 01m 0 001m 1L 0 1L 0 01L 0 001L 1t 0 1t 0 01t 0 001t 1kg 0 1kg 0 01kg 0 001kg 1gal 0 1gal 0 01gal 0 001gal 1ig 0 1ig 0 01ig 0 001ig 13 Pulse output method...

Страница 11: ...geable 18 Converter coefficient Factory set unchangeable 19 Converter code value Factory set unchangeable 20 Empty pipe alarm Yes No 21 Empty pipe alarm threshold value Factory set unchangeable Empty...

Страница 12: ...Electrode alarm threshold 0 999 9 adjustable 27 Resistance coefficient 28 Current zero point correction Factory set unchangeable 29 Current full scale correction Factory set unchangeable Current Full...

Страница 13: ...on linear correction point 2 36 Non linear correction point 3 37 Non linear correction point 4 NonlineCorrenct4 V 1 2000m s K 1 0000 NonlineCorrenct3 V 0 9000m s K 1 0000 NonlineCorrenct2 V 0 6000m s...

Страница 14: ...t test 20mA 2000Hz 10mA 1000Hz 4 16mA 20Hz 4mA 1Hz 43 Density of measured fluid As customers request 44 Change rate limit value 0 100 adjustable 45 Insensitive time 0 99S adjustable Slope Limit Time 1...

Страница 15: ...ord modification adjustable 50 Date YY MM DD adjustable 51 Time HH MM SS adjustable 52 System running time 53 System time adjustable System Time 2021 03 08 11 57 54 System Run Time 1 Day 13 Hour 34 Mi...

Страница 16: ...01GJ 0 1GJ 1GJ 0 0001KWh 0 001KWh 0 01KWh 0 1KWh 1KWh 0 0001MWh 0 001MWh 0 01MWh 0 1MWh 1MWh 60 Cool accumulation unit 0 0001MJ 0 001MJ 0 01MJ 0 1MJ 1MJ 0 0001GJ 0 001GJ 0 01GJ 0 1GJ 1GJ 0 0001KWh 0 0...

Страница 17: ...perature difference 67 Cut off the difference between cold and heat Enable Disable 68 Heat meter initial measurement temperature 69 Cold meter initial measurement temperature Cold Start T 0 0000 Heat...

Страница 18: ...PT1000 calibration 1 Access standard resistance 1 automatic correction 77 Input PT1000 calibration 2 Access standard resistance 2 automatic correction In Pt1000 Check 2 Input R 1 5k Measure 1498 0 In...

Страница 19: ...h MJ h KWh h MWh h 3 Cooling flow unit Choose GJ h MJ h KWh h MWh h 4 Temperature difference signal removal Setting 5 Total heat unit Choose 0 0001MJ 0 001M 0 010MJ 0 100MJ 1 000MJ 0001GJ 0 001GJ 0 0...

Страница 20: ...tomatic correction 17 Inlet PT check 2 Access standard resistance 2 Automatic correction 18 Outlet PT check 1 Access standard resistance 1 Automatic correction 19 Outlet PT check 2 Access standard res...

Страница 21: ...tings are prohibited 7 2 Output parameters 7 2 1 Current output mode There are six ways of current output of electromagnetic flowmeter energy meter Flow output Heat output Cooling output Cold and heat...

Страница 22: ...pulse output indicates the cold and hot state the heat is at low level and the cold is at high level Flow direction output When the pulse output indicates the flow direction the forward direction is...

Страница 23: ...l value of the flow which is mainly used for instrument maintenance and instrument replacement The flow cumulative amount can be modified generally cannot exceed the maximum value counted by the count...

Страница 24: ...mended When there are valves at the front and rear of the flowmeter the front and rear straight pipe must meet the front 5D and rear 2D installation methods at least and the valve must be fully open a...

Страница 25: ...e needed between the flowmeter and the tail end of the elbow as shown in Figure 5 Figure 5 When energy meter is installed at the back end of the expanded diameter pipe the flowmeter and the back end o...

Страница 26: ...ference sources as much as possible such as pumps and other equipment to avoid their interference on the measurement as shown in Figure 8 Figure 8 In order to ensure the upstream piping conditions req...

Страница 27: ...re range 0 0 6MPa1 1 6MPa 4131 0x1023 Unsigned short Total heat unit 0 MJ 1 GJ 2 KWh 3 MWh 4132 0x1024 Unsigned short Empty Pipe alarm 0 Normal 1 Alarm 4133 0x1025 Unsigned short System alarm 0 Normal...

Страница 28: ...en the low byte The high byte is the byte where the sign bit and exponent bit in the floating point number are located and the low byte is the byte where the mantissa is located Above D0 D1 D2 and D3...

Страница 29: ...de representation of 2n The bit field length of the mantissa is 23 bits in the figure but it is actually24 bits This bit is invisible and its value is fixed at 1 which means that the effective digits...

Страница 30: ...www microsensorcorp com...

Отзывы: