background image

6

ADJUSTABLE OUTDOOR DRY BULB CHANGEOVER

 

(-DWDS 

Models) —

 

For this control mode, the outdoor temperature is compared 

to a selectable set point on the OAT sensor. If the outdoor air temperature 

is  above  the  set  point,  the 

economizer will adjust the outdoor air 

dampers to minimum position. If the outdoor air temperature is below 

the set point, the position of the outdoor air dampers will be controlled 

to provide free cooling using outdoor air. When in this mode, the Free 

Cool LED next to the outdoor enthalpy set point (ABCD) potentiometer 

will be on. The changeover temperature set point is controlled by the dip 

switches on the sensor. See Fig. 12 for the switch positions corresponding 

to the temperature changeover values. The ABCD potentiometer on the 

controller should be turned fully clockwise (CW) to the “D” position.

OUTDOOR ENTHALPY CHANGEOVER (-DWES Models) 

 When the outdoor air enthalpy rises above the outdoor enthalpy 

changeover  set  point,  the  outdoor-air  damper  moves  to  its  minimum 

position The outdoor enthalpy changeover set point is set with the outdoor 

enthalpy set point (ABCD) potentiometer on the 

economizer controller. 

The set points are A, B, C, and D (See Figs. 11, 14 and 15). The factory-

installed 620-ohm jumper must be in place across terminals SR and SR+ 

on economizer controller. (See Fig. 7). When not using CO2 sensors, set 

the DCV Max potentiometer to completely closed (CCW) to insure that 

the Minimum Position potentiometer functions correctly.

DIFFERENTIAL ENTHALPY CONTROL (-DWZS Models)

 — For 

differential 

enthalpy control, the 

economizer controller uses two enthalpy 

sensors,  9901-0018  in  the  outside  air  and  9901-0018  in  the  return 

airstream. The economizer controller compares the outdoor air enthalpy 

to the return air enthalpy to determine economizer damper position. The 

controller selects the lower enthalpy air (return or outdoor) for cooling. 

For example, when the outdoor air has a lower enthalpy than the return 

air, the 

economizer opens to bring in outdoor air for free cooling. Mount 

the return air enthalpy sensor in the return air duct. (See Fig. 7 and 13) 

When using this mode of changeover control, turn the outdoor enthalpy 

set point (ABCD) potentiometer fully clockwise to the D setting.

POWER EXHAUST SET POINT ADJUSTMENT

—If the optional 

power exhaust accessory is installed, the exhaust set point will determine 

when the power exhaust fan runs based on damper position. The set point 

is modified with the Exhaust Fan Set Point (EXH SET) potentiometer. 

(See Fig. 11) The set point represents the damper position above which 

the exhaust fans will be turned on. When there is a call for exhaust, the 

economizer

 controller provides a 45 ± 15 second delay before exhaust 

fan activation to allow the dampers to open. This delay allows the damper 

to reach the appropriate position to avoid unnecessary fan overload.

Fig. 13 - Differential Return Air Enthalpy Sensor

Mounting Location

Fig. 12 - Outdoor Air Temperature

Changeover Set Points

Economizer

Economizer

Controller

Grommet

Differential 

Enthalpy Sensor

Return Duct

(Field-Provided)

CAUTION

EQUIPMENT DAMAGE HAZARD

Failure to follow this caution may result in damage to equipment.

If a separate field-supplied transformer is used to power the IAQ 

sensor, the sensor must not be grounded or the 

economizer control 

board will be damaged.

!

FIXED DRY BULB OUTDOOR AIR TEMPERATURE SENSOR 

(-DWFS Models)

  —  For  this  control  mode  the,  the  outside  air 

temperature  is  compared  to  the  fixed  temperature  on  the  OA  sensor, 

which is 70 degrees.

If  the  outside  air  temperature  is  above  70  degrees  F,  the  economizer 

will adjust the outdoor dampers to minimum position. If the outdoor air 

temperature is below 70 degrees, the position of the outside air damper 

will be controlled to provide free-cooling using outside air.

  When  in  the  free-cooling  mode,  the  Free  Cooling  LED  next  to  the 

enthalpy  potentiometer  will  be  on.  The  ABCD  potentiometer  on  the 

controller should be adjusted to the “D” position.

Содержание ECD-SRT SA Series

Страница 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTSA DW Install Guide...

Страница 2: ...Table of Contents Topic Page Number General 1...

Страница 3: ...trol ventilation is supported The economizer system utilizes gear drive technology with a direct mount spring return actuator that will close upon loss of power The economizer system comes standard wi...

Страница 4: ...12 Remove the indoor fan motor access panel See Fig 8 13 The supply air temperature sensor looks like an eyelet terminal or probe with wires running to it The sensor is located on the crimp end and i...

Страница 5: ...t Screw in Economizer Flanges Wiring Harness Damper Controller Economzier Fig 6 Rear Economizer Flange Installation ECD SRT12SA and ECD SRT34SA Only Unit Filter Rack Unit Base Economizer Hold Down Tab...

Страница 6: ...elow 70 degrees F On DWDS economizers the outside air temperature allowed for free cooling is adjustable on the C7660 sensor See figure 12 for details On DWES and DWZS economizers with a C7400 OA enth...

Страница 7: ...tage 1 W2 heat stage 2 and G fan The economizer control does not support space temperature sensors Connections are made at the thermostat section of the central terminal board located in the main unit...

Страница 8: ...mple when the outdoor air has a lower enthalpy than the return air the economizer opens to bring in outdoor air for free cooling Mount the return air enthalpy sensor in the return air duct See Fig 7 a...

Страница 9: ...7 Fig 14 Enthalpy Changeover Setpoints Fig 16 Proportional and Exponential Control Fig 15 W7212 Controller CONTROL CURVE CONTROL POINT APPROX o F o C AT 50 RH A 73 23 B 70 21 C 67 19 D 63 17...

Страница 10: ...tches the calculated value Measurement must be done with a separate thermometer or sensor accurate to 0 5 F because you have fooled the unit controls in step 2 above 5 If you are going to set the DCV...

Страница 11: ...ought into the building when the enthalpy is high In most cases the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications If normal...

Страница 12: ...nsor signals between minimum position and either maximum position DCV or fully open mixed air signal INPUTS OUTPUTS Demand Control Ventilation DCV Enthalpya Y1 Y2 Compressor N Terminalb Outdoor Return...

Страница 13: ...ces economizer in occupied mode If connected remove C7400 Enthalpy Sensor from terminals SO and Connect 1 2K ohm from 4074EJM Checkout Resistor kit purple sleeve across terminals SO and makes OA entha...

Страница 14: ...jumper from N terminal economizer goes into not occupied mode Motor remains at 45 degrees open Motor will move to position set by DCV MAX pot Adjust DCV MAX towards CW Adjust DCV MAX to fully CCW Rec...

Страница 15: ...harge temperature 3 Economizer logic 9901 1805 accepts input from discharge sensor and outside air sensor Analyzes input to control actuator modulation and economizer switching Logic also houses minim...

Страница 16: ...1 DA920 ECD SRT12SA DWXS Siemens Non Communicating Actuator Differential Adjustable Dry Bulb W7212 Controller 0688 0101 DE920 ECD SRT12SA DWZS Siemens Non Communicating Actuator Differential Enthalpy...

Страница 17: ...l Commuicating Actuator Differential Enthalpy W7220 JADE Controller N A ECH SRT34SA D00B X Belimo MFT Actuator No Controls Wiring For PremierLink RTU Open SystemVU N A ECH SRT34SA D00S 4 Siemens Non C...

Страница 18: ...ble Economizer Not Available Please Choose Dedicated Horizontal or Vertical Economizer 0699 0201 B0920 N A Convertible Economizer Not Available Please Choose Dedicated Horizontal or Vertical Economize...

Отзывы: