background image

2

ACCESSORIES LIST

The  economizer

  has  several  field-installed  accessories  available  to 

optimize performance. Refer to Table 4 for authorized parts and power 

exhaust descriptions

INSTALLATION

1. 

Turn off unit power supply(s) and install lockout tag.

2.  Remove the existing unit filter access panel. Raise the panel and 

swing the bottom outward. The panel is now disengaged from the 

track and can be removed. (See Fig. 2.)

3.  Remove the indoor coil access panel and discard. (See Fig. 2.)

4.  The economizer hood components are shipped with the economizer. 

Remove hood from packaging. The hood top and sides are shipped 

factory assembled.

NOTE:

 If the power exhaust accessory is to be installed on the unit, 

the 

hood shipped with the economizer will not be used and may be discarded. 

Save the aluminum filter for use in the power exhaust hood assembly.
5.  Insert the hood divider between the hood sides. (See Fig. 3) Secure 

hood divider with 2 screws (provided) on each hood side. Screws 

should go through the hood sides into the divider. The hood divider 

is also used as the bottom filter rack for the aluminum filter.  On 

hood for ECD-SRT05SA economizer install filter divider. (See Fig. 

4A.)

6.  Set the economizer upright. (See Fig. 5.)  
7.  Slide the damper assembly into the rooftop unit. (See Fig. 

5). On 

ECD-SRT12SA  and  ECD-SRT34SA  be  sure  to  engage  the  rear 

economizer flange under the tabs in the return-air opening of the 

unit base. (See Fig. 6)

8.  Secure the economizer to unit along side and bottom flanges 

using 

the screws provided.

9.  Remove the tape securing the relief dampers in place.

10.  Remove  and  save  the  12-pin  jumper  plug  from  the  unit  wiring 

harness (located in the upper left corner of the unit). Insert the 

economizer plug into the unit wiring harness.  Refer to Fig. 7 for 

wiring diagram.

NOTE: The 12-pin jumper plug should be saved for future use, in the 

event that the economizer is removed from the unit. The jumper plug is 

not needed as long as the economizer is installed.

11.  The outside air sensor may be taped to the front economizer 

divider 

plate for shipping purposes. Relocate sensor to operating position as 

shown in Fig. 1.

12.  Remove the indoor fan motor access panel. (See Fig. 8.)
13.  The supply air temperature sensor looks like an eyelet terminal or 

probe with wires running to it. The sensor is located on the “crimp 

end” and is sealed from moisture. Mount the supply air temperature 

sensor (provided) to the lower left section of the indoor fan blower 

housing. (See Fig. 9.) Use the screw provided and use existing hole. 

Connect  the  violet  and  pink  wires  to  the  supply  air  temperature 

sensor. (See Fig. 7.)

Table 3 - Economizer Sensor Usage

APPLICATION

Outdoor Air

Dry Bulb

ECD-SRT**SA-DWFS includes (MM PN 9901-0183) fixed dry 

bulb sensor. ECD-SRT**SA-DWDS includes 

(MM PN 9901-2251) C7660 adjustable dry bulb sensor

Single

Enthalpy

ECD-SRT**SA-DWES includes (MM PN 9901-0018) C7400 

OA enthalpy sensor

Differential

Enthalpy

ECD-SRT**SA-DWZS includes a (MM PN 9901-0018) C7400 

OA enthalpy and (MM PN 9901-0018) C7400 differential RA 

enthalpy

CO

2

 for

DCV Control

Using a

Wall-Mounted

CO

2

 Sensor

8002-WMDM

CO

2

 for 

DCV Control

Using a 

Duct-Mounted

CO

2

 Sensor

8002-XVDM

Table 4 - Economizer Field-Installed 

Propeller Power Exhausts and CO2

DESCRIPTION

PART NUMBER

ECD-SRT12SA Prop. Power Exhaust 208-230 v 1Ph

PPD-SRT12TA-D-1VC

ECD-SRT12SA Power Exhaust 460 v 3 Ph

PPD-SRT12TA-D-4VC

ECD-SRT34SA Power Exhaust 208-230 v 1 Ph

PPD-SRT34TA-D-1VD

ECD-SRT34SA Power Exhaust 460 v 3 Ph

PPD-SRT34TA-D-4VD

ECD-SRT05SA Power Exhaust 208-230 v 1 Ph

PPD-SRT05TA-D-1VD

ECD-SRT05SA Power Exhaust 460 v 3 Ph

PPD-SRT05TA-D-4VD

Return Air CO

2

 Sensor (4 to 20 mA)

8002-XVDM

CO

2

 Room Sensor (4 to 20 mA)

8002-WMDM

Fig. 1 - Economizer Component Locations 

(ECD- SRT12SA-DWDS Shown)

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury and/or 

death. 
Disconnect power supply and install lockout tag before attempting to 

install accessory.

!

W7212

CONTROLLER

OUTSIDE AIR

DAMPER

RELIEF 

DAMPER

Table 2 - Package Contents

PACKAGE NO.

QTY

CONTENTS

ECD-SRT12SA

ECD-SRT34SA

1

1

1

18

1

1

Hood Top and Sides

Hood Divider

Aluminum Filter

Screws

Damper Assembly

Supply Air Temperature Sensor

ECD-SRT05SA

1

1

1

2

1

1

1

Hood Top and Sides

Hood Divider

Hood Filter Divider

Aluminum Filters

Hardware Bag

Damper Assembly

Supply Air Temp Sensor

Note: ECD-SRT**-DWZS models also include a differential 

enthalpy in hardware bag for field installation in return duct.

Содержание ECD-SRT SA Series

Страница 1: ...Foremost HVAC Accessory Manufacturer Economizer ECD SRTSA DW Install Guide...

Страница 2: ...Table of Contents Topic Page Number General 1...

Страница 3: ...trol ventilation is supported The economizer system utilizes gear drive technology with a direct mount spring return actuator that will close upon loss of power The economizer system comes standard wi...

Страница 4: ...12 Remove the indoor fan motor access panel See Fig 8 13 The supply air temperature sensor looks like an eyelet terminal or probe with wires running to it The sensor is located on the crimp end and i...

Страница 5: ...t Screw in Economizer Flanges Wiring Harness Damper Controller Economzier Fig 6 Rear Economizer Flange Installation ECD SRT12SA and ECD SRT34SA Only Unit Filter Rack Unit Base Economizer Hold Down Tab...

Страница 6: ...elow 70 degrees F On DWDS economizers the outside air temperature allowed for free cooling is adjustable on the C7660 sensor See figure 12 for details On DWES and DWZS economizers with a C7400 OA enth...

Страница 7: ...tage 1 W2 heat stage 2 and G fan The economizer control does not support space temperature sensors Connections are made at the thermostat section of the central terminal board located in the main unit...

Страница 8: ...mple when the outdoor air has a lower enthalpy than the return air the economizer opens to bring in outdoor air for free cooling Mount the return air enthalpy sensor in the return air duct See Fig 7 a...

Страница 9: ...7 Fig 14 Enthalpy Changeover Setpoints Fig 16 Proportional and Exponential Control Fig 15 W7212 Controller CONTROL CURVE CONTROL POINT APPROX o F o C AT 50 RH A 73 23 B 70 21 C 67 19 D 63 17...

Страница 10: ...tches the calculated value Measurement must be done with a separate thermometer or sensor accurate to 0 5 F because you have fooled the unit controls in step 2 above 5 If you are going to set the DCV...

Страница 11: ...ought into the building when the enthalpy is high In most cases the normal heating and cooling processes are more than adequate to remove the humidity loads for most commercial applications If normal...

Страница 12: ...nsor signals between minimum position and either maximum position DCV or fully open mixed air signal INPUTS OUTPUTS Demand Control Ventilation DCV Enthalpya Y1 Y2 Compressor N Terminalb Outdoor Return...

Страница 13: ...ces economizer in occupied mode If connected remove C7400 Enthalpy Sensor from terminals SO and Connect 1 2K ohm from 4074EJM Checkout Resistor kit purple sleeve across terminals SO and makes OA entha...

Страница 14: ...jumper from N terminal economizer goes into not occupied mode Motor remains at 45 degrees open Motor will move to position set by DCV MAX pot Adjust DCV MAX towards CW Adjust DCV MAX to fully CCW Rec...

Страница 15: ...harge temperature 3 Economizer logic 9901 1805 accepts input from discharge sensor and outside air sensor Analyzes input to control actuator modulation and economizer switching Logic also houses minim...

Страница 16: ...1 DA920 ECD SRT12SA DWXS Siemens Non Communicating Actuator Differential Adjustable Dry Bulb W7212 Controller 0688 0101 DE920 ECD SRT12SA DWZS Siemens Non Communicating Actuator Differential Enthalpy...

Страница 17: ...l Commuicating Actuator Differential Enthalpy W7220 JADE Controller N A ECH SRT34SA D00B X Belimo MFT Actuator No Controls Wiring For PremierLink RTU Open SystemVU N A ECH SRT34SA D00S 4 Siemens Non C...

Страница 18: ...ble Economizer Not Available Please Choose Dedicated Horizontal or Vertical Economizer 0699 0201 B0920 N A Convertible Economizer Not Available Please Choose Dedicated Horizontal or Vertical Economize...

Отзывы: