4.0 WebUI Configuration
Port
Values (Port #)
Active Timeout
Values (seconds)
Enter the port number on the IPn3G in which to listen for incoming Modbus
messages.
502
Define the active timeout in seconds.
300
Slave ID
Each Modbus slave device must have a unique address, or Slave ID. Enter
this value here as required by the Modbus Host System.
Values (value)
1
Coils Address Offset
Enter the Coils Address offset as required by the Master.
Values (value)
0
Input Address Offset
Enter the Input Address offset as required by the Master.
Values (value)
0
Register Address Offset
Enter the Register Address offset as required by the Master.
Values (value)
0
Master IP Filter Set
It is possible to only accept connections from specific Modbus Master IP’s,
to use this feature enable the Master IP Filter and specify the IP Addresses
in the fields provided.
Values (selection)
Disable /
Enable
Содержание IPN3G
Страница 112: ...Microhard Systems Inc 112 4 0 WebUI Configuration 4 10 8 3 Modbus Modbus Data Map Image 70 Advanced Modbus Data Map...
Страница 187: ...Microhard Systems Inc 187 Appendix E VPN Example Step 3 Add and configure a Gateway to Gateway VPN tunnel for the IPn3G...
Страница 188: ...Microhard Systems Inc 188 Appendix E VPN Example Step 4 Using Cisco ASDM configure the ASA 5505...
Страница 189: ...Microhard Systems Inc 189 Appendix E VPN Example Step 4 continued...
Страница 190: ...Microhard Systems Inc 190 Appendix E VPN Example Step 4 continued...
Страница 237: ...Microhard Systems Inc 237 Appendix J Digital I O Example Output driving external relay...
Страница 238: ...150 Country Hills Landing N W Calgary AB Canada T3K 5P3 Phone 403 248 0028 Fax 403 248 2762 www microhardcorp com...