24. SETTING’S FORM
Relay Type
IM30-GLF
Station :
Circuit :
Date :
/
/
Firmware Ver.
Relay Serial Number :
Power Supply
24V(-20%) / 110V(+15%) a.c.
24V(-20%) / 125V(+20%) d.c.
In
1A
5A
80V(-20%) / 220V(+15%) a.c.
90V(-20%) / 250V(+20%) d.c.
Ion
1A
5A
RELAY PROGRAMMING
Variable
Description
Setting
Range
Default
Setting
Actual
Setting
Test Result
Pick-up Reset
NodAd
Identification number for serial connection
1 - 250
-
1
Fn
Mains frequency
50 - 60
Hz
50
In
Rated primary current of the phase C.Ts.
1 - 9999
Ap
500
On
Rated primary current of the C.Ts.
1 - 9999
Ap
500
Uns
Rated secondary voltage of Vts (phase to phase)
100 - 125
V
100
Ib
Generator’s rated current as p.u. of Cts rated
current
0.5 - 1.1
In
0.5
F(I>)
Oper. charact. of the low-set overcurrent element
D, SI
D
I>
Trip level of low-set overcurrent element
1 - 2.5 - Dis
Ib
1.0
tI>
Trip time delay of the low-set overcurrent element
0.05 - 30
s
0.05
I>>
Trip level of high-set overcurrent element
1
– 12 - Dis
Ib
1
tI>>
Trip time delay of the high-set overcurrent element
0.05 - 3
s
0.05
O>
Trip level of earth fault element
0.02-0.4-Dis
On
0.02
tO>
Trip time delay of low-set earth fault element
0.05 - 30
s
0.05
1Is
Generator’s max. continuos negative sequence
current rating
0.05-0.5-Dis
Ib
0.05
Ks
Time multiplier of the I
2
t time-current curve
5 - 80
s
5
tc
Cooling time from trip level to cold state
10 - 1800
s
10
2Is
Negative sequence current alarm level
0.03 - 1 - Dis
Ib
0.03
t2Is
Independent trip time delay of alarm element
1 - 100
s
1
Ir>
Trip level of the reverse power element
0.02-0.2-Dis
In
0.02
tIr>
Indep. trip time delay of reverse power element
0.1 - 60
s
0.1
=
Impedance characteristic angle
0 - 330
C
270
K
1
Diameter of the circle
50 - 300
%Zb
300
K
2
Offset of the circle including the underimpedance
tripping zone
5 - 50
%Zb
50
tz
Trip time delay of the underimpedance element
0.2 - 60
s
0.2
ti
Integration time of underimpedance element.
0 - 10
s
0
tBF
Max. reset time delay of the instantaneous
elements after tripping
0.05 - 0.5
s
0.05