IM30-GLF
Doc. N° MO-0062-ING
Rev.
3
Date
14.02.2005
Copyright 2010 - Microener
Firmware:
2.0X
Pag
8
of
31
2.3.4 - F46 - Current unbalance : Measurement of RMS Negative Sequence Current I
2
F1 46
: I
2
2
t = K (adiabatic heating)
Generator’s continuous I
2
rating
Setting
1Is
= Dis blocks function’s operation
:
1Is
= (0.05-0.5)Ib, step 0.01Ib
Time multiplier
:
Ks
= (5-80)s, step 1s
Trip time when I
2
= I
b
Trip time delay
2
b
2
h
)
/I
(I
Ks
t
Heat accumulation only operates if I
2
[1Is]
Cooling time from trip level to the status corresponding to
the operation at I
2
=[1Is]
:
tc
= (10-1800)s, step 1s
Cooling time
t
I
I
Ks
[tc]
t
2
b
2
l
: t
l
= [tc] when
Ks
t
I
I
2
b
2
Cooling only takes places if
1Is
I
I
b
2
(see curves TU0312 Attachment. B)
F2 46
: Alarm
Alarm level
Setting
2Is
= Dis blocks function’s operation
:
2Is
= (0.03-1)Ib, step 0.01Ib
Independent trip time delay
:
t2Is
= (1-100)s, step 1s
2.3.5 - F32 - Reverse active power
Active current setting range
Setting
Ir>
= Dis blocks function’s operation
:
Ir>
= (0.02-0.2)In, step 0.01In
Operation level
: = Ic cos (
c-180°)
[Ir]
Independent trip time delay
:
tIr>
= (0.1-60)s, step 0.1s
Operation zone
: (-90°+180°)<
c<(90°+180°)