MC2-30M
Doc. N°
MO-0495-ING
Copyright 2018
Date
17.03.2022
Rev.
2
Pag.
5
of
64
2. General
The main features of the relays are:
User friendly front face with hi-resolution graphic display (240x128), 10 programmable signal Leds, 6 push-
buttons (configurable) and four push-button for complete local managemen, USB for local communication.
Eight
user programmable Output Relays.
Eight
opto-isolated, self powered Digital Inputs.
Additional RS485 communication port
Input currents are supplied to 3 current transformers: measuring phase currents.
An additional internal CT directly measures the residual (Zero Sequence) current of the three inputs.
Current inputs can be 1 or 5A: selection between 1A or 5A is made by movable jumpers provided inside the
Relay.
2.1 - Power Supply
The relay can be fitted with two different types of
power supply
:
Type 1
24V(-20%) / 110V(+15%) a.c.
24V(-20%) / 125V(+20%) d.c.
Type 2
80V(-20%) / 220V(+15%) a.c.
90V(-20%) / 250V(+20%) d.c.
Before energizing the unit check that supply voltage is within the allowed limits.
3. Front Panel