MC2-30M
Doc. N°
MO-0495-ING
Copyright 2018
Date
17.03.2022
Rev.
2
Pag. 42
of
64
17.15 - Function:
MotSt
(Motor Start)
Oper.Levels
→
Im
0.1
In
(0.05
÷
1)
step
0.01 In
Timers
→
tfst
0.1
s
(0.02
÷
1)
step
0.01 s
→
tst
120
s
(10
÷
120)
step
0.01 s
17.15.1 - Description of variables
Im
: Minimum operation level
tfst
: Motor start filter time
tst
: Motor starting time; 2xtst Inhibition time of the locked rotor function
17.16 - Function:
LR
(Locked Rotor – Rotor jam)
Status
→
Enab.
Yes
[No / Yes]
Oper.Levels
→
ILR
1
In
(1
÷
5)
step
0.01 In
Timers
→
tLR
120
s
(1
÷
120)
step
0.01 s
17.16.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
ILR
: Minimum operation level
tLR
: Trip time delay
17.17 - Function:
StNo
(Limitation Start Number)
Status
→
Enab.
Yes
[No / Yes]
Oper.Levels
→
StNo
10
In
(1
÷
60)
step
1
Timers
→
tstNo
600
s
(60
÷
3600)
step
60
s
→
tBst
600
s
(60
÷
3600)
step
60
s
17.17.1 - Description of variables
Enab.
: Function enabling (No = Disable / Yes = Enable)
StNo
: Maximum number of starting allowed within te time tStNo
tstNo
: Time in to which the StNo is counted
tBst
: Restart inhibition time after tripping StNo