GENERAL WIRING INFORMATION
GENERAL WIRING INFORMATION
•
Wiring must be performed by qualified personnel / certified electrician.
.
•
Familiarize yourself with the content of the manual following before commencing with the
wiring.
•
The line voltage “AC” applied must comply with the inverter’s specified input voltage
.
•
The AC connections are located at the top of the inverter under the wiring terminal cover.
•
Do not connect the AC output of the inverter directly to another AC source.
•
The inverter is not designed for parallel operation with another inverter.
•
If an electrical load distribution board or sub distribution board is fed from the inverter AC
output and the load is also required to be powered from another AC source, the AC load, AC
source and the inverter output should be connected to a manual or automatic transfer switch.
•
An earth leakage must be fitted at the inverter AC output and not on the AC source input line.
•
Make sure the BATTERY INPUT CIRCUIT BREAKER is OFF before attempting any wiring.
•
Battery interconnection cables must be a minimum of 35mm² and as short as possible.
•
Connect the Positive terminal of the inverter battery cable to the Positive post of the battery
and connect the Negative terminal of the inverter battery cable to the Negative post of the
battery.
.
Warning! The inverter battery input is not reverse polarity protected.
Reverse polarity will damage the unit!!
Please Note:
This Inverter is pre-programmed with a set of default values.
These settings might not be correct for your battery type.
Please contact your battery supplier for your battery specifications
“Battery Float Voltage, Boost Voltage, Boost to Float Time “Absorb Time”
and program the Inverter accordingly.